2026-10-12
52 minutes ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-Z4B-T1-&-443-PR1-T1
|
Repare sensor temperature Preheater + Clean UP TAD
|
Do repare sensor temperature 443 Z4B T1 found cable short at temperature transmitter service cable also cross check temperature compare reading local at CCR result different 5 degree celsius to 7 degree celsius. Clean up temperature IR TAD for flange probe ad lens of sensor result reading temperature normal ( RIZAL & ANDRI )
|
|
2026-10-12
3 hours ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-473-CC1-&-463-KL1
|
PMR critical motor CM & CC & KL
|
Clean up area motor and filter motor. Measure vibration-noise-temperature of FS and LS. Add grease motor 25 times and 30 times of FS and LS to make vibration below 4 mm/s and noise below 2 gE. Check at ER4 and ER5 for RPM-KW-Voltage-Ampere-Temperature and write at data check sheet ( MUHAIMIN & DADANG )
|
|
2026-10-12
3 hours ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR critical motor RM & PH
|
Clean up area motor and filter motor. Measure vibration-noise-temperature of FS and LS. Add grease motor 15 times and 25 times of FS and LS to make vibration below 4 mm/s and noise below 2 gE. Check at ER4 and ER3 for RPM-KW-Voltage-Ampere-Temperature and write at data check sheet note fan of south side 443 FN1 not working make notification ( AGUS & ADI )
|
|
2026-10-09
2 days ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1
|
Replace Breaker + Test Signal Upgrade IKGA+ activation signal pressure
|
Replace breaker and do test signal of upgrade analyzer 463 2K1 also activation signal pressure result good ( AGUS & MUHAIMIN & DADANG )
|
|
2026-10-09
3 days ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Do clean up flange probe-sample line-filter sample line-diaphragm pump-filter balston from dirty of dust coal use instrument air supply also water for filter sample line. Check humidity sensor and replace humidity result function humidity sensor good also filter humidity good condition ( RIZAL & ANDRI )
|
|
2026-10-09
3 days ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Report Completly PMR and WBI (Sep-Okt 2026), create SOT , TO October 2026
|
Do complete data check sheet PMR analyzer L63 2K1-L63 2k2-L63 2K3-483 2K1-463 2K1-443 2K1-423 2K1 for 1st week of October 2026; PMR critical motor area CM-CC-KL-RM-PH for 1st weeks of October 2026. Create SOT for October 2026 ( JAJAT & ADI & EDI )
|
|
2026-10-08
4 days ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
PMR service CEMS
|
Do clean up purge air unit and filter motor of dust hunter and flowsic.-swivel window T/R also R-flange with tube of T/R from dirty of dust use instrument air supply also equipment cleaning tools & R unit alignment T/r also R unit result ok-transducer probe A also transducer B from dirty of dust use instrument air supply also equipment cleaning tools-CEMS room also filter cabinet MCS 100 E-gas CEMS room from dirty of dust use equipment cleaning tools and instrument air supply ( RIZAL & ANDRI )
|
|
2026-10-08
4 days ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-EL1-&-WBI-SUMP-PUMP
|
PMR Serv. Elevator PH NAR1 & WBI Sump pump El + activation temperature control 8th floor
|
Do WBI sump pump electrical at room L63 HS1-IDO tank-L1C BC1-L1BC4 test function sump pump result working normal note there is no permanent way for water sump pump room L63 HS1. Do PMR service 443 EL1-clean up room of elevator also outside room every floor from 1st to 8th floor-clean up top elevator room-service sensor 1sr floor to 8th floor. Activation temperature control of 8th floor elevator control test function result ok ( AGUS & ADI & MUHAIMIN & DADANG )
|
|
2026-10-07
4 days ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1
|
Replace Breaker + Test Signal Upgrade IKGA
|
Do replace breaker and test signal of upgrade IKGA result normal working ( AGUS & MUHAIMIN )
|
|
2026-10-07
4 days ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-BF1
|
Issue compartment 6 & compartment 7 are not working
|
Service solenoid valve compartment 6 & compartment 7 from dirty of dust coal test function result normal working ( RIZAL & ANDRI )
|
|
2026-10-07
4 days ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-CC1
|
Prepare observation lighting lamp at street cooler
|
Do installing lighting lamp to street cooler at HRG room back side and IDO room west side also pulling cable power of lighting lamp test function result good ( JAJAT & EDI & ADI & DADANG )
|
|
2026-10-06
6 days ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-EL1
|
Repare partition lift control-install partition of door-cover of hole-install temperature sensor
|
Do install plywood board for cover wall elevator control at 8th floor and repainting grey color also cover hole at elevator control mote take 2 plywood board ( JAJAT & AGUS & EDI & RIZAL & ADI & IMAN & ANDRI & DADANG & MUHAIMIN )
|
|
2026-10-05
6 days ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Continue fabrication door of room control elevator
|
Do fabrication door of room control elevator at workshop ( ANDRI & DADANG )
|
|
2026-10-05
1 week ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR service critical motor LSR RM-PH
|
Do clean up area motor and filter motor. Measure vibration-noise-temperature of FS and LS motor. Add grease motor for 15 times and 20 times for FS and LS motor make vibration below 4 mm/s and noise below 2 gE. Check at ER3 and ER4 for RPM-Voltage-Ampere-KW-Temperature put at data check sheet also clean up filter 363 FA2 note filter at west side 1 side bad condition ( EDI & ADI )
|
|
2026-10-05
1 week ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-473-CC1-&-463-KL1
|
PMR Service Crit Motor & LSR KL & Cooler
|
Do clean up area motor and filter motor. Measure vibration-noise-temperature of FS and LS motor. Add grease motor for 25 times and 30 times for FS and LS motor make vibration below 4 mm/s and noise below 2 gE. Check at ER4 and ER5 for RPM-Voltage-Ampere-KW-Temperature put at data check sheet ( AGUS & MUHAIMIN )
|
|
2026-10-05
1 week ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer & replace or repare support proximity of IKGA
|
Clean up flange probe-probe-filter sample line-sample line tube-diaphragm pump-filter balston from dirty of dust use instrument air supply and water. Check function for humidity sensor and filter humidity result function humidity sensor good and filter humidity fine. Repare support proximity of IKGA result good ( RIZAL & ANDRI & DADANG )
|
|
2026-10-02
1 week ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Complete report PMR and WBI September 2026
|
Do complete data check sheet PMR analyzer L63 2K1-L63 2K2-L63 2K3-483 2K1-463 2K1-443 2K1-423 2K1; PMR Temperature IR TAD-T scanner-CCTV-Camera burner month august-september 2026 ( JAJAT & ADI )
|
|
2026-10-02
1 week ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-SCA-M1
|
Connect motor
|
Do connect motor 393 SCA M1 test function motor result good ( JAJAT & AGUS & EDI & RIZAL & MUHAIMIN & ANDRI & DADANG )
|
|
2026-10-02
1 week ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Continue fabrication welding point
|
Fabrication welding point at workshop result ok ( AGUS & MUHAIMIN )
|
|
2026-10-01
1 week ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-FN1-&-393-SCA-M1
|
Issue temperature trafo high temperature & issue motor burn
|
Install indication ready for trafo also pulling cable to I/O panel test function result good ( JAJAT & RIZAL & EDI & ANDRI & MUHAIMIN& DADANG )
|
|
2026-10-02
1 week ago
|
NR.EL-01
|
Wahyu Adi Triono
|
PT-PINCURAN-MAS
|
Inspection electrical and welding tools
|
Do inspection electrical tools of PT PINCURAN MAS tagging equipment use yellow color note service portable map and extension cable because unsafe cable power also make note for cable extension that use at indoor area because no cover of male connector ( EDI & ADI )
|
|
2026-10-02
1 week ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-EL1
|
Continue fabrication door-prepare cover of wall-tidy up elevator control
|
Fabrication door also install cover of wall and di tidy up elevator control use brush and equipment cleaning tools ( JAJAT & AGUS & RIZAL & ANDRI & MUHAIMIN & DADANG )
|
|
2026-09-30
1 week ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Continue fabrication panel welding point
|
Do fabrication of panel welding point at workshop result good ( AGUS & DADANG & EDI & ADI )
|
|
2026-09-30
1 week ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1-&-443-PR1-T1
|
PMR service analyzer & service temperature IR TAD issue reading temperature low
|
Do clean up flange probe-probe-sample line-filter sample line-diaphragm pump-filter balston from dirty of dust use instrument air supply also water for filter sample line. Check function of humidity sensor and filter humidity result function humidity sensor good and filter humidity good condition. Clean up lens of camera and flange probe IR TAD result value temperature show around 960 degree celcius at CCR operator ( JAJAT & RIZAL & ANDRI )
|
|
2026-09-28
1 week ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-473-CC1-&-463-KL1
|
PMR Service Crit Motor & LSR KL & Cooler
|
Clean area motor and filter motor from dirty of dust use instrument air supply and rag. Measure vibration-noise of FS and LS add grease motor for 25 times and 30 times of FS and LS. Check at ER4 and ER5 for RPM-KW-Ampere-V input-I total put at data check sheet ( ANDRI & DADANG )
|
|
2026-09-28
1 week ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-LQ2-M1
|
Disconnect auto grease motor
|
Disconnect cable power auto grease of L63 LQ2. Also reconnect cable power after finish service replace pump test function auto grease result ok ( EDI & ADI )
|
|
2026-09-28
1 week ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1
|
Cyclone 4 cross check temperature gas and material
|
Do cross check temperature at exit gas and materials cyclone 4 result CCR reading high than local adjust range temperature transmitter ( JAJAT & ANDRI & DADANG )
|
|
2026-09-28
2 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR service critical motor LSR RM-PH
|
Clean area motor and filter motor from dirty of dust use instrument air supply and rag. Measure vibration-noise of FS and LS add grease motor for 20 times and 25 times of FS and LS. Check at ER3 and ER4 for RPM-KW-Ampere-V input-I total put at check sheet. Clean up filter motor 363 FA2 from dirty of dust use instrument air supply note filter motor at east side one side bad condition need replace new filter motor ( EDI & ADI )
|
|
2026-09-25
2 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
BELT-FEED
|
Close hole cable and ER VSD belt feed
|
Add seal foam of hole between cable and ER VSD also wall from rust and plat . Result hole already cover by seal foam and plat for wall ( AIMAN )
|
|
2026-09-25
2 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-FN1
|
Issue alarm Fan red cool on (Cleaning Filter)
|
Clean up filter from dirty of dust use hand blower. Reinstall filter result alarm fan disappear. Clean up filter panel VSD 363 FN1-363 FN2-443 FN1 from dirty of dust use hand blower ( AGUS & MUHAIMIN )
|
|
2026-09-25
2 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
HRG-&-L1C-BC1-L1C-BC2-L1C-BC3-OF-M1
|
Install Lamp Filter WTP-HRG & observation installation Material Level at Truck Lift
|
Check at site, looking location install lighting lamp. Prepare support of lighting lamp and cable power wiring existing lighting lamp . Install lighting lamp and cable power lighting lamp test function result good lighting lamp on. Do observation of installation material level at L1C BC1-L1C BC2-L1C BC3. Decided material level will install top of main hole check material coal. Prepare support of material level at work shop (JAJAT & EDI & ADI & ANDRI & DADANG )
|
|
2026-09-24
2 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-EL1
|
Prepare Replacement cable
|
Pulling cable power and relocation conduit from main hole to protect from positive hot gas. Also install LCS at north side from existing south side ( JAJAT & AGUS & EDI & ADI & ANDRI & ANDRI & DADANG & DAFI TRUBA )
|
|
2026-09-23
2 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
CAMERA-BURNER
|
Observation camera burner issue often retract
|
Dismantle camera burner found front lens cracked, bring down to work shop. Continue clean up all lens and part support of lens also card from dirty of dust and oil. Replace front of lens with spare unit. Reassembling camera. Install camera burner at site test function insert and retract camera result good ( AGUS & MUHAIMIN & ANDRI )
|
|
2026-09-23
2 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1-&-483-RF2
|
Repare Auto Drain & pulling cable power Start / Stop
|
Check at location found AUTO Drain always energized, service per membrane from dirty of dust and reinstall test function result normal. Do pulling cable of 483 RF2 from LCS to panel I/O 4C1-2RB 31 ( EDI & ADI & DADANG )
|
|
2026-09-22
2 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1-4.5-&-6-TH-FLOOR-&-L93-SC1-&-453-PF1-&-L63-BF1
|
Issue lighting lamp off and relocation lighting lamp of bridge issue hit from water
|
Do replace lighting lamp of 443 ph1 4.5 floor and 6th floor & L93 SC2-453 PF1-l63 BF1 of bridge also relocation lighting lamp test function result lighting lamp on ( AGUS & MUHAIMIN & ANDRI & DADANG )
|
|
2026-09-21
2 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1-&-L63-RM1-&-473-CC1-&-463-KL1
|
PMR service critical motor LSR CM - PH & PMR critical motor area kiln and cooler
|
Clean CB dan Add greasing area ( AGUS & EDI & ADI & MUHAIMIN & DADANG )
|
|
2026-09-21
2 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean Filter and sample line ( AGUS & RIZAL & MUHAIMIN & ANDRI & DADANG )
|
|
2026-09-02
2 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1-4.5-&-6-TH-FLOOR
|
Check and replace lighting lamp reason blinking
|
Do replace lighting lamp at 4th and 6th floor reason blinking. Test function lighting lamp result good (AGUS & ANDRI & MUHAIMIN & DADANG )
|
|
2026-09-21
2 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-MD1
|
PMS 363 MD1, clean up filter 363 FA2-area motor -carbon brush room
|
Clean up filter 363 FA2-area motor main drive-carbon brush room from dirty of dust use instrument air supply. Measure long all carbon brush result replace carbon brush no 2 reason bad condition ( EDI & ADI )
|
|
2026-09-18
3 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-PW1
|
Calibration Tonase
|
Do calibration tonase of zero and span result good ( RIZAL & ANDRI & DADANG )
|
|
2026-09-18
3 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-443-WI-&-443-FN1
|
Tapping cable power & tidy up cable motor & tap power panel cooling motor
|
Do tapping cable power of L63 RM1 & Do tidy up cable motor of 443 WI result ok. Tap power 380 volt of panel cooling fan 443 FN1( AGUS & MUHAIMIN & KARDI CIVACON )
|
|
2026-09-18
3 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-T1
|
Replace thermocouple
|
Replace sensor thermocouple of 463 KL1 T1 result indication available at CCR operator ( RIZAL & ANDRI & DADANG )
|
|
2026-09-18
3 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM-&-FEED-BIN-&-483-FN1-M1
|
Clean up panel I/O - LCS motor & issue plat support vent fan add vibration. Eliminated plat sticking at platform
|
Do clean up LCS motor also control speed sensor and panel I/O area raw mill - feed bin from dirty of dust use wire brush - hand blower- rag. Do eliminated sticking plat at plat from of vent fan 483 FN1 M1 result ok ( EDI & ADI )
|
|
2026-09-18
3 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
333-WF2
|
Issue high noise motor
|
Check at site. Dismantle cover chain motor. Test running motor no load measure noise motor result normal. Stop motor install back cover chain motor ( EDI & ADI & KARDI CIVACON )
|
|
2026-09-18
3 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-RF2
|
Issue over load and motor trip
|
Check at site measure resistance R-S-T found 2 cable over load. Check at terminal motor found 1 cable untighten. Do tighten cable and recover all cable use rubber isolation and cable isolation test function 483 RF2 with different speed result normal. Check VSD of 483 RF2 test function motor with different speed check ampere at display VSD result around 1.71 to 1.75 ampere ( JAJAT & EDI & ADI )
|
|
2026-09-17
3 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-T1
|
Issue error indication at CCR
|
Replace sensor of L63 RM1 T1 use spare unit result indication normal at CCR note welding support of sensor temperature reason bad condition ( RIZAL & ANDRI & DADANG )
|
|
2026-09-17
3 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L93-RF2-&-393-FA1
|
Install Motor & replace bearing motor issue high noise
|
Check at site found actual high noise note replace bearing motor. Dismantle motor bring to work shop continue replace bearing motor. Install motor at site test run local motor measure vibration and noise of FS and LS motor result vibration below 2 mm/s and noise motor below 1 gE. Bring spare motor to location but not install because mechanic will replace complete unit note put spare motor inside analyzer L63 2k2 ( AGUS & MUHAIMIN & KARDI CIVACON )
|
|
2026-09-17
3 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
413-3B1-&-413-3B2-&-443-PH1-&-463-KL1-&-473-CC1-&-L63-RM1
|
Clean up panel I/O
|
Do clean up panel I/O area east blending & west blending - pre heater 8th - 5th- 3rd floor from dirty of dust use rag and hand blower note clean up panel I/O 5th top side from hard dust need install cover for top panel I/O to protect from dust make panel available from long term use. Do clean up panel I/O are kiln-cooler from dirty of dust also coal use rag and hand blower ( EDI & ADI & IMAN & RISNA CIVACON )
|
|
2026-09-17
3 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3-&-ER4-&-ER5
|
Support black out process
|
Do support black out process result ok ( RIZAL & EDI & ADI & MUHAIMIN & ANDRI & DADANG & KARDI CIVACON & RISNA CIVACON )
|
|
2026-09-16
3 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1
|
Continue modification air blaster of TAD + Trial
|
Install tank air blaster of temperature TAD test function result normal high pressure air and bring dwon existing tank of air blaster to workshop ( RIZAL & ANDRI )
|
|
2026-09-16
3 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1-&-463-KL1-&-473-CC1
|
Check and repaire welding panel
|
Check panel welding 4W3-1NH found output 220 VAC 3 units bad condition replace 3 units with spare unit and panel welding 4W3-1NC found output 220 VAC 1 unit bad condition no cover available replace use spare unit result ok normal. Also panel welding at 8th floor 443 PH1 found 1 unit output 22o VAC bad condition no cover available replace use spare unit and wiring 2 units output 220 VAC result normal ( EDI & ADI )
|
|
2026-09-14
4 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR critical motor RM & PH
|
Clean up area motor and filter motor. Measure vibration-noise-temperature of FS and LS motor. Add grease motor for 25 times and 90 times of FS and LS motor make vibration below 4 mm/s and noise below 2 gE. Check at ER3 and ER4 for KW-voltage-ampere-temperature motor and write at check sheet note noise 363 MD1 still up2 gE even add grease 1.5 bottle grease gun. Replace auto grease motor 363 MD1 at LS side issue empty grease motor ( AGUS & ADI )
|
|
2026-09-14
4 weeks ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-473-CC1-&-463-KL1
|
PMR Service Crit Motor & LSR KL & Cooler
|
Clean up area motor and filter motor. Measure vibration-noise-temperature of FS and LS motor. Add grease motor for 25 times and 30 times of FS and LS motor make vibration below 4 mm/s and noise below 2 gE. Check at ER4 and ER5 for KW-voltage-ampere-temperature motor and write at check sheet ( MUHAIMIN & DADANG )
|
|
2026-09-11
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1
|
Tidy up cable at 463 2K1 + test signal+ prepare activation fan exchanger
|
Do PMR service: clean up probe flange-probe-filter sample line-sample line tube-diaphragm pump-filter balston form dirty of dust use instrument air supply also water. Pulling cable new fan exchanger also wiring cable power-prepare pipe for activation fan exchanger. Do pulling cable of compressor to panel I/O inside analyzer room. Do test signal result good ( JAJAT & AGUS & RIZAL & ADI & EVE INDY & ANDRI & MUHAIMIN & DADANG )
|
|
2026-09-11
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-SC1-&-473-SC2
|
Issue speed failure
|
473 SC1: check at site probe and propeller normal, also inspection wiring cable measure voltage result bad condition from color black & white replace color chocolate & white result normal. 473 SC2 check at site found propeller detached. Ask stop motor from CCR and install propeller test function result speed failure normal when start motor from CCR ( JAJAT & RIZAL & ADI & ANDRI & EVE INDY & DADANG )
|
|
2026-09-11
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
CGA analyzer
|
Do calibration of zero and span gas some gas MCS 100E use span gas 3rd party result good drift below 2.5% ( JAJAT & RIZAL & EVE INDY )
|
|
2026-09-10
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-FN1-M1
|
Install Fan motor
|
Install fan 483 FN1 M1, test function measure ampere result 5.1 ampere also vibration FS and LS result around 5.2 from setting maximum 7ampere mm/s to 25 mm/s-noise around 1.3 gE note because vibration high run with 483 FN1 M2 ( MUHAIMIN & ANDRI & DADANG )
|
|
2026-09-10
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
CGA analyzer
|
Do calibration zero and span gas for MCS 100E together with 3rd party result good ( RIZAL & EVE INDY )
|
|
2026-09-10
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP-&-MAINGATE
|
Create SOT -TO month of september 2026 & inspection electrical tool s of PT Tupsa
|
Do create reporting SOT of September 2026 for 4 reporting at SHE SIG & inspection electrical tools for GENSET 2 unit PT TUPSA tagging equipment with yellow color ( JAJAT & AGUS & ADI )
|
|
2026-09-09
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Clean up flange probe-sample line-filter sample line-diaphragm pump-filter balston from dirty of dust coal use instrument air supply also water. Check function humidity sensor and filter humidity result function humidity sensor normal and filter humidity good condition ( JAJAT & RIZAL & EVE INDY & ANDRI )
|
|
2026-09-09
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L93-SC2
|
Cover motor not tight
|
Check at location found part of cover motor broken, install cover motor use wire because nuts cover bad condition ( MUHAIMIN & ADI & DADANG )
|
|
2026-09-08
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-BF1-&-423-2K1
|
Issue purging abnormal & issue failure
|
Check at site found membrane bad condition replace big membrane 6 unit and small membrane 5 units test function bag filter result normal and do PMR service CEMS result analyzer back at good condition ( RIZAL & ANDRI )
|
|
2026-09-08
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L33-BC1-M1
|
Issue speed motion block at CCR & test function motion
|
Check at site and replace card miltronics of sensor motion setting same like existing do test function speed result good at CCR ( AGUS & MUHAIMIN & DADANG )
|
|
2026-09-08
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1;-L63-RM1;-463-KL1
|
PMR IR TAD- T Scanner- CCTV - Camera Burner
|
Do clean up flange probe and lens of IR TAD-T scanner lens-CCTV lens-Pyrometer lens from dirty of dust use rag and equipment cleaning tools ( EDI & ADI & EVE INDY )
|
|
2026-09-07
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1
|
Replace lighting lamp
|
Do replace lighting lamp at area 363 RM1 use spare lighting lamp 2 units test function result normal on ( MUHAIMIN & DADANG & ANDRI )
|
|
2026-09-07
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PR1-T1
|
Issue temperature low
|
Pipe purging blocked, replace tube for purging test function result normal (Rizal & Andri)
|
|
2026-09-07
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
453-AE8-SV8
|
Issue open-close abnormal
|
Check at location found relay 24 VDC bad condition of coil, service coil replace 1 unit relay test function aeration normal note spare relay 24 VDC( RIZAL & ANDRI )
|
|
2026-09-07
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-FN1-M1
|
Issue motor loose bolt check abnormally
|
Check at location found 4 nuts untighten. Replace nuts motor with spare units note 2 nuts can not replace because part of drat nut left at flange motor ( EDI & ADI & EVE INDY )
|
|
2026-09-07
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR service critical motor LSR RM-PH
|
Clean up area motor and filter motor. Measure vibration-noise of FS and LS add grease motor 25 times-30 times for FS and LS make vibration below 4 mm/s and noise below 2 gE. Check at ER4 and ER5 for KW-Voltage -Ampere-Temperature of motor fill in at check sheet motor note replace tank of AUTO grease motor 2 units ( JAJAT &MUHAIMIN )
|
|
2026-09-07
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-&-473-CC1
|
PMR Service Crit Motor & LSR KL & Cooler
|
Clean up area motor and filter motor. Measure vibration-noise of FS and LS add grease motor 25 times-30 times for FS and LS make vibration below 4 mm/s and noise below 2 gE. Check at ER4 and ER5 for KW-Voltage -Ampere-Temperature of motor fill in at check sheet motor ( AGUS & DADANG )
|
|
2026-09-04
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
Issue CO reading low cross check
|
Clean up filter sample line and do zero also span calibration for CO result normal and reading CO back to normal at CCR ( RIZAL & EVE INDY & ANDRI )
|
|
2026-09-03
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-&-473-CC1
|
WBI Weld & Panel Lighting area KILN also Cooler
|
Do WBI welding and lighting area kiln also cooler ( EDI & IMAN )
|
|
2026-09-03
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-AR1-SV13
|
Solenoid valve is not working
|
Do check at site found s/v bad condition, replace 4 s/v test function result working normal ( RIZAL & MUHAIMIN & EVE INDY & DADANG )
|
|
2026-09-02
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
List Motor down at OH 2027 (included Bearing)
|
Do make list of motor down at OH 2027 included bearing ( AGUS & JAJAT )
|
|
2026-09-02
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Clean up flange probe-sample line tube-sample filter-diaphragm pump-filter balston from dirty of dust coal use instrument air supply and equipment cleaning tools. Test function humidity sensor and check filter humidity result function sensor humidity normal and filter good condition ( RIZAL & ANDRI )
|
|
2026-09-02
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
BELT-FEED
|
Repare Area Belt Feed-RM Recaptacle Short
|
Check at location found receptacle trip at panel lighting lamp. Do elimination 2 receptacle at north side and south side do rewiring cable for lighting lamp test function result normal ( EDI & ADI & EVE INDY & DADANG )
|
|
2026-09-01
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-FN1
|
Issue KW is not value ( issue transducer )
|
Check at ER4 and do reset power of KW metering result indication KW normal at CCR ( AGUS & EDI & DADANG )
|
|
2026-09-01
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
333-WF1
|
Issue speed monitor bad indication
|
Check at location found belt roller crooked make good position of belt roller and install speed monitor result indication normal at CCR operator ( JAJAT & RIZAL & ANDRI & EVE INDY & UNJ AZRIEL )
|
|
2026-09-01
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean flange probe-probe-sample line filter-sample line line tube-diaphragm pump-filter balston from dirty of dust use instrument air supply. Test function humidity sensor and check filter humidity result function humidity sensor normal and filter humidity good condition note replace filter humidity at 443 2K1 with spare filter. Do test gas CO at 463 2K1 reason reading often -0.001 to 0.002 result reading CO 1.1 PPM ( RIZAL & ADI & EVE INDY & ANDRI & UNJ AZRIEL )
|
|
2026-08-31
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-BC2
|
Test function BD
|
Do test function BD of L1C BC2 result normal ( EDI & EVE INDY & ANDRI )
|
|
2026-08-31
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-&-473-CC1
|
PMR Service Critical Motor & LSR KL & Cooler
|
Clean up area motor and filter motor. Measure vibration-noise of FS and LS. Check ampere-KW-voltage-temperature at ER4 & ER5 put in check sheet form ( AGUS & DADANG )
|
|
2026-08-31
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Support TPM activity
|
Do support TPM activity ( RIZAL & AZRIEL UNJ & EVE INDY )
|
|
2026-08-31
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER4
|
Fabrication piping of water and air ( support AC rubicon ER4 )
|
Do fabrication piping of water and air for support AC Rubicon ER4 (EDI & DADANG & ANDRI )
|
|
2026-08-28
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
333-WF1
|
Install and fabrication fan ccoller
|
Replace Tesys LUB12 also jumper contact relay test function fan cooling motor working normal and check vibration motor result still good ( AGUS & ADI & ANDRI )
|
|
2026-08-28
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-MD1-&-363-FN1-&-363-FN2
|
PMS-clean up carbon brush room
|
Do clean up carbon brush room of 363 MD1-363 FN1-363 FN1 from dirty of dust use instrument air supply also clean up filter 363 FA2. Measure long of all carbon brush result still up to minimum ( EDI & DADANG )
|
|
2026-08-27
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER4
|
Repare lock ER4
|
Do repare of ER4 use welding machine ( ADI & ANDRI )
|
|
2026-08-27
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
333-WF1-&-393-BE2-&-FEED-BIN
|
Recalibration if possible & check speed failure & install lighting lamp
|
Do calibration zero and span result zero before 0 t/h zero after 0 t/h- span before 155 t/h span after 161 t/h-Replace speed sensor, result indication normal at CCR-Do install lighting lamp test function result lighting lamp on ( JAJAT & RIZAL & UNJ AZRIEL & ANDRI )
|
|
2026-08-27
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Install heater spare motor 363 FN2-463 MD1-363 MD1 and clean up use blower
|
Open cover cable heater motor, rewiring cable heater 363 FN1-363 FN2-463 MD1. Tidy up recondition motor put at north side and spare motor at south side ( AGUS & ADI & DADANG )
|
|
2026-08-26
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Clean up flange probe-sample line tube-filter sample line-diaphragm pump-filter balston from dirty of coal dust use instrument air supply. Check function humidity sensor and filter humidity result function humidity sensor normal and filter humidity good condition ( RIZAL & ANDRI )
|
|
2026-08-25
1 month ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
444-PH1
|
Support feeding process at Nr2
|
Check value pressure at 444 PI 13A at 7th floor use manual manometer show pressure 131 to 150 mmH2O compare with CCR reading 660 mmH2O check range existing -4 to 0 mmH2Ot change range to 0-600 mmH2O result reading local same with CCR. Check reading temperature 444 PH1 T3 reading minus at CCR check connection cable and do recorrect wiring cable result temperature good. 444 GT4 materials don't flow to sirculation try change open and close gate result still same and use instrument air supply to make materials go to sirculation point result good ( JAJAT & EDI & ADI & MUSLIH SHIFT & RIZKY SHIFT & RIZKY FAUZI & SUPRIYADI & DADANG & IMAN )
|
|
2026-08-25
1 month ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
YM-CEMS
|
Support Hannes and Adrianus
|
Do support YM CEMS with Mr. Hannes and Mr. .Adrianus. Clean up Flowsic 100 complete unit also filter purge air unit. Bring down Dust Hunter T100 check zero adjust result value zero without materials 1.2 mg/m3 recheck function of swivel windows result replace swivel windows with spare units install back Dust Hunter at stack result value dust 4 until 5 mg/m3 ( RIZAL & ANDRI & HANNES KISS & ADRIANUS KISS )
|
|
2026-08-24
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
HRG-ROOM-
|
Issue dirty area inside and outside
|
Do clean up area HRG inside and outside also filter panel from dirty of dust use instrument air supply ( JAJAT & UNJ AZRIEL )
|
|
2026-08-24
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe-probe-filter sample line-sample line tube-diaphragm pump-filter balston from dirty of dust use instrument air supply. Check function of humidity sensor and filter humidity result function humidity sensor normal and filter humidity good condition ( RIZAL & ANDRI )
|
|
2026-08-24
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-473-CC1-&-463-KL1
|
PMR Service Crit Motor & LSR KL & Cooler
|
Cleaning area and filter motor from dirty of dust use instrument air supply and equipment cleaning tools. Measure vibration-noise of FS and LS motor also add grease motor for 25 times and 30 times of FS and LS. Check at ER4 and ER5 for ampere motor-voltage motor-RPM-KW write at check sheet motor ( MUHAIMIN & DADANG )
|
|
2026-08-24
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR service critical motor LSR RM-CM
|
Cleaning area and filter motor from dirty of dust use instrument air supply and equipment cleaning tools. Measure vibration-noise of FS and LS motor also add grease motor for 25 times and 40 times of FS and LS. Check at ER3 and ER4 for ampere motor-voltage motor-RPM-KW write at check sheet motor ( EDI & ADI )
|
|
2026-08-22
1 month ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
494-PN1
|
Install sling TLS for north and south side
|
Do install sling cable of TLS at south and north side also support of sling cable. Do test function TLS result good ( IRMIS & ADI & MUHAIMIN & ANDRI & DADANG )
|
|
2026-08-21
1 month ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
HYDRAULIC-ROOM-NR2
|
Continue Installation Sensor Temp + Hum
|
Do installation sensor temperature and humidity at room hydraulic Nr2 also wiring cable at I/O panel ( AGUS & MUHAIMIN & DADANG )
|
|
2026-08-21
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Position motor from BOVERI
|
Achieve motor 463 MD1 from BOVERI put motor behind workshop ( AGUS & MUHAIMIN & DADANG )
|
|
2026-08-21
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
MAIN-GATE-ACCES-CONTROL
|
Check tools jack hamer of PT Indoporlen 4 units
|
Do inspection electrical tools of PT INDOPORLEN for jack hammer 4 units test run tools result ok note equipment tagging blue color ( EDI & ADI )
|
|
2026-08-20
1 month ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
L64-SC1
|
Install signal indication ampere motor for VSD L64 SC1 at ER5 Nr2
|
Prepare cable for signal indication output ampere motor of VSD L64 SC1 continue wiring cable at I/O panel ER5 Nr2 ( ZAHRA & ADI )
|
|
2026-08-20
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-W1-M1&-443-WI1-M1
|
Issue motor high load. Prepare motor spare
|
Check name plate motor of 443 WI1 M1 and 443 WI1 M3 and cross check spare motor at warehouse result find motor 2P 45 KW do test run megger motor result good no load measure ampere R-S-T get value 10 until 12 ampere and put motor spare 443 WI M3 behind workshop electric 1 ( EDI & ADI & JAJAT )
|
|
2026-08-19
1 month ago
|
NR.N2-OH
|
yulandiandi
|
L94-SC2
|
Motor L94-SC2 Mati Ready
|
Check local, Replace Probe test blm bisa pulse, Replace Amplifier test bisa pulse. Test Run L94-SC2 Sudah tidak mati Ready lagi/ normal ( Melky, Yulandi, Kardi )
|
|
2026-08-19
1 month ago
|
NR.N2-OH
|
yulandiandi
|
L94-SC2
|
Motor L94-SC2 Mati Ready
|
Check local, Replace Probe test masih blm pulse, Ganti Amplifier test langsung dengan motor L94-SC2 Kondisi bisa pulse/ok
|
|
2026-08-19
1 month ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
L94-SC5
|
Issue often trip if on start from CCR
|
Replace probe and pre amplifier at local test function result normal ( TITOK & FAHRI & EVE TEGAR & EVE ZAHRA & KARDI CIVACON & ADI )
|
|
2026-08-19
1 month ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
394-CV2-CV3-CV4-CV5
|
Install sensor motion
|
Install support and sensor motion at 394 CV2-CV3-CV4-CV5 ( EVE SUPRIYADI & KARDI CIVACON & ADI )
|
|
2026-08-18
1 month ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
WORK-SHOP-RMK-NR2-&-L64-RM1
|
Install motor 454 PF2 and bearing motor at workshop
|
Install motor at 454 PF2 and bearing motor 434 BL2 at workshop electric Nr2 with do heater bearing 6213 before install at motor ( HARYANTO & EDI & ADI )
|
|
2026-08-18
1 month ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Create SOT July-August 2026
|
Create SOT document for month august for all member at electric RMK Nr1 ( JAJAT & ADI )
|
|
2026-08-15
1 month ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
474--FA8-M1
|
Issue motor unbalance information CBM Najib
|
Clean up area panel cable motor-connector cable-winding cable from dirty of dust use hand blower and liquid dust degreaser also clean up area motor from dirty of dust. Test run without load result good ( HARYANTO & ADI & @ CIVACON EMPLOYEE )
|
|
2026-08-14
1 month ago
|
NR.N2-OH
|
Sadi Bin Rowi
|
L34-BC2
|
OCR masih type TOR
|
Replace OCR, ganti dgn EOCR+ instal CT... Test trip Done
|
|
2026-08-14
1 month ago
|
NR.N2-OH
|
Sadi Bin Rowi
|
L34-BC1
|
OCR masih type TOR
|
Replace OCR, ganti dengan EOCR + instal CT..test trip..Done
|
|
2026-08-14
1 month ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
ER3-VSD-ROOM
|
Clean up VSD panel 364 FN2-364 FN3 and inverter also filter panel-bus bar from dirty of dust use hand blower and thinner
|
Do clean up panel VSD of 364 FN2 & FN3 also filter cabinet-bus bar-cable power supply from dirty of dust use hand blower and thinner also equipment cleaning tools ( ADI & EVE ELGI & KARDI CIVACON & RAHMAT CIVACON & EKO & MARDIYANTO )
|
|
2026-08-14
1 month ago
|
NR.N2-OH
|
Sadi Bin Rowi
|
L64-SX1
|
OCR respons too late, the seting Dtime isnt effect
|
Replace OCR + Replace R1
|
|
2026-08-13
1 month ago
|
NR.N2-OH
|
Sadi Bin Rowi
|
L94-RF1
|
OCR not respons
|
Replace EOCR dan test trip ok
|
|
2026-08-13
1 month ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
ER9
|
Clean up VSD panel and inverter also filter panel-bus bar from dirty of dust use hand blower and thinner
|
Do clean bus bar-capacitor inverter-filter panel use hand blower and thinner. Measure value of capacitor write top of capacitor. Reinstall filter panel of VSD ( EKO JUAN & MARDIYANTO & ADI & EVE ELGI & KARDI CIVACON & 2 CIVACON EMPLOYEE )
|
|
2026-08-13
1 month ago
|
NR.EL-04
|
yulandiandi
|
59B-RF2
|
Wending motor kebakar
|
Replace motor & EOCR
|
|
2026-08-12
1 month ago
|
NR.N2-OH
|
Yurizal Rachman
|
473-CR1
|
Instal Level Material
|
Instal level material,trashing kabel
|
|
2026-08-12
1 month ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
BURNER-FLOOR
|
Inspection electrical and welding tools of PT RMP
|
Do inspection electrical tools of PT RMP for panel power supply AC tagging equipment use blue color ( ADI & EVE ELGI )
|
|
2026-08-12
1 month ago
|
NR.N2-OH
|
Sadi Bin Rowi
|
494-FN4
|
OCR absolute/TOR
|
Replace TOR dengan EOCR
|
|
2026-08-12
1 month ago
|
NR.N2-OH
|
Sadi Bin Rowi
|
474-CV4.-M01
|
EOCR not responsif by manual test
|
Replace EOCR, seting ampere sesuai dgn existing dan test manual trip ok.. Done
|
|
2026-08-12
1 month ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
364-RM1-474-CC1-444-PH1-L64-RM1
|
Calibration pressure transmitter of zero and span
|
Do calibration pressure transmitter area PH 5 units note replace pressure transmitter of 444 FN2 P2 from VEGA to Yokogawa because when give pressure at H or L always drop to zero do test zero and span result normal. Complete data check sheet calibration pressure transmitter for 12/8/2026 ( ADI & EVE ELGI & EVE INDY & EVE TEGAR )
|
|
2026-08-12
1 month ago
|
NR.EL-04
|
yulandiandi
|
535-BF1
|
Control purgingnya mati
|
Check cable power input 110V...cable netral 110V Conectionnya kendor.
|
|
2026-08-11
2 months ago
|
NR.EL-04
|
yulandiandi
|
51B-CM7
|
Selector switch tidak bisa posisi Remote & Local
|
Replace selector switch
|
|
2026-08-11
2 months ago
|
NR.EL-04
|
yulandiandi
|
535-BF1
|
Control BF mati
|
Check power control purging ada yg shot
|
|
2026-08-11
2 months ago
|
NR.EL-04
|
yulandiandi
|
546-RM1.M1
|
Ada suara noist di bearing Motor yang LS
|
Check yg noist bearing motor yang LS dengan cara di discouple, hasilnya tidak ada noist. CBM Alignment ulang motor 546-RM1.M1
|
|
2026-08-11
2 months ago
|
NR.N2-OH
|
Sadi Bin Rowi
|
ER5-NR2
|
Protection loss over current
|
Test trip EOCR dan List data set EOCR all equipment
|
|
2026-08-11
2 months ago
|
NR.N2-OH
|
Sadi Bin Rowi
|
444-PU1.-M2
|
TOR tidak bisa di test trip
|
Replace TOR dengan EOCR+CT ratio 400/5
|
|
2026-08-11
2 months ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
364-RM1-474-CC1-444-PH1-L64-RM1
|
Calibration pressure transmitter area RM-PH-CM-CC
|
Do calibration pressure transmitter Honeywell 3 units but can not detected name of unit base on instruction Mr.Titok install back pressure transmitter at site no need replace new spare. Complete data check sheet calibration pressure transmitter since 4/8/26 to 10/8/26 ( ADI & EVE TEGAR & EVE INDY & EVE ELGI & UNJ AZRIEL )
|
|
2026-08-11
2 months ago
|
NR.N2-OH
|
hamdani
|
444PU1M2
|
Tor absolute
|
Ganti tor ke eocr
|
|
2026-08-10
2 months ago
|
NR.N2-OH
|
hamdani
|
ER3-NAR2
|
364 gd 1 ocr absolute/ tor
|
Ganti tor dengan eocr
|
|
2026-08-10
2 months ago
|
NR.N2-OH
|
Sadi Bin Rowi
|
R4
|
Abnormal EOCR
|
Cek seting EOCR all equipment and test trip EOCR
|
|
2026-08-10
2 months ago
|
NR.N2-OH
|
Sadi Bin Rowi
|
394-CV1
|
Relay R1 ga mau energize pada saat di test
|
Replace relay R1 dgn yg baru, test.. Ok
|
|
2026-08-10
2 months ago
|
NR.N2-OH
|
Sadi Bin Rowi
|
364-GD1.-M1
|
OCR absolut, tidak ada fasilitas test... Old type
|
Replace TOR dengan EOCR... Test position trip dan seting trip sesuai sebelumnya
|
|
2026-08-10
2 months ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
364-RM1-474-CC1-444-PH1-L64-RM1
|
Calibration pressure transmitter area PH-RM-CC-CM
|
Calibration pressure transmitter area PH-CC-RM for zero and span get 20 units note replace pressure transmitter from VEGA of 364 BF1 F1 use Yokogawa test zero and span result good ( ADI & EVE TEGAR & UNJ AZRIEL & EVE ELGI & EVE INDY )
|
|
2026-08-10
2 months ago
|
NR.N2-OH
|
Yurizal Rachman
|
474-FN2
|
Service damper
|
Check,service dan setting damper fan R
|
|
2026-08-10
2 months ago
|
NR.N2-OH
|
Yurizal Rachman
|
474-T1
|
Thermocouple rusak
|
Replace thermocouple exit cooler,inlet ep cooler
|
|
2026-08-10
2 months ago
|
NR.N2-OH
|
Yurizal Rachman
|
474-VA1
|
Valve rusak
|
Replace valve kinetrol untuk flushing gun
|
|
2026-08-08
2 months ago
|
NR.N2-OH
|
Yurizal Rachman
|
ER2
|
Blackout
|
Suport black out activitg,clean up switch gear and mcc,meger buabar dan trafo
|
|
2026-08-07
2 months ago
|
NR.N2-OH
|
Yurizal Rachman
|
474-FA
|
Lepas Thermocouple
|
Lepas thermocouple undergrate
|
|
2026-08-07
2 months ago
|
NR.N2-OH
|
Yurizal Rachman
|
474-FA
|
Repair tubing
|
Repair tubing yg rusak,rojok lubang draft flow fan cooler area
|
|
2026-08-09
2 months ago
|
NR.N2-OH
|
Muhaimin
|
394-BE1
|
Support OH Nar2.
|
Tap power untuk control drive portable alat gulung belt dan pulling cable output drive ke motor serta test running.
|
|
2026-08-09
2 months ago
|
NR.N2-OH
|
Muhaimin
|
484-BL2,L34-BC1,L34-BC2
|
Rekondisi Motor OH Nar 2
|
Instal dan connect motor setelah rekondisi dari vendor Rems.
|
|
2026-08-08
2 months ago
|
NR.N2-OH
|
Muhaimin
|
NAR-2-ER5
|
Balckout Nar 2 pergantian VCB.
|
Jumper outgoing kubikel W1E ke kubikel EP cable 6 x 240 mm.
|
|
2026-08-07
2 months ago
|
NR.N2-OH
|
Muhaimin
|
334-BC1
|
Cable output LCS kurang panjang
|
Ganti cable dan pasang grounding motor.
|
|
2026-08-07
2 months ago
|
NR.N2-OH
|
Muhaimin
|
484-BL2
|
Base motor 484 BL2 baut slek.
|
Ganti baut base motor 484 BL2 dan modifikasi base.
|
|
2026-08-09
2 months ago
|
NR.N2-OH
|
yulandiandi
|
394-BE2.M2,474-GD1MO2
|
Proteksi masih menggunakan TOR
|
Penggantian proteksi dari TOR ke EOCR
|
|
2026-08-08
2 months ago
|
NR.N2-OH
|
yulandiandi
|
474-GD1.MO1
|
Proteksi masih menggunakan Sistem TOR
|
Penggantian dari Proteksi TOR ke EOCR
|
|
2026-08-08
2 months ago
|
NR.N2-OH
|
yulandiandi
|
565-MD1,565-RM1,566-MD1,566-RM1
|
VCB kondisi kotor/berdebu
|
Service VCB & Blow out
|
|
2026-08-08
2 months ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
364-RM1-474-CC1-444-PH1-L64-RM1
|
Calibration pressure transmitter zero and span area RM-Cooler-PH-CM
|
Do calibration zero and span for pressure transmitter area raw mill-cooler-preheater-coal mill totals 6 units ( EVE TEGAR & ADI )
|
|
2026-08-08
2 months ago
|
NR.N2-OH
|
yulandiandi
|
TR-071,TR-072,TR-073,TR-074,565-1T1,566-1T1
|
Trafo dalam kondisi kotor
|
Blow out trafo & penegecekan baut conection
|
|
2026-08-08
2 months ago
|
NR.N2-OH
|
Hendro Supramono
|
BATTERY-CHARGER-MSS-N2
|
Baterry Charger 110VDC failure
|
Perbaikan penggantian kabel battery yang short. Service dan cleanup periodik.
|
|
2026-08-08
2 months ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
MAIN-GATE-ACCES-CONTROL
|
Inspection electrical and welding tools of Quadro
|
Do inspection electrical and welding tools of Quadro. Tagging electrical tools use blue color note extention cable 2 units no cover female connection ask quadro replace with cover for all female connection ( ADI & TRUBA ILHAM )
|
|
2026-08-08
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-473-CC1
|
PMR Service Crit Motor & LSR KL & Cooler
|
Clean up area motor and filter motor. Measure vibration-noise-temperature of FS and LS motor. Add grease motor for LS and FS 25 times and 30 times . Check at ER5 and ER4 for data KW-Ampere-Voltage-Temperature and fill in at data check sheet ( AGUS & MUHAIMIN )
|
|
2026-08-08
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR Service Critical Motor & LSR RM&CM1
|
Clean up area motor and filter motor. Measure vibration-noise-temperature of FS and LS motor. Add grease motor for LS and FS 15 times and 20 times note 363 MD1-363 FN1-363 FN2 off condition. Check at ER3 and ER4 for data KW-Ampere-Voltage-Temperature and fill in at data check sheet ( EDI & DADANG )
|
|
2026-08-08
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe-probe-filter sample line-sample line tube-diaphragm pump-filter balston from dirty of dust use instrument air supply. Check function humidity sensor and filter humidity result function humidity sensor normal and filter good condition ( RIZAL & ANDRI )
|
|
2026-08-08
2 months ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
ER2-&-ER3-&-ER4-&-ER5
|
Support black out process OH NR2
|
Do support black out process at ER2-ER5-ER4-ER3. Clean up trafo-MCC-MSS -I/O panel from dirty of dust use equipment cleaning and hand blower also do vacuum electric room. Do megger cable R-S-T to ground fill in at check sheet of data ER2 ( JAJAT & AGUS & RIZAL & ADI & ANDRI & AIMAN & DADANG )
|
|
2026-08-07
2 months ago
|
NR.N2-OH
|
Hendro Supramono
|
BATTERY-CHARGER-ER3-N2
|
Cooling Fan sudah lifetime, Battery sudah drop dan service tahunan
|
Penggantian Cooling Fan 3 EA, Penggantian Battery 18 EA 12V 120Ah, Service
|
|
2026-08-07
2 months ago
|
NR.N2-OH
|
yulandiandi
|
364-PU1.MO1,364-PU1.MO2,364-SJ1.MO1,364-LQ2.MO6,364-LQ2.MO7
|
Proteksi masih menggunakan TOR
|
Penggantian proteksi TOR ke EOCR
|
|
2026-08-07
2 months ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
364-RM1-474-CC1-444-PH1
|
Calibration pressure transmitter zero and span area RM-Cooler-PH
|
Do calibration zero and span for pressure transmitter area raw mill-cooler-preheater-coal mill totals 10 units note replace 1 unit pressure transmitter 364 BF1 P1 range 0-150 mmH2O calibration result good because existing pressure transmitter check span output drop to 7 mA ( ADI & EVE TEGAR & UNJ AZRIEL )
|
|
2026-08-06
2 months ago
|
NR.N2-OH
|
yulandiandi
|
364-LQ2.MO2
|
Masih menggunakan proteksi TOR
|
Penggantian proteksi dari TOR ke EOCR
|
|
2026-08-06
2 months ago
|
NR.N2-OH
|
yulandiandi
|
364-LQ2.MO1
|
Proteksi masih menggunakan TOR
|
Penggantian dari TOR ke EOCR
|
|
2026-08-06
2 months ago
|
NR.N2-OH
|
Muhaimin
|
364-LQ1,394-FA6,434-FA1,L94-SC3,L94-SC6,L94-FN2
|
Rekondisi motor Oh Nar2
|
Support OH Nar2 disconncet dan bongkar motor 364-LQ1,394-FA6,434-FA1,L94-SC3,L94-SC6,L94-FN2 untuk rekondisi keluar ke PT Rems dan Tridaya.
|
|
2026-08-05
2 months ago
|
NR.N2-OH
|
Muhaimin
|
L94-RF1,L94-RF2,484-FN4
|
Rekondisi motor OH Nar 2
|
Support OH Nar 2 Disconnect dan bongkar motor L94 RF1,RF2, 484 FN4 rekondisi motor ke luar PT Rems dan Tridaya.
|
|
2026-08-06
2 months ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
364-RM1-474-CC1-444-PH1-L64-RM1
|
Calibration pressure transmitter area PH-RM-CC-CM
|
Do calibration zero and span for pressure transmitter area raw mill-cooler-preheater-coal mill totals 10 units ( ADI & EVE TEGAR & UNJ AZRIEL )
|
|
2026-08-06
2 months ago
|
NR.N2-OH
|
Yurizal Rachman
|
474-FAE
|
Service dan repair
|
Check,service repair ganti card,repaire blade dan setting
|
|
2026-08-05
2 months ago
|
NR.N2-OH
|
Yurizal Rachman
|
474-FA
|
Check dan service damper
|
Check open close damper dari ccr
|
|
2026-08-05
2 months ago
|
NR.N2-OH
|
Yurizal Rachman
|
484-FN2,FN3
|
Check damper
|
Check open close damper
|
|
2026-08-05
2 months ago
|
NR.N2-OH
|
Hendro Supramono
|
BATTERY-CHARGER-ER5
|
Fan Cooling sudah kurang lifetime dan service tahunan
|
penggantian Cooling Fan sebanyak 3 EA dan service tahunan
|
|
2026-08-05
2 months ago
|
NR.N2-OH
|
Hendro Supramono
|
UPS-ER5
|
Cooling Fan sudah lifetime dan service tahunan
|
Service tahunan, ganti fan 3EA
|
|
2026-08-05
2 months ago
|
NR.N2-OH
|
yulandiandi
|
3C2-2RA.20
|
Panel I/O & Panel ATS kondisi kotor/berdebu
|
Blow out & ganti lampu tl yg mati di dalam panel I/O
|
|
2026-08-05
2 months ago
|
NR.N2-OH
|
yulandiandi
|
364-RM1.C1
|
Check toleransi capasitor
|
Hasil pengukuran capasitor : ( Y1+PH ) ( Y2+PH ) ( Y1+Y2 ) 42,87uF 42,94uF 21,47uF 42,42uF 39,68uF 20,51uF 42,90uF 39,50uF 20,60uF
|
|
2026-08-05
2 months ago
|
NR.N2-OH
|
Naufal
|
ER3
|
Pengecekan EOCR
|
Pengecekan respon trip dari EOCR
|
|
2026-08-05
2 months ago
|
NR.N2-OH
|
Naufal
|
334-LQ.M01
|
Proteksi masih menggunakan TOR
|
penggantian proteksi menjadi EOCR
|
|
2026-08-05
2 months ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
364-RM1-474-CC1-444-PH1
|
Calibration pressure transmitter area PH-RM-CC
|
Do calibration zero and span for pressure transmitter area raw mill-cooler-preheater totals 15 units ( ADI & EVE TEGAR & UNJ AZRIEL )
|
|
2026-08-04
2 months ago
|
NR.N2-OH
|
Muhaimin
|
484-BL2,454-BL4
|
Rekondisi Motor OH Nar 2
|
Disconnect dan lepas motor 484 BL2,454 BL4 untuk rekondisi keluar ke PT Rems.
|
|
2026-08-04
2 months ago
|
NR.N2-OH
|
Muhaimin
|
474-CV1,CV2,CV3,CV4
|
Rekondisi motor
|
Disconnect dan lepas motor 474 CV1,CV2,CV3,CV4 untuk rekondisi keluar ke PT Tridaya.
|
|
2026-08-04
2 months ago
|
NR.N2-OH
|
yulandiandi
|
ER04A
|
Area mcc dan all panel tubical 380V kondisi kotor
|
Blow out panel tubical 380V dan vacum lantai mcc ER04A
|
|
2026-08-04
2 months ago
|
NR.N2-OH
|
Naufal
|
ER4A
|
Pengecekan Proteksi EOCR
|
Pengecekan respon proteksi EOCR serta pengecekan equipment yang masih menggunakan TOR sebagai berikut: 474-GD1.M2 Set : 5A
434-BL7 Set : 60 A
444-PU1.M2 Set : 115 A
474-GD1.M01 Set :3.5
414-BL5 Set : 20A
4D4-BL1.M01 Set : 275 A
454-WS1.C1 Set : 60 A
|
|
2026-08-04
2 months ago
|
NR.N2-OH
|
yulandiandi
|
ER-4A
|
Lampu indikasi panel tubical 434-BL2.MO1rusak
|
Replace lampu indikasi yg baru
|
|
2026-08-04
2 months ago
|
NR.N2-OH
|
Yurizal Rachman
|
474-GQ
|
Lepas pressure transmitter
|
Lepas pressure transmitter area great cooler
|
|
2026-08-04
2 months ago
|
NR.N2-OH
|
Yurizal Rachman
|
474-FA
|
Lepas pressure transmitter
|
Lepas pressure transmitter fan cooler all
|
|
2026-08-04
2 months ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
WORK-SHOP-ELECTRIC-NR2
|
Calibration pressure transmitter area RM
|
Do calibration zero and span for pressure transmitter area raw mill 4 units ( ADI & EVE TEGAR & UNJ AZRIEL )
|
|
2026-08-03
2 months ago
|
NR.N2-OH
|
Yurizal Rachman
|
494-BF3-
|
Service
|
Repair diafragm bocor,replace solenoid rusak,clean up panel purging
|
|
2026-08-04
2 months ago
|
NR.N2-OH
|
Hendro Supramono
|
424-EP1
|
Service Transformer tahunan
|
Survey oleh Trafindo persiapan service, ganti oli, bushing dan seal termasuk purifying.
|
|
2026-07-29
2 months ago
|
NR.N2-OH
|
Hendro Supramono
|
BATTERY-UPS-CCRN2
|
battery sudah tua
|
rencana penggantian batere tipe basah dengan batere tipe kering bersamaan service OHN2-2026 bulan Agustus.
|
|
2026-08-03
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-PF1-&-453-PF1
|
Adjust CF
|
Do adjusted CF ( RIZAL & ANDRI )
|
|
2026-08-03
2 months ago
|
NR.N2-OH
|
Wahyu Adi Triono
|
PY-ADZALAMA
|
Inspection electrical and welding tools
|
Do inspection electrical and welding tools of PT Adzalama tagging equipment bule color note repare brook machine because grounded cable not connected properly. Rejected 2 extention cable because no cover at male connector ( ADI & WILDAN CIVA & MUSLIH SMI )
|
|
2026-08-03
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Complete data of AUDIT API
|
Do complete data AUDIT API ( JAJAT & ADI & UNJ AZRIEL )
|
|
2026-07-31
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
PMR service CEMS
|
Dust hunter: clean up purge air unit-filter motor flange with tube-swivel window T/R & R -alignment T/R & R result ok. Flowsic: clean up purge air unit-filter motor-transduce A & B. CEMS room: clean area CEMS room-filter cabinet MCS 100E-CEMS gas room from dirty of dust use instrument air supply ( RIZAL & ANDRI )
|
|
2026-07-31
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1
|
Continue project upgrade analyzer
|
Do continue project upgrade 463 2K1 and test signal result ok ( AGUS & DADANG )
|
|
2026-07-31
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-L1C-TR1-&-L1C-TL1
|
WBI CM-L!C TR1-L3C RE1-BC coal transport
|
Do WBI area CM-truck lift-tripper-bc transport coal. Add grease for L1C BC4-L1C BC5-483 BL2 around 15 times-20 times-30 times for FS and LS. Test function sump pump L1C BC1 & L1C BC4 result normal-water spray L1C BC5 & L1C BC6 & L1C BC7 & L63 HS1 result function normal ( EDI & ADI & UNJ AZRIEL )
|
|
2026-07-30
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1
|
Repare + Install repare Blower Sheel Kiln
|
Install motor blower shell kiln 4 units- install cable motor blower shell kiln; install propeller motor blower. Do test function blower shell kiln result function normal. Bring down 1 motor shell kiln to workshop for rewinding ( JAJAT & AGUS & RIZAL & ADI & EDI & MUHAIMIN & ANDRI & DADANG & TRUBA TEAM & UNJ AZRIEL )
|
|
2026-07-29
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Clean up flange probe-probe-sample line tube-filter sample line-diaphragm pump-filter balston from dirty of dust coal use instrument air supply and water supply. Check function humidity sensor and filter humidity result function humidity sensor normal and filter good condition note replace gas cooler at L63 2K3 because bad condition replace use spare unit ( RIZAL & ANDRI )
|
|
2026-07-29
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-3B1-CLINKER-SILO
|
PMR Motor Area Clinker
|
Clean up motor area clinker silo from dirty of dust clinker use equipment cleaning tools. Measure vibration-noise and add grease motor 25 times for FS and LS ( DADANG & AIMAN )
|
|
2026-07-29
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
-WORK-SHOP
|
Upgrade analyzer ( activation power + testing signal )
|
Continue activity wiring LCS and IO ( AGUS & MUHAIMIN )
|
|
2026-07-29
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP-PPUP
|
Inspection electrical and welding tools of PPUP
|
Check inspection electrical and welding tools of PPUP. Do repare some tools and tagging equipment use blue color ( EDI & UNJ AZRIEL )
|
|
2026-07-28
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-PF1
|
Issue different reading
|
Adjust CF , reduce around - 4 t/h ( RIZAL & JAJAT )
|
|
2026-07-28
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1
|
Upgrade analizer (Pulling cable 10 mm) estimation120 m ) fabrication- wiring termination cable 120 m )
|
Pulling cable 4 x 10 mm x 120 m -Done ( AGUS & RIZAL & MUHAIMIN & DADANG )
|
|
2026-07-27
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe-probe-sample filter-sample line tube-diaphragm pump-filter balston from dirty of dust use instrument air supply. Check function humidity sensor and filter humidity result function humidity sensor good and filter humidity good ( RIZAL & ANDRI )
|
|
2026-07-27
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-473-CC1-&-463-KL1
|
PMR critical motor CM & CC & KL
|
Clean up area motor-filter motor from dirty of dust use instrument air supply. Measure vibration-noise motor of FS and LS add grease motor 25 times for FS and LS. Check at ER4 and ER5 for RPM-Voltage-KW-Ampere-Temperature fill in at check sheet motor note replace AUTO grease tank at L63 MD1-L63 FN1 for FS and LS with spare unit ( MUHAIMIN & DADANG )
|
|
2026-07-27
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR critical motor RM & PH
|
Clean up area motor-filter motor from dirty of dust use instrument air supply. Measure vibration-noise motor of FS and LS add grease motor 15 times for FS and LS. Check at ER3 and ER4 for RPM-Voltage-KW-Ampere-Temperature fill in at check sheet motor ( EDI & ADI & UNJ AZRIEL )
|
|
2026-07-24
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER5
|
TPM Continue ER 5 bottom
|
Do TPM activity at ER5 bottom floor. Clean up room ER5 from dirty of dust use equipment cleaning tools ( JAJAT & AGUS & EDI & RIZAL & ADI & MUHAIMIN & ANDRI & AIMAN & DADANG & UNJ AZRIEL )
|
|
2026-07-24
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
BC-COAL-TRANSPORT
|
Repare-activation water spray at L1C BC7, BC6, BC5
|
Check at location, L1C BC7: found power s/v off and valve water spray off. Do turn on power s/v and valve water spray also adjust stick water spray result function water spray normal, L1C BC6 found valve water spray off action valve water off action on valve water and adjust stick water spray result function water spray normal. L1C BC5 found valve water spray off action open valve water spray function water spray normal ( EDI & ADI & DADANG )
|
|
2026-07-23
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-WI1-M3
|
Issue over load and motor trip, motor normal function
|
Check use megger of R-S-T to ground result 0.4 ohm note inside motor moist hit water from 443 WI1 M2. Install heater lamp at motor 443 WI1 M3 around 10 minutes reconnect cable R-S-T and do megger result 2 mega ohm. Test function motor 443 WI1 M3 result ampere meter 13-14 ( JAJAT & EDI & ADI & UNJ AZRIEL & DADANG )
|
|
2026-07-23
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-MD1-&-363-FN1-&-363-FN2
|
Observation noise motor
|
Check noise motor 363 MD1 of FS and LS result LS around 2,4 gE add grease motor 15 times-FS noise 9.85 gE; 363FN1 noise LS and FS around 1.5 gE add grease motor 15 times; 363 FN2 noise motor LS 2,4 gE add grease motor 15 times-FS noise around 2.3 gE add grease motor 15 times ( CBM NAJIB & ADI & UNJ AZRIEL )
|
|
2026-07-23
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Clean up flange probe-sample line tube-filter sample line-diaphragm pump-filter baslton from dirty of coal use instrument air supply and equipment cleaning tools. Check function humidity sensor and filter humidity result function humidity sensor normal and filter humidity good ( RIZAL & ANDRI )
|
|
2026-07-22
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-FN1
|
Replace AUTO grease tank issue low level
|
Replace 3 unit AUTO grease tank because existing low level with spare unit ( EDI & ADI )
|
|
2026-07-22
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-2K2
|
Cleaning_ Service Filter
|
PMR service analyzer such as clean up flange probe-sample line tube-filter sample line-diaphragm pump-filter balston from dirty of dust use equipment cleaning tools and instrument air supply. Check function humidity sensor and filter humidity result function humidity sensor normal and filter humidity good ( RIZAL & ANDRI )
|
|
2026-07-22
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Support Team Safety for Tools Inspection
|
Do support team safety and student university at job training for inspection electrical and welding tools ( EDI & ADI & SAFETY JOKO & STUDENT UNIVERSITY JOB TRAINING )
|
|
2026-07-22
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-L63-RM1
|
Add grease motor of 363 FN1-363 FN2-363 MD1-L63 MD1-483 BL5-483 BL9 issue noise motor high
|
Check actual noise with CBM Mr. Najib at 363 FN2-363 FN1 of FS & LS result noise FN2 FS 2.42 gE-LS 1.81 gE-FN1 noise FS 0.85 gE-LS 0.94 gE add grease for FS 15 times of FS and LS at FN2-add grease 15 times for FS and LS at FN1; 363 MD1 check noise motor at FS result 0.35 gE LS 2.4 gE add grease 15 times; check noise motor at L63 MD1 FS and LS add grease motor 20 times at LS and 15 times at FS; add grease motor 10 times at 483 BL5 for FS and LS; add grease motor 10 times for FS and LS at 483 BL9 ( EDI & ADI & NAJIB CBM )
|
|
2026-07-22
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
IDO-TANK-&-L1C-BC1-&-L1C-BC4
|
WBI Elect & Ins & Check I/O CM,Sump T&T
|
Do WBI Elect & Ins & Check I/O CM, Sump T&T. Test function sump pump and clean up motor sump pump result function good and area motor clean note at area sump pump L1C BC4 dirty of coal need clean up ( EDI & ADI )
|
|
2026-07-21
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
PMR service CEMS
|
Clean up purge air unit motor and filter motor from dust use instrument air supply. Dust hunter: clean up flange with tube-swivel window T/R-R unit-alignment result normal function. Flowsic 100: clean up transducer A & B also flange from dirty of dust use equipment cleaning tools and instrument air supply. CEMS room: clean up CEMS room analyzer-filter cabinet 0f MCS 100E-CEMS gas room from dirty of dust use equipment cleaning tools and instrument air supply ( RIZAL & UNJ AZRIEL & ANDRI )
|
|
2026-07-21
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-FN1-&-363-FN2-&-L1C-TL1
|
Greasing motor noise 2.6 gE-2.9 gE. Vibrator not tight
|
Check actual noise with CBM team Mr. Najib found 363 FN2 for LS and FS below 2 gE but 363 FN1 for FS noise 2.5 gE add grease 15 times measure noise result 0.85 gE and for LS noise below 1 gE. Check noise at 363 MD1 for FS below 1 gE but LS 2.4 gE add grease 15 times measure noise 1.5 gE Check at location found support vibrator broken at round bar. Repare round bar by mechanic team result function vibrator normal ( EDI & ADI & DADANG & CBM NAJIB ) .
|
|
2026-07-20
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1
|
Continue project upgrade analyzer
|
Do continue project upgrade 463 2K1 and install 3 LCS with canopy ( AGUS & MUHAIMIN )
|
|
2026-07-20
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-FN1-&-HYDRAULIC-ROOM
|
Continue project upgrade 463 2K1- issue lighting lamp off Replace or install lighting lamp
|
Do continue project upgrade 463 2K1. Replace and install lighting lamp at 443 FN1 also hydraulic room test function lighting lamp result lighting lamp normal on ( RIZAL & UNJ AZRIEL & ANDRI & DADANG )
|
|
2026-07-20
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-473-CC1
|
PMR Service Crit Motor & LSR KL & Cooler
|
Clean up area motor and filter motor. Measure vibration-noise of FS and LS, add grease motor 25 times- 30 times for FS and LS make vibration below 4 mm/s and noise below 2 gE. Check at ER5 and ER4 for RPM-KW-Voltage-Ampere-Temperature and fill in at check sheet ( MUHAIMIN & AGUS )
|
|
2026-07-20
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR service critical motor LSR RM-CM
|
Clean up area motor and filter motor. Measure vibration-noise of FS and LS, add grease motor 15 times for FS and LS make vibration below 4 mm/s and noise below 2 gE. Check at ER3 and ER4 for RPM-KW-Voltage-Ampere-Temperature and fill in at check sheet ( EDI & ADI )
|
|
2026-07-17
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1
|
Module no 4 DI station 74 Preheater Error
|
Replace module and check power 24 VDC result normal indication at panel I/O also CCR ( JAJAT & MUAIMIN )
|
|
2026-07-17
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
433-BE1-&-433-SG8
|
Issue appear indication D4 & Issue stop kiln indication DO close still open
|
Check limit switch and repare incline plat of 433 BE1 result normal indication. Check limit switch and cylinder also indication open-close at CCR result in accordance ( AGUS & MUHAIMIN )
|
|
2026-07-17
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-MD1-&-473-FN7
|
Check or replace CB
|
Clean up carbon brush room from dirty of dust use instrument air supply. Check and replace carbon brush area 463 MD1 and 473 FN7 result 1 CB area 463 MD1 with spare unit because bad condition ( EDI & DADANG )
|
|
2026-07-17
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
453-PF1
|
Calibration zero and span ( reset all CF )
|
Do calibration dynamic zero and span for 453 PF1 result good ( RIZAL & UNJ AZRIEL & ANDRI )
|
|
2026-07-17
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
413-3B1-&-3B2
|
Clean up panel I/O
|
Clean up panel I/O of 413 3B1-413 3B1-panel power supply-panel solenoid valve from dirty of dust use hand blower also equipment cleaning tools ( ADI & JAJAT )
|
|
2026-07-16
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
PMR service CEMS
|
Clean up area motor purge air unit and filter purge air unit-flange with tube of Dust Hunter-swivel window of Dust Hunter-alignment Dust Hunter result good-transducer A & B of Flowsic 100-CEMS room-CEMS gas room-filter cabinet MCS 100 E from dirty of dust use instrument air supply and equipment cleaning tools ( RIZAL & ANDRI )
|
|
2026-07-16
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
issue cable drum frequently slip down
|
Clean up are cable drum and adjustment sensor result ok ( AGUS & MUHAIMIN & DADANG )
|
|
2026-07-16
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-BF1
|
Replace lighting lamp 1 each area L63 BF1
|
Replace 1 lighting lamp test function result good ( MUHAIMIN & DADANG )
|
|
2026-07-16
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
PLANT-BUILDING-WORKSHOP
|
Inspection electrical and welding tools Civil building
|
Do inspection electrical and welding tools of plant building, tagging equipment blue color note repare some extention cable and portable lamp because cable ground not connected ( EDI & ADI & UNJ AZIEL )
|
|
2026-07-15
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-BF1
|
Replace lighting lamp 2 unit issue lighting lamp off
|
Replace 2 unit lighting lamp at L63 BF1 test function result lighting lamp on ( AGUS & MUHAIMIN & ANDRI & DADANG )
|
|
2026-07-14
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
PANEL-INPUT-OUTPUT
|
Station NL1 Node 2 error
|
Data line broken because trouble at switch gear solved ( JAJAT & AGUS )
|
|
2026-07-14
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-CT1-&-463-2K1
|
Solenoid Valve Water no 19 , Issue Leaked
|
Replace membrane solenoid valve of water test function result gun no 19 of water no leakage ( MUHAIMIN & ANDRI )
|
|
2026-07-14
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR service critical motor LSR RM-CM
|
Clean area motor and filter motor also clean filter motor of 363 FA2 from dirty of dust use instrument air supply. Measure vibration-noise-temperature of FS and LS add grease motor 20 times and 25 times of FS and LS. Check KW-Ampere-Voltage-Temperature motor at ER3 and ER4 also fill in at check sheet ( AGUS & DADANG )
|
|
2026-07-14
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ROOM-VSD-WF-AND-AC
|
Check cooling area VSD WF and AC
|
Check function cooling fan of area WF and AC result normal function. Clean up area room VSD area WF and AC note equipment tools are not available need make available make easy to clean up area vSD WF and AC ( ADI & AIMAN )
|
|
2026-07-13
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-FA6
|
Issue reading of N1 vibration low
|
Do replace sensor vibration and tighten sensor vibration result reading vibration 1.2 mm/s ( MUHAIMIN & UNJ AZRIEL & DADANG )
|
|
2026-07-13
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
STATION-22
|
Pulling profibus cable station 22 to IKGA
|
Pulling cable profibus from IKGA to station 22 ( MUHAIMIN & ANDRI & DADANG & ADI )
|
|
2026-07-13
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-473-CC1-&-463-KL1
|
PMR Service Crit Motor & LSR KL & Cooler & CM
|
Clean up area motor and filter motor. Measure vibration-noise-temperature of FS and LS motor also add grease motor 25 times and 30 times. Check at ER4 and ER5 for RPM-Voltage-Ampere-KW-Temperature of motor and fill in at check sheet ( MUHAIMIN & UNJ AZRIEL & DADANG )
|
|
2026-07-13
2 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe-probe-sample filter-tube sample line-diaphragm pump-filer balston from dirty of dust use equipment cleaning tools. Check function humidity sensor and filter humidity result function humidity sensor normal and filter good condition ( ADI & ANDRI )
|
|
2026-07-10
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Continue create station 23 analyzer. Fabrication structure control and station 423 2K1
|
Do fabrication structure control and station 423 2K1 result ok ( AGUS & MUHAIMIN & UNJ AZRIEL )
|
|
2026-07-10
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Clean up flange probe-filter sample line-sample line-diaphragm pump-filter balston from dirty of dust coal. Check function humidity sensor and filter humidity result function humidity sensor normal and filter good condition ( RIZAL & EVE INDY &ANDRI )
|
|
2026-07-10
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
4D3-LA1
|
Install motor
|
nstall motor and rectifier test function result normal ampere motor 2.3 DC to 2.5 DC ( EDI & ADI & EVE ABY & EVE ELGI & DADANG )
|
|
2026-07-09
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Check test final wiring project 463 2K1-re installation wiring + Install
|
Testing Wiring by life line + Install Fan Blower ( AGUS & MUHAIMIN )
|
|
2026-07-09
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3-&-ER4-&-ER5-&-ER6
|
Inspection electrical room thermograph
|
Do inspection thermograph electric room 3-4-5-6 ( EDI & DADANG )
|
|
2026-07-09
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
PMR service CEMS
|
Clean up filter purge air unit-swivel window T/R and R of dust hunter-Flange with tube from dirty dust: clean up transducer A and B flowsic 100 from dirty dust. Clean up CEMS room-filter cabinet MCS 100E-CEMS gas room from dirty of dust use instrument air supply (RIZAL & ANDRI )
|
|
2026-07-09
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP-PINCURAN-MAS
|
Inspection electrical tools
|
Do inspection electrical tools of PT Pincuran Mas. Tagging equipment with blue color. Repairing the cable ground of portable lamp 2 units, note : 1 extention cable not safe because 2 cover missing ( ADI & EVE ABY & EVE INDY )
|
|
2026-07-08
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Continue Project 463-2K1 Re-installation -wiring + Prepare New Station
|
Re installation and wiring also testing result ok. Prepare of new station 60% ( AGUS & MUHAIMIN )
|
|
2026-07-08
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-&-443-PH1
|
PMR service analyzer
|
Do clean up flange probe-probe-filter sample line-sample line-diaphragm pump-filter balston from dirty of dust use instrument air supply. Check function humidity sensor and filter humidity result function humidity sensor good and filter humidity normal also dry ( RIZAL & EVE ABY & EVE INDY & CIVACON EMPLOYEE )
|
|
2026-07-08
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1-&-463-KL1-&-BURNER-FLOOR
|
PMR Service burner pyrometer-IR TAD temperature-T scanner-CCTV
|
Do clean up flange probe also lens Temperature IR TAD result temperature 920 degree celcius-clean up lens of T scanner found before dirty of dust-clean up CCTV such as lens also camera unit form dirty of dust use equipment cleaning tools-clean up camera burner such as probe of camera, panel instrument air, panel control PLC, dryer oil and water from dirty of dust use hand blower and equipment cleaning tools note lens of t scanner east side cracked advice need to replace with spare unit ( ADI & EVE ELGI )
|
|
2026-07-07
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
Issue O2 high indication
|
Check at site do test gas of O2 result normal .Do monitoring O2 reading ( RIZAL & EVE INDY & ANDRI )
|
|
2026-07-07
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
LA3-VA2
|
Prepare-install-fabrication replacement proportional valve
|
Replace Proportional Valve, test Normal ( RIZAL & EVE ABY & EVE INDY & ANDRI )
|
|
2026-07-07
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Complete form WBI and PMR month June 2026 + Create SOT for all team
|
Complete data check sheet PMR analyzer L63 2K1-L63 2K2-L63 2K3-483 2K1-463 2K1-443 2K1-423 2K1; PMR Hoist-Crane-PMR IR TAD-T Scanner-CCTV-Camera Burner-WBI electrical & instrumentation bottom blending_kiln_cooler_clinker silo-WBI electrical & instrumentation top blending_CT_PH_klin for month March to June 2026. Make SOT for month of July 2026 ( JAJAT & ADI & EVE ELGI )
|
|
2026-07-07
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Inspection electrical tools of PT Pincuran Mas
|
Do inspection electrical tools of PT Pincuran Mas. Tagging tools use blue color note 1 extention cable not safe because not full fill safety requirement SBI ( JAJAT & ADI )
|
|
2026-07-07
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
4D3-LA1
|
Info control trafo failure and issue motor burned
|
Check voltage at transformer result value below. Replace transformer and do megger test result good. Install new transformer and do monitoring ( EDI & EVE ELGI & DADANG )
|
|
2026-07-06
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-BF1
|
Calibration and install pressure transmitter PDT 2001-2002
|
Do calibration zero and span for 423 PDT 2001 and 423 PDT 2002 with range pressure transmitter 0-20 mbar result drift good. Install pressure transmitter at site and check reading pressure result normal indication ( RIZAL & ADI & EVE ELGI & EVE INDY & ANDRI )
|
|
2026-07-06
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-473-CC1
|
PMR Service Crit Motor & LSR KL & Cooler
|
Clean up area motor and filter motor from dirty of dust use instrument air Measure vibration-noise-temperature of FS and LS add grease motor for FS and LS 30 times and 25 times make vibration below 4 mm/s and noise below 2 gE. Check at ER5 and ER4 for data RPM-Voltage-Ampere-KW-Temperature motor and fill in at check sheet ( MUHAIMIN & DADANG )
|
|
2026-07-06
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR service critical motor LSR RM-CM
|
Clean up area motor and filter motor from dirty of dust use instrument air Measure vibration-noise-temperature of FS and LS add grease motor for FS and LS 20 times and 25 times make vibrationbelow 4 mm/s and noise below 2 gE. Check at ER3 and ER4 for data RPM-Voltage-Ampere-KW-Temperature motor and fill in at check sheet. Also cleanup 363 FA2 of filter motor from dirty of dust use instrument air supply ( EDI )
|
|
2026-07-06
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-BF1
|
Calibration and install pressure transmitter PDT 2001-2002 and install unit at site
|
Do calibration zero and span for 423 PDT 2001 and 423 PDT 2002 with range pressure transmitter 0-20 mbar result drift good. Install pressure transmitter at site and check reading pressure result normal indication ( RIZAL & ADI & EVE INDY & EVE ELGI & ANDRI )
|
|
2026-07-03
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Clean up flange probe-sample line- filter sample line - diaphragm pump - filter balston from dirty of coal. Check function humidity sensor and filter humidity result function humidity sensor good and filter humidity normal condition ( EDI & DADANG )
|
|
2026-07-03
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-BF1
|
Calibration pressure transmitter and install calibration pressure
|
Do make addressing-unit-range of pressure transmitter. Calibration zero and span result good. Install pressure transmitter at site and cross check reading pressure at CCR result normal reading ( RIZAL & ADI & ANDRI & EVE ABY & EVE ELGI & AZRIEL UNJ )
|
|
2026-07-02
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-483-BL5-483-BL9-&-443-WP1-443-WP2MD1-
|
Add grease motor. Check motor condition & test run
|
Add greasing motor for LS and FS for L63 MD1-483 BL5-483 BL9. Measure vibration-noise make below 4 mm/s and below 2 gE. Do check motor condition for 443 WP1 & 443 WP2 also test run ( EDI & DADANG )
|
|
2026-07-02
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1-&-463-KL1-
|
Inspection electrical and welding tools of PT Truba Jaga Cita
|
Do inspection electrical and welding tools of PT Truba Jaga Cita at 8th 443 Ph1 and 463 KL1 bottom floor tagging tools use blue color ( ADI & EVE ABY & EVE ELGI )
|
|
2026-07-01
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TL1
|
Install and fabrication box terminal pf L1C BC2 - cleaning control also RADIO LINK L1C TR1
|
Released Old Box + Install -reconnection New Box Released old box and install new box also do reconnection ( JAJAT & EDI & DADANG & AIMAN )
|
|
2026-07-01
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1-&-333-WF3
|
Install Fidor + Testing Sample & Issue Rate WF --0 t/h
|
Install + Calibration ---Done, result function FIDOR normal Replace load cell - monitor note WF not calibration issue material full( RIZAL & ANDRI & EVE ABY & EVE ELGI )
|
|
2026-06-30
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
TRUBA-JAGA-CITA;
|
Inspection electrical and welding tools
|
Do inspection electrical and welding tools of PT Truba Jaga Cita, note repare connection extention cable 2 units. Tagging tools with bule color ( ADI & EVE ELGI )
|
|
2026-06-30
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe-probe-filter sample-sample line-diaphragm pump-filter balston from dirty of dust use instrument air supply. Check function humidity sensor and filter humidity result function humidity sensor normal and filter good condition ( RIZAL & EVE ABY & EVE ELGI & ANDRI )
|
|
2026-06-30
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1
|
Pulling cable from new I/O panel to room analyser
|
Do pulling cable from new panel I/O to 463 2K1 room of 6 cable and put at cable tray ( JAJAT & EDI & ADI & DADANG & 2 CIVACON )
|
|
2026-06-29
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
Issue reading O2 high
|
Check at site O2 reading high.. do calibration zero and span O2 run MCS100E reading O2 still high. Try disconnect FIDOR and also run MCS 100E reading O2 7-8%. Suspected s/v for zero gas FIDOR bad condition or dirty service s/v of zero gas FIDOR and install at site. Run MCS 100E result O2 reading still high. Not connected sample line FIDOR reading O2 7% note instrument air must be oil and water free suspected filter instrument air replace with spare unit ( RIZAL & EVE ABY & ANDRI )
|
|
2026-06-29
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR service critical motor LSR RM-CM
|
Clean up area motor and filter motor. Measure vibration-noise-temperature FS and LS motor continue add grease motor 20 times and 15 times for FS and LS make vibration below 4 mm/s-noise below 2 gE also 363 FA2 at 363 MD1 filter motor. Check at ER3 and ER4 for RPM-Voltage-Ampere-Temperature motor and fill in at check sheet form ( EDI & ADI )
|
|
2026-06-29
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
CM-&-KILN-&-CC1
|
PMR Service Crit Motor & LSR KL & Cooler
|
Clean up area motor and filter motor. Measure vibration-noise-temperature FS and LS motor continue add grease motor 25 times and 30 times for FS and LS make vibration below 4 mm/s-noise below 2 gE. Check at ER4 and ER5 for RPM-Voltage-Ampere-Temperature motor and fill in at check sheet form ( MUHAIMIN & DADANG )
|
|
2026-06-26
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Make notification for WBI Elect & Inst Feed bin-RM-CT-Dust Transport-BF
|
Do make notification for job WBI Elect & Inst Feed bin-RM-CT-Dust Transport-BF ( ADI & EVE ELGI )
|
|
2026-06-26
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-MD1
|
Blower Cooling MC burn
|
Replace -Test Blower ( AGUS & MUHAIMIN & DADANG )
|
|
2026-06-26
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
PMR service analyzer
|
Clean up flange probe-sample line-filter sample line-diaphragm pump-filter balston from dirty of coal use instrument air supply and equipment cleaning tools. Check function humidity sensor and filter humidity result function humidity sensor good and filter humidity normal ( RIZAL & EVE ABY & ANDRI )
|
|
2026-06-26
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
BLENDING-&-COAL-MILL-&-IDO-BIN
|
WBI Elec & Ins & Check I/O & S Pump Bl-,C (Area Kiln
|
Do WBI Elec & Ins & Check I/O & S Pump Bl,-C (Area Kiln ). Test sump pump L1C BC4 note area very dirty of coal dust need clean-L1C BC1 note area sump pump much dirty of coal need clean up-IDO bin-L63 HS1 result good function. Clean up I/O panel area clinker silo at bottom floor-area cooler-area kiln from dirty of dust use equipment cleaning tools (EDI & ADI )
|
|
2026-06-25
3 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
363-BE1-M1
|
Install transducer Amp
|
Replace transducer ampere at 363 BE1, do test function result ok ( EDI & MUHAIMIN & DADANG )
|
|
2026-06-25
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP-&-463-2K1
|
Prepare + Redrawing 463-2K1 Upgrade
|
Prepare upgrade 463 2K1 and redrawing at computer ( AGUS & MUHAIMIN & DADANG & EDI )
|
|
2026-06-25
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
Issue O2 drift 16%
|
Do calibration zero and span for O2 result drift below 1% good ( RIZAL & EVE ABY & EVE ELGI & ANDRI )
|
|
2026-06-25
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Support TPM Document
|
Do make report of TPM for AM month June 2026 and safety finding 3 file continue print out and install at dash board TPM work shop ( RIZAL & ADI )
|
|
2026-06-24
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Prepare + Redrawing 463-2K1 Upgrade
|
Do redrawing upgrade 463 2K1 ( JAJAT & AGUS )
|
|
2026-06-24
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L3C-RE1
|
Install Power Point
|
Install power point at L3C RE1 continue painting support and canopy with grey color ( EDI & ADI & EVE ELGI )
|
|
2026-06-24
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-2K2-&-443-FN1-P1
|
Cleaning Sample Line and Filter sample line & issue draft low indication
|
Do cleaning sample line tube and filter sample line from dirty of dust use instrument air supply and equipment cleaning tools. Check at site found power common contact lose for 110 VAC take power 110 VAC from 443 2K2 note contact relay for purging result function purging normal ( MUHAIMIN & ANDRI & EVE ABY )
|
|
2026-06-23
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
333-BC1-&-363-SR1
|
Add grease motor issue high vibration and noise
|
Add grease motor of FS and LS measure vibration-noise for FS and LS result vibration below 4 mm/s and noise below 2 gE ( JAJAT & EDI )
|
|
2026-06-23
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-WF1
|
Issue contractor trip failure often exist
|
Check at site and do replace address for RUN result ok ( AGUS & JAJAT & MUHAIMIN )
|
|
2026-06-23
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1
|
Repare and fabrication travelling probe
|
Do fabrication of travelling probe continue install at site test function probe retract-inset result good ( RIZAL & DADANG )
|
|
2026-06-23
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-BF1-T3
|
Issue indication more high
|
Cross check indication temperature compare with CCR reading different do adjustment range at local make same with local value ( RIZAL & DADANG )
|
|
2026-06-22
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
413-BE1
|
Issue nut untighten
|
Do tighten nut of 413 BE1 result ok ( RIZAL & MUHAIMIN )
|
|
2026-06-22
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-WF1
|
Issue Trip Failure + hot are motor
|
Tightening terminal-fabrication blower of cooling motor and install at site ( RIZAL & MUHAIMIN )
|
|
2026-06-22
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-473-CC1-&-463-KL1-&-473-CC1
|
PMR Service Crit Motor & LSR KL & Cooler + Issue 473-FAA Issue Noise + Add greasing 473-FA4-5-6
|
Cleaning area motor and filter motor. Measure vibration-noise-temperature of FS and LS motor. Add grease motor 25 times-30 times of FS and LS. Check at ER5 and ER4 for RPM-Voltage-Ampere-kW-Temperature motor fill in at check sheet form. Add grease motor for FS and LS for 473 FAA measure noise motor below 2 gE also add grease motor for 473 FA4-FA5-FA6 for FS and LS measure vibration-noise of FS and LS result vibration below 4 mm/s and noise below 2 gE ( AGUS & DADANG )
|
|
2026-06-22
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1&-393-RF4-&-393-SC3
|
PMR Service Critical Motor & LSR RM&CM1, Issue lighting lamp for 333 BC1 and bel feed separated-Cover Motor un connected-Speed Switch Failure
|
Cleaning area motor and filter motor. Measure vibration-noise-temperature of FS and LS motor. Add grease motor 15 times-20 times of FS and LS. Check at ER3 and ER4 for RPM-Voltage-Ampere-kW-Temperature motor fill in at check sheet form. Do separated power lighting lamp for 333 BC1 and bel feed test function result normal-Install cover motor for 393 RF4 result function normal- Do adjust position of probe speed sensor result normal error speed failure off( EDI & ADI )
|
|
2026-06-19
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Test run motor no load
|
Do test run no load of motor result normal ( AGUS & RIZAL & MUHAIMIN & ANDRI )
|
|
2026-06-19
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3
|
Connect cable DO from ABB to Yokogawa FABA
|
Check at ER3, continuity cable and wiring cable of DO at relay at panel I/O test function result ok ( JAJAT & EDI & FIRMAN & DADANG & ADI )
|
|
2026-06-19
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-BL9-M1
|
Issue overload
|
Check at site found finger bar burned, replace cable and pulling cable continue connected cable and terminated ( JAJAT & AGUS & EDI & RIZAL & ADI & ANDRI & MUHAIMIN & DADANG )
|
|
2026-06-19
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-2K2
|
Pulling cable of heater & modification contact
|
Do pulling cable power of heater and modification contact heater at 443 2K2 result function normal ( AGUS & MUHAIMIN & DADANG )
|
|
2026-06-19
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
BURNER-FLOOR
|
Camera Kiln Abnormal View
|
Do dismantle camera kiln and clean up lens. Reinstall camera kiln result picture available at operator CCR ( JAJAT & RIZAL & ANDRI )
|
|
2026-06-18
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-BL9
|
Issue Hot Point
|
Install Blower , Monitor Max 80 Deg celcius - Monitor ( AGUS & MUHAIMIN )
|
|
2026-06-18
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1-&-BURNER-FLOOR-&-463-KL1
|
PMR CCTV-IR TAD-T Scanner-Camera Burner
|
Do PMR CCTV-IR TAD-T scanner-camera burner. Clean up CCTV camera glasses- IR TAD probe glasses- T scanner camera glasses and camera burner probe also glasses from dirty of dust process use equipment cleaning tools and instrument air supply ( AGUS & MUHAIMIN )
|
|
2026-06-19
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-EP1-&-443-PH1-&-463-KL1
|
WBI Elec & Ins & Check I/O GCT, EP,PH&KL
|
Do WBI Elec & Ins & Check I/O GCT, EP,PH&KL. Measure vibration-noise motor and fill at check sheet high vibration motor up to 4 mm/s ( EDI & ADI )
|
|
2026-06-18
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-423-BF1-FFED-BIN
|
WBI Electric & Ins & Check I/O Feed Bin
|
Do WBI Electric & Ins & Check I/O Feed Bin. Clean up area 423 BF1 room from dirty of dust use instrument air supply. Measure vibration-noise motor area 393 FA4-443 WP4,5,6-443 FN1-363 FN1-363 FN2-333 AC1& 333 SX1-333 AC2 & 333 SX2-333 WF1 to WF4-333 BC1-363 SR1-363 CV1 & CV2-363 LQ1 M1 & M2 note area motor dirty of dust need clean up some motor vibration and noise high ( up to 4 mm/s-up to 2 gE ) ( ADI & DADANG )
|
|
2026-06-17
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-EL1-&-SUMP-PUMP
|
PMR Elevator & WBI sump pump
|
Clean up elevator room door and top side-VSD room 8th floor from dirty of dust use hand blower test function elevator form 8th to 1st floor result normal. Check function of sump pump at L63 HS1-IDO tank-L1C BC1-L1C BC4 note: L63 HS1 need install pipe conduit cable of cable power sump pump- IDO tank need clean up sump pump and install flow siwtch-L1C BC1 & L1C BC4 need clean up area from dirty of wet dust coal make performance sump pump good ( AGUS & ADI )
|
|
2026-06-17
3 months ago
|
NR.EL-02
|
Wahyu Adi Triono
|
463-2K1-&-333-WF4
|
Observation installation Circulation Valve LA3-VA4. & issue cooling fan of iron sand
|
Prepare material of installation circulation valve LA3 VA4 and install at site result ok Do replace cooling fan of iron sand test function motor result good ( MUHAIMIN & DADANG & AIMAN )
|
|
2026-06-17
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
PMR service CEMS
|
Clean up purge air unit motor and filter motor. Dust Hunter: clean up flange with tube-swivel window-aligmment TR & R unit. Flowsic 100: transducer A & B. MCS 100 E: filter cabinet. FIDOR: filter cabinet. CEMS room & gas CEMS room: clean area from dirty of dusy use instrument air supply ( RIZAL & ANDRI )
|
|
2026-06-15
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
BURNER-FLOOR
|
Camera Kiln , IP No respond
|
Replace connector LAN for camera test function IP result normal and view camera available at computer CCR ( RIZAL & ANDRI )
|
|
2026-06-15
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe-probe-filter sample line-sample line tube-diaphragm pump-filter balston from dirty of dust use instrument air supply. Check function humidity sensor and filter humidity result function humidity sensor normal and filter good condition ( RIZAL & ANDRI )
|
|
2026-06-15
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-473-CC1
|
PMR Service Crit Motor & LSR KL & Cooler
|
Clean area motor and filter motor. Measure vibration-noise-temperature FS and LS motor add grease motor 25 times and 20 times for FS also LS. Check RPM-Voltage-Ampere-Temperature motor at ER5 and ER4 fill in at check sheet form ( EDI & DADANG )
|
|
2026-06-15
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-L63-CM1-463-KL1-473-CC1
|
PMR service critical motor LSR RM-CM
|
Clean area motor and filter motor. Measure vibration-noise-temperature FS and LS motor add grease motor 16 times and 15 times for FS also LS. Check RPM-Voltage-Ampere-Temperature motor at ER3 and ER4 fill ini at check sheet form ( EDI & ADI )
|
|
2026-06-12
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1
|
Reactivation automatic filling water
|
Do make reactivation for automatic filling water test function result normal also clean up filter motor compressor and filter sample line from dirty of dust use instrument air supply ( JAJAT & RIZAL & MUHAIMIN & ANDRI )
|
|
2026-06-12
3 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1
|
Cross Check Lamp Area PH 2 and 3 floor
|
Replace cable power lighting lamp at 2nd floor at north side and replace lighting lamp test function lighting lamp result normal ( EDI & ADI & DADANG )
|
|
2026-06-11
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-WB2-M1
|
Issue unbalance ampere motor
|
Check at site found cable motor is not tighten, make tighten cable motor result ampere motor balance note install SOP check problem at motor ( JAJAT & MUHAIMIN & EVE FARAH )
|
|
2026-06-12
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Completely electrical Drawing 443-2K2
|
Do make drawing for electrical at 443 2K2 ( AGUS )
|
|
2026-06-11
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1
|
issue leakage O2
|
Check at site 443 2K1 found there is leakage tube at diaphragm pump to humidity sensor use silicone and isolation electrical to cover leakage of tube ( RIZAL & ANDRI )
|
|
2026-06-11
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
FEED-BIN
|
Issue level Tonnage Limestone Sensor error (Load Cell)
|
Do tighten cable power and output at sensor result indication normal ( JAJAT & MUHAIMIN & EVE FARAH )
|
|
2026-06-10
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-BU1&-363-HS2
|
Relocation sensor flow to calciner. Stop Local
|
Relocation flow sensor for Reference calibration. Repare Cable , Done ( EDI & DADANG )
|
|
2026-06-10
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Modification roof SW L1 BC4, repare all safety device-test safety device
|
Modification roof SW at L1C BC4 also repare all safety device area L1C BC1 to L1C BC7 and test function safety device result normal (JAJAT & AGUS & EDI & RIZAL & MUHAIMIN & ANDRI & DADANG )
|
|
2026-06-10
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-2K2
|
Activation lamp for collective fault
|
Do activation lamp lamp of collective fault ( MUHAIIN & ANDRI )
|
|
2026-06-09
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-2K2
|
Continue electrical drawing and test signal
|
Do drawing electrical continue test signal result normal ( AGUS & MUHAIMIN )
|
|
2026-06-09
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L3C-TR1
|
PMR Inspection Motor Area Tripper ( L1C_BC1 to BC7 ) and TLS
|
Do PMR motor area tripper for L1C BC1-L1C BC2-L1C BC3-L1C BC4-L1C BC5-L1C BC6-L1C BC7 and check TLS note cable gland for probe speed sensor at L1C BC1 & L1C BC3 not connected action reconnected cable gland result ok-rope of TLS L1C BC4 east side not connected action reconnected rope of TLS-rope TLS north side L1C BC5 not connected action reconnected rope. Also check function of sump pump at L1C BC1 and L1C BC4 result function good ( EDI & ADI )
|
|
2026-06-08
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-FA2
|
Check vibration-noise of FS and LS
|
Measure vibration-noise FS and LS result vibration below 4 mm/s-noise below 2 gE add grease motor 10 times for FS and LS motor ( EDI & ADI & DADANG )
|
|
2026-06-08
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-2K2
|
Make programe off delay at LOGO around 2s for input 1-2-3
|
Do make program for off delay 2 second at LOGO for input 1-2-3 ( RIZAL & EVE ILHAM & UNJ AZRIEL )
|
|
2026-06-08
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-2K2
|
activation proximity level sensor signal N-M input to LOGO 110 VAC for output DC and labelling push button signal reset at 443 2K2-C1-ACK
|
Do activation proximity level sensor og signal N-M and labelling push button signal 443 2k2-C1-ACK result ok ( MUHAIMIN & ANDRI )
|
|
2026-06-08
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
443 2K2 re electric drawing upload to server manual book server
|
Redrawing of electrical for 443 2K2 and upload to server manual book ( AGUS )
|
|
2026-06-08
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-
|
Support feed on for KILN
|
Do support feeding of 463 KL1 ( AGUS & RIZAL & EDI & ADI & MUHAIMIN & ANDRI & DADANG & EVE ILHAM &UNJ AZRIEL )
|
|
2026-06-08
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ROOM-DIESEL-PUMP
|
Issue lighting lamp off
|
Check at location found cable phase and neutral joint, make different connection for cable phase and neutral, test function lighting lamp result normal lighting lamp on note replace MCB 10A ( EDI & ADI & DADANG )
|
|
2026-06-08
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-MD1-&-363-FA2
|
clean up CB room-filter motor 363 FA2-measure all CB replace if needed
|
Clean up 363 FA2 area motor and filter motor-area 363 MD1 and CB room from dirty of dust use instrument air supply and equipment cleaning tools. Measure long CB1 47.57-CB2 41.56-CB3 47.82-CB4 39.11-CB5 42.84-CB6 48.13-CB7 40.63-CB8 37.68-CB9 47.24-CB10 41.34-CB11 42.02-CB12 40.28 ( EDI & ADI & DADANG )
|
|
2026-06-07
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-BF1-&-L63-HS1-&-443-2K2-&-483-PF1-&-453-PF1
|
Issue zero value is big around 2.2 mbar. Recalibration for zero adjust-issue sump pump area many water or sump pump not working-rewiring cable for reset continue test function reset and alarm humidity-calibration zero and span
|
Check indication pressure of 423 BF1 PDT 2002 value 2.2 to 2.3 mbar same with CCR operator. Bring down pressure transmitter do zero adjustment result indication become 0.0 mbar output 4.00 mA. Install pressure transmitter at site result indication 0.1 mbar compare CCR around 0.2 mbar-Check at location area sump pump at L63 HS1 found there is no water and sump pump working normal-Do rewiring cable for reset at 443 2K2 continue test function result good also test function for alarm humidity result good-Do calibration zero at 483 PF1 with running blower and calibration zero-span for 453 PF1 with running blower result calibration good ( JAJAT & EDI & ADI & DADANG )
|
|
2026-06-07
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-BF1-PDT-2002-&-L63-HS1
|
Issue zero value is big around 2.2 mbar. Recalibration for zero adjust. Sump pump area many water or sump pump not working
|
Check indication pressure of 423 BF1 PDT 2002 value 2.2 to 2.3 mbar same with CCR operator. Bring down pressure transmitter do zero adjustment result indication become 0.0 mbar output 4.00 mA. Install pressure transmitter at site result indication 0.1 mbar compare CCR around 0.2 mbar. Check at location area sump pump at L63 HS1 found there is no water and sump pump working normal ( EDI & ADI & DADANG )
|
|
2026-06-04
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-SX1
|
Repare coupling Motor
|
Do dismantle motor L63 SX1 bring to workshop repare by mechanic team replace coupling motor ( JAJAT & ADI & MUHAIMIN & DADANG )
|
|
2026-06-04
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-3B1
|
Issue indication often not accurate
|
Replace radar sensor ( RIZAL & ANDRI )
|
|
2026-06-03
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-BF1-&-443-2K1
|
Service JB 19 no 6 issue leakage & check addresing from CCR and create alarm to CCR
|
Make normal of JB 19 no 6 and monitoring. Input addresing new indicator of 443 2K1 and create program ( AGUS & MUHAIMIN & UNJ AZRIEL & DADANG & EVE ILHAM )
|
|
2026-06-03
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Clean up flange probe-sample line tube-filter sample line-diaphragm pump-filter balston from dirty of coal process. Check function humidity sensor and filter humidity result function humidity normal and filter humidity good condition ( RIZAL & ANDRI )
|
|
2026-06-03
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-BL5-&-483-BL9
|
Add grease motor
|
Do add greasing motor for FS and LS around 10 times and 20 times measure vibration-noise FS & LS: 483 BL9 2.6 mm/s-4.3 mm/s; 1.4 gE-5.02 gE ( EDI & ADI & EVE FARAH )
|
|
2026-06-02
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Make notification for job rewinding motor shell of kiln
|
Do make notification for job rewinding motor shell kiln: 463 FX5B-463 FX6-463 FX8-463 FX10 save at computer ( ADI & MUHAIMIN )
|
|
2026-06-02
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
BURNER-FLOOR
|
Reposition camera for view of fire
|
Do reposition camera burner for view fire result view fire available at computer operator ( RIZAL & MUHAIMIN & UNJ AZRIEL & ANDRI )
|
|
2026-06-02
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-473-CC1-&-463-KL1
|
PMR Critical Motor Area KL + CM + CC
|
Clean up area motor and filter motor. Measure vibration-noise-temperature FS and LS motor. Add grease motor for 15 times-20 times for FS and LS motor. Check RPM-Voltage-Ampere motor-Temperature motor at ER4-ER5 write at form check sheet ( AGUS & DADANG )
|
|
2026-06-02
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR Critical Motor Area RM
|
Clean up area motor and filter motor. Measure vibration-noise-temperature FS and LS motor. Add grease motor for 15 times-10 times for FS and LS motor. Check RPM-Voltage-Ampere motor-Temperature motor at ER3-ER4 write at form check sheet. Clean up area carbon brush room and filter 363 FA2 from dirty of dust use instrument air supply ( EDI & ADI )
|
|
2026-05-29
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1
|
Check motor shell cooling fan
|
Check at site for 463 FX 5B-463 FX6-463 FX8-463 FX10 result motor burned because short ground. Replace breaker result normal ( RIZAL & MUHAIMIN )
|
|
2026-05-29
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-FN1
|
Install cable power for Power Point
|
Install conduit pipe of cable power, pulling cable power from welding panel inside water pump room to power point. Do wiring cable power ( AGUS & MUHAIMIN & DADANG )
|
|
2026-05-29
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
TPM Assessment & Report
|
Complete data for assessment report and print out install at TPM board at workshop ( RIZAL )
|
|
2026-05-29
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
Check indication temperature roller of west side
|
Check at site for RTD roller coal mill measure resistance result 183 ohm. Rewiring cable RTD at cross check indication at CCR result around 83 degree celcius ( EDI & ADI & UNJ AZRIEL )
|
|
2026-05-28
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1-&-L63-RM1
|
Install AUTO grease pump
|
Install AUTO Grease motor at 363 FN1-363 FN2-423 FN1-443 FN1-L63 MD1-L63 FN1 ( AGUS & DADANG )
|
|
2026-05-28
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-FA5
|
Replace bearing motor issue high noise
|
Check at site found bearing motor bad condition, replace motor with spare unit check ampere motor result 10 to 11 ampere ( EDI & MUHAIMIN & ANDRI )
|
|
2026-05-28
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
IDO-TANK-&-L1C-BC1-&-L1C-BC4
|
WBI Elect & Ins & Check I/O CM,Sump T&T
|
Do clean up area sump from grass-leaf-coal use equipment cleaning tools. Test function sump pump local mode result sump pump work good water come out from tank sump pump Note grass at IDO tank already not tidy, need to tidy up grass ( ADI & UNJ AZRIEL & EVE ILHAM & EVE FARAH )
|
|
2026-05-26
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-BE1
|
Issue speed failure at CCR operator
|
Check at site found probe speed sensor failure, replace probe speed use spare unit result speed indication normal ( JAJAT & MUHAIMIN & DADANG )
|
|
2026-05-26
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1
|
Cross Check temperature Cyclone 4 north and south (Gas Material)
|
Cross check indication temperature at cyclone north and south for gas material compare with CCR. Adjust range at local same with indication at local ( RIZAL & ANDRI )
|
|
2026-05-26
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
333-MS1
|
Optional installation MS
|
Check actual motor at warehouses find 1 motor but different shaft motor. Continue check at FM warehouses find motor 22 KW and shaft motor 50.1 mm. Dismantle cover motor4 KW at workshop result all bearing failure and bad condition ( EDI & ADI )
|
|
2026-05-25
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1-&-463-2K1
|
Certification Flow Diesel Calciner & Travelling probe not smooth
|
Do certification diesel oil at calciner. Repare support travelling probe test function insert and retract probe result normal ( RIZAL & UNJ AZRIEL & EVE AJI & ANDRI )
|
|
2026-05-25
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Prepare AUTO Grease tank
|
Do prepare Auto Grease tank at workshop ( AGUS & JAJAT )
|
|
2026-05-25
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-473-CC1-&-463-KL1
|
PMR Critical Motor Area KL + CM
|
Clean up area motor and filter motor. Measure vibration-noise-temperature of FS and LS. Add grease motor for 25 times and 30 times for FS and LS motor. Check at ER4 and ER5 for RPM-Voltage-Ampere-Temperature for L63 MD1-L63 FN1-473 FN7-463 MD1 write at check sheet form ( MUHAIMIN & DADANG )
|
|
2026-05-25
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR Critical Motor Area RM
|
Clean up area motor and filter motor. Measure vibration-noise-temperature of FS and LS. Add grease motor for 15 times and 10 times for FS and LS motor. Check at ER3 and ER4 for RPM-Voltage-Ampere-Temperature for 423 FN1-363 FN1-363 FN2-363 MD1-443 FN1 write at chek sheet form Note area 363 MD1 inside CB room very dirty of dust. Advice clean up employee not use high pressure near filter 363 FA2 will make easy dirty of dust ( EDI & ADI )
|
|
2026-05-22
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-FA2
|
Recondition motor
|
Replace bearing motor, install at location test run motor measure vibration and noise of LS & FS motor result vibration below 4 mm/s and noise below 2 gE ( EDI & JAJAT & MUHAIMIN & DADANG )
|
|
2026-05-23
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-FA2
|
High vibration and noise motor
|
Measure vibration-noise-temperature result vibration 5.33 mm/s-noise 5.14 gE-temperature 45 degree celcius ( MUHAIMIN & DADANG )
|
|
2026-05-23
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-CV2
|
Issue speed failure
|
Check at location found speed sensor bad condition, replace speed sensor with spare unit rewiring cable test run363 CV2 result normal ( AGUS & EDI & ADI & IMAN )
|
|
2026-05-23
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
LA3-VA1
|
Install and fabrication vessel air tank
|
Do fabrication vessel air tank at workshop and install vessel tank of air and s/v water drain at vessel air tank and pulling cable power from welding panel test function water drain result good ( RIZAL & ANDRI )
|
|
2026-05-23
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-BC4
|
Pulling cable powerpoint from L1C BC4 to L1C BC5. Install power point
|
Take cable power for power point at feed bin bring to location. Install power point panel at L1C BC4 and pulling cable power of power point from welding panel of L1C bC5 to panel power point continue termination at panel note prepare water for make safe area of welding power point ( JAJAT & AGUS & EDI & ADI & MUHAIMIN & DADANG & IMAN )
|
|
2026-05-22
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1
|
Support sample Line broken
|
Do repare support sample line test function insert and retract of probe result good ( RIZAL & DADANG )
|
|
2026-05-21
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-FA2-M1
|
Ddismantle motor issue vibration motor high
|
Do dismantle motor at 483 FA2 M1 bring to workshop. Replace bearing 4 each install motor at site ( EDI & DADANG )
|
|
2026-05-21
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
453-PF1
|
Adjusment CF to 3 t/h Decrease
|
Do adjust CF at maximal note if still needed request adjust do calibration zero and span 453 PF1 ( RIZAL & UNJ AZRIEL )
|
|
2026-05-21
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WP3-WF1
|
Install lighting lamp
|
Install lighting lamp at WP3 WF1 test function lighting lamp result ok ( EDI & DADANG )
|
|
2026-05-20
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-443-CT1
|
PMR service analyzer & issue high temperature
|
Clean up flange probe-sample line-filter sample line-diaphragm pump-filter balston from dirty of coal. Check humidity sensor and sensor humidity result function humidity sensor normal and filter good condition. Cross check temperature result indication normal note still looking for of phenomenon build material ( RIZAL & ANDRI & UNJ AZRIEL & EVE ILHAM & EVE FARAH )
|
|
2026-05-19
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-BF1
|
Issue JB03 No 9 abnormal
|
Check at site. Do make all at normal position solenoid valve result function normal ( MUHAIMIN & DADANG )
|
|
2026-05-19
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1-&-463-KR2-T2
|
PMR service analyzer Cross check or replace
|
Clean up flange probe- probe-filter sample line-sample line-diaphragm pump-filter balston from dirty of dust use instrument air supply. Check humidity sensor and filter humidity result function humidity sensor normal and filter good condition. Replace sensor RTD at 463 KR2 T2 result normal check indication at CCR reading normal( RIZAL & UNJ AZRIEL & ANDRI )
|
|
2026-05-19
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
493-AC2-&-493-AC3
|
Check AUTO Grease motor and replace if needed
|
Check Auto Grease motor 493 AC2 and 493 AC3 found low level at tank Auto Grease. Replace Auto grease with spare unit test function result normal. Note environment at 493 AC4 is not good condition and safety because many clinker at floor cover until junction box and cable power. Need action to clean up environment at 493 AC4 ( EDI & ADI )
|
|
2026-05-18
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-BE1-M2
|
Install motor
|
Install +Connected Motor , test no load , Commissioning result normal ( MUHAIMIN & ANDRI & DADANG )
|
|
2026-05-18
4 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
423-2K1
|
PMR service CEMS and issue flame off at FIDOR
|
Check connection tube of Hydrogren reset power result flame on. Clean up purge air unit motor and filter purge air unit of Dust Hunter and Flowsic 100, clean up swivel windows T/R and R dust hunter-flange with tube-alignment dust hunter. Clean up transducer A & transducer B of flowsic, clean up up CEMS room and gas bottle-filter cabinet MCS 100 E from dirty of dust use equipment cleaning tools and instrument air supply (RIZAL & UNJ ASRIEL & EVE FARAH & ANDRI )
|
|
2026-05-18
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
CAMERA-BURNER
|
Issue Abnormal
|
Retighten connection of inside camera kiln and outside camera kiln. Insert camera kiln result normal ( MUHAIMIN & DADANG )
|
|
2026-05-18
4 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-473-CC1
|
PMR Service Crit Motor & LSR KL & Cooler
|
Clean up area motor and filter motor, Measure vibration-noise-temperature of FS and LS motor. Add grease motor for 15 times-25 times for FS and LS motor. Also replace battery for AUTO grease motor at 473 FA2-473 FA3-473 FA9-473 FAA-483 FA2 and replace tube of AUTO grease motor at 473 FA6 found tube leakage. Also check 483 BL1-483 BL2-453 BL6-483 BL7 add grease motor for 15 times for FS and LS ( AGUS & ADI & EVE ILHAM )
|
|
2026-05-11
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
BIN-SHALE
|
Calibration bin shale
|
Do calibration bin shale result good ( EDI & MUHAIMIN & DADANG & TRUBA CEPI )
|
|
2026-05-11
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Complete data calibration RTD area RM-CC-Kiln-CM
|
Complete data check sheet calibration RTD area RM-CC-KL-CM of OH 2026, scan file save at computer and send to Mr.Jajat ( JAJAT & ADI )
|
|
2026-05-11
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
333-MS1
|
Issue motor abnormal function
|
Check at site, found motor bad condition. Dismantle motor bring to work shop. Do clean up motor from dirty of dust and grease also oil ( AGUS & MUHAIMIN )
|
|
2026-05-11
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1-&-393-RF6
|
Install sensor temperature at location. Issue oil come inside motor
|
Install sensor temperature at location cross check indication result normal indication. Dismantle cove motor and drain oil from motor. Reinstall cover motor test run 393 RF6 result function normal no oil come inside motor ( EDI & ADI & TRUBA CEPI )
|
|
2026-05-11
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1&-393-RF6
|
Install sensor temperature at location. Issue oil come inside motor at 393 RF6
|
Install sensor temperature at location cross check indication result normal indication. Dismantle cove motor and drain oil from motor. Reinstall cover motor test run 393 RF6 result function normal no oil come inside motor ( EDI & ADI & TRUBA CEPI )
|
|
2026-05-10
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-BE1---473-FA6--473-FA7
|
Connected cable motor
|
Connected cable motor for 393 BE1 - 473 FA6 - 473 FA7 ( MUHAIMIN & CIVACON EMPLOYEE )
|
|
2026-05-10
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
CCR-&-443-CT1
|
Cleaning all PC unit operator and replace s/v gun no 14 of air issue air leakage, check function gun 4 for water not function
|
Cleaning PC of operator from dirty of dust use hand blower and vacuum cleaner. Replace S/V for air at gun no 14 issue leakage found existing S/V membrane not available test function result ok no leakage air. Pulling cable at gun no4 for water because found voltage drop below 220 VAC ( JAJAT & EDI & ADI & TRUBA SUSILO )
|
|
2026-05-10
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-CC1
|
Pulling cable RTD of 473 FA5-473 FA3-473 FA6
|
Pulling cable RTD for 473 FA3- 473 FA5 and 473 FA6 check indication at CCR result good ( YOGA & DADANG & TRUBA NANANG )
|
|
2026-05-10
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-CX1
|
Pulling cable indication ( 120 m ) issue pressure low indication and activation I/O
|
Pulling cable result indication activation I/O result pressure normal indication ( RIZKY & CIVA IRMIS & CIVACON EMPLOYEE )
|
|
2026-05-10
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
453-PF1
|
Mechanical reposition slide gate make normal indication. Cleaning ventury cooler
|
Reposition slide gate and cleaning ventury cooler ( FAHRI & EVE SUPRIYADI & CIVACON EMPLOYEE )
|
|
2026-05-09
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER5
|
Replace ampere meter - prepare replace battery of ER5 and connection cable
|
Replace ampere meter and battery at ER5 test function result good ( AGUS & FIRMAN & AIMAN )
|
|
2026-05-09
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-VA2
|
continue fabrication and test gate - ML
|
Fabrication of 423 VA2 and install at site test function gate - ML result ok ( RIZKY & CIVACON EMPLOYEE )
|
|
2026-05-09
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-CC1
|
Prepare pulling cable and re-installation cable RTD
|
Replace cable at 473 FA3 and reinstall sensor RTD at motor result indication normal ( YOGA & DADANG & TRUBA NANANG )
|
|
2026-05-09
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-HC1-&-443-FN1-&-473-FA6
|
Issue motor trip - connected sensor motor
|
Test run 473 HC result ok. Connected sensor motor 443 FN1-473 FA6 test run no load 443 FN1 measure vibration and noise LS 7 FS result vibration below 4 mm/s and noise below 2 gE ( HARYANTO & MHAIMIN & CIVACON EMPLOYEE )
|
|
2026-05-09
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-CC1-&-463-KL1-&-L63-RM1
|
Calibration temperature RTD
|
Do calibration temperature RTD area Cooler-Kiln-Coal Mill ( EDI & ADI & TRUBA SUSILO )
|
|
2026-05-09
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3-&-ER4-&-ER5
|
Black out support process
|
Do support black out process at ER3-ER4-ER5 ( JAJAT & AGUS & EDI & RIZAL & ADI & MUHAIMIN & ANDRI & DADANG & FIRMAN & AIMAN )
|
|
2026-05-08
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
RM-CC-CM
|
Calibration temperature RTD area RM-Cooler-CM
|
Do calibration RTD area RM for 363 FN1-363 FN2; area Cooler: 473 FA1-473 FA2-473 FA-473 FA5-473 FA6-473 FA7-473 FA8 ( EDI & ADI & EVE AJI & UNJ ASRIEL )
|
|
2026-05-07
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1-&-L63-RM1
|
Install motor and connect cable- alignment motor
|
Install service motor, alignment motor and connect cable motor ( AGUS & MUHAIMIN & EDI & CIVACON EMPLOYEE 7 PEOPLE & EVE SONY & TRUBA SUSILO & TRUBA NANANG )
|
|
2026-05-07
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WEST-AND-EAST-BLENDING
|
Replace terminal unit at panel I/O
|
Do replace TU 17 units at east blending and 5 units at west blending. Clean up area panel I/O use hand blower from dirty of dust ( JAJAT & PENY & ADI & EVE SONIY & FIRMAN & CIVA HERMAN )
|
|
2026-05-06
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Complete data calibration pressure transmitter OH Nr1
|
Do complete data check sheet calibration pressure transmitter OH Nr1 and continue scan file send to Mr. Jajat ( JAJAT & ADI )
|
|
2026-05-06
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-FN7-&-MAIN-GATE-ACCESS-CONTROL
|
Rrecheck connection cable power motor and add silicone for outside panel cable motor & Inspection electrical and welding tools
|
Recheck connection cable power at 473 FN7 and clean up area motor add silicone at panel cable motor. Inspection electrical and welding tools of PT Jantan Setia Sakti and PT Bintang Eka Sakti note 1 welding machine rejected because ground cable not connected. Tagging equipment with green color ( EDI & TRUBA SUSILO & TRUBA NANANG )
|
|
2026-05-04
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Calibration pressure transmitter area RM-CM-PH-CC for zero and span
|
Calibration pressure transmitter area cooler for zero and span ( ADI & EVE SUPRIYADI & EVE ZAHRA )
|
|
2026-05-04
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
MAIN-GATE-ACCES-CONTROL-&-WORK-SHOP
|
Inspection electrical and welding tools
|
Inspection electrical tools of Mechanic 1-Pincuran Mas-Plant Building tagging equipment with green color ( EDI & TRUBA SUSILO & TRUBA NANANG )
|
|
2026-05-03
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Calibration pressure transmitter for zero and span area Cooler
|
Calibration pressure transmitter for zero and span area Cooler-CM for 7 units note replace 2 transmitter because output mA not stable and output pressure not stable also replace resistance 200 ohm found bad condition ( ADI & EVE SUPRIYADI )
|
|
2026-05-03
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3-&-ER4
|
Support black out process. Measure MV-clean up VCB-VCS-DS. Regreasing VCB-VCS-DS
|
Support black out process at ER3 and ER4. Clean up trafo-VCB-VCS and DS from dirty of dust use hand blower and vacuum machine. Measure MV at trafo ( JAJAT & AGUS & EDI & RIZAL & ADI & MUHAIMIN & ANDRI & DADANG & TRUBA SUSILO & TRUBA NANANG )
|
|
2026-05-01
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Calibration pressure transmitter area PH-RM-CC-CM
|
Calibration pressure transmitter for zero and span area cooler and pre heater Note: replace 1 pressure transmitter with spare unit because leakage pressure indication and output mA too big ( ADI & EVE SUPRIYADI & EVE ZAHRA )
|
|
2026-05-01
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
MAIN-GATE-ACCES-CONTROL
|
Inspection electrical and welding tools for contractor
|
Inspection electrical and welding tools of PT MBL - PT Truba Jaga Cita - PT Indoporlen Tagging equipment with green color ( JAJAT & ADI )
|
|
2026-04-29
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Calibration pressure transmitter area Cooler - Pre heater - Coal mill for zero and span process
|
Calibration pressure transmitter area cooler-pre heater- coal mill total 14 units for zero and span ( ADI & EVE AJI & EVE SUPRIYADI & EVE ZAHRA & UNJ ASRIEL )
|
|
2026-04-29
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
MAIN-GATE-ACCES-CONTROL
|
Inspection electrical and welding tools
|
Inspection electrical and welding tools of PT Quadro tagging equipment with green color ( EDI & TRUBA SUSILO & TRUBA NANANG )
|
|
2026-04-28
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
MAIN-GATE-ACCES-CONTROL
|
Inspection electrical and welding tools
|
Inspection electrical and welding tools of PT Quadro-PT MBL- PT BMC note repare cable connection vacuum pump because existing joint cable to single cable. Tagging equipment with green color ( EDI & ADI & TRUBA SUSILO & TRUBA NANANG )
|
|
2026-04-27
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
MAIN-GATE-ACCES-CONTROL
|
Inspection electrical and welding tools
|
Inspection electrical and welding tools of PT MBL- PT RMP note 1 cutting machine rejected because breaker not install and ground cable is not connected- PT Jantan Setia Sakti note 1 grinding machine rejected because start-stop is not function. All equipment tagging green color ( EDI & ADI & TRUBA SUSILO & TRUBA NANANG )
|
|
2026-04-26
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
MAIN-GATE-ACCES-CONTROL--&-473-CC1
|
Inspection electrical and welding tools
|
Do inspection electrical and welding tools PT MBL-ADZALAMA-RMP_INDOPORLEN tagging green color note 2 cutting machine RMP rejected because ground cable are not connected, 1 extention cable MBL rejected because not full fill safety requirement SBI ( ADI 7 TRUBA SUSILO & TRUBA NANANG
|
|
2026-04-24
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
TENT-OH
|
Install lighting lamp
|
Do install 1 lighting lamp test function lighting lamp result normal ( RIZAL & ANDRI )
|
|
2026-04-24
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1
|
Issue O2 Abnormal. Replace O2 sensor
|
Replace O2 sensor test function sensor O2 with calibration zero and span result normal ( RIZAL & ANDRI )
|
|
2026-04-24
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-WP5-M1
|
Issue high noise replace bearing
|
Dismantle motor from site bring to work shop. Do replace bearing motor and installation motor at site ( AGUS & MUHAIMIN & DADANG )
|
|
2026-04-24
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
MAIN-GATE-AND-WORK-SHOP
|
Inspection electrical and welding tools
|
Do inspection electrical and welding tools of PT Jantan Setia Sakti tagging equipment green color. Inspection electrical and welding tools of Electrical Nr1 tagging equipment green color note repare 1 extention cable because ground cable is not connected ( ADI & TRUBA SUSILO & TRUBA NANANG )
|
|
2026-04-23
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-WP5-M1
|
Issue high noise up 2 gE
|
Discouple motor test run no load result high noise up 2 gE note need replace bearing motor ( JAJAT & AGUS & MUHAIMIN )
|
|
2026-04-23
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
TENT-OH
|
Install lighting lamp
|
Do Install lighting lamp tend OH test function result lighting lamp on ( AGUS & MUHAIMIN & RIZAL & ANDRI & DADANG & EVE AJI )
|
|
2026-04-23
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
SUPRA-&-TRUBA-JAGA-CITA
|
Inspection electrical and welding tools
|
Inspection electrical tools of PT Supra and tagging equipment with green color. Inspection welding tools of PT Truba Jaga Cita for 21 units tagging green color. Inspection electrical and welding tools of Electrical 1 tagging green color ( EDI & ADI & TRUBA SUSILO 7 TRUBA NANANG )
|
|
2026-04-22
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Completly data TPM ER3
|
Do complete data TPM ER3 safe at computer and print out ( JAJAT & RIZAL )
|
|
2026-04-22
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1-&-473-CC1
|
Repare-Replace lighting lamp
|
Fabrication and install new lighting lamp area 443 PH1 & 473 CC1 test function lighting lamp result good ( AGUS & MUHAIMIN & DADANG )
|
|
2026-04-22
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
AFR-WORK-SHOP-&-TPE
|
Inspection electrical and welding tools
|
Inspection electrical and welding tools of AFR work shop tagging green color. Inspection electrical tools of Total Prime Engineering note repare ground cable at extention cable because cable is not connected tagging equipment green color ( ADI & TRUBA SUSILO & TRUBA NANANG )
|
|
2026-04-21
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1-&-L63-RM1
|
Repare-Replace Lamp
|
Fabrication and install new lighting lamp area PH and CM test function lighting lamp result good ( AGUS & MUHAIMIN & DADANG )
|
|
2026-04-21
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
FLOW-METER-DIESEL
|
Support Calibration Flow meter diesel
|
Do support calibration for flow meter diesel result normal ( RIZAL & ANDRI & AIMAN )
|
|
2026-04-21
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
INSPECTION-ELECTRICAL-AND-WELDING-TOOLS
|
Mechanic 2 & Truba Jaga Cita & CBM
|
Inspection electrical and welding tools of mechanic II. Tagging green color note: repare connection cable at extention cable and welding cable. 1 portable lamp and 1 welding machine are not full fill safety requirement of plant. Inspection welding tool of PT Truba Jaga Cita tagging green color. Inspection electrical and welding tools of CBM note repare portable lamp ground cable connection and cover of lamp tagging green color ( EDI & ADI & TRUBA SUSILO & TRUBA NANAG )
|
|
2026-04-20
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
PYROMETER
|
Issue often retract
|
Replace filter result monitoring still not good performance camera still stuck ( RIZAL & EVE AJI & ANDRI )
|
|
2026-04-20
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
MAIN-GATE-ACCES-CONTROL-&-NECHANIC-2
|
Inspection electrical and welding tools
|
Check inspection tools of MEGA VOLT PERKASA, tagging with green color. Mechanic work shop Nr2 inspection electrical tools and welding tools tagging green color, note repare female connector of welding machine and cable welding minus and cable welding plus (continue) ( EDI & ADI & TRUBA ANIS & TRUBA AZIZ )
|
|
2026-04-20
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe-probe-filter sample line-sample line-diaphragm pump-filter balston from dirty of dust use instrument air supply. Check function of humidity sensor and filter humidity result function humidity sensor normal and filter humidity good condition ( RIZAL & EVE AJI & ANDRI )
|
|
2026-04-20
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-473-CC1
|
PMR Service Crit Motor & LSR KL & Cooler
|
Clean up area motor and filter motor from dirty of dust use instrument air supply. Measure vibration-noise-temperature of FS and LS also add grease motor of FS and LS for 25 times-30 times. Write KW-Voltage-Ampere-Temperature of motor at ER5 & ER4. Add grease for 333 BC1 issue high vibration up 4 mm/s and high noise up 2 gE ( MUHAIMIN & DADANG )
|
|
2026-04-20
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR Service Critical Motor & LSR RM&CM1
|
Clean up area motor and filter motor from dirty of dust use instrument air supply. Also clean up filter 363 FA2 M1 from dirty of dust use instrument air supply. Measure vibration-noise-temperature of FS and LS also add grease motor of FS and LS for 15 times-25 times-30 times. Write KW-Voltage-Ampere-Temperature of motor at ER3 & ER4 ( EDI & ADI )
|
|
2026-04-17
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WF-LIMESTONE-&-W83-WF1
|
Activation power point front & Pulling cable power +Tagging Labeling
|
Do activation power point near WF limestone. Pulling cable power and continue tagging labelling of W83 WF1 ( AGUS & MUHAIMIN & DADANG )
|
|
2026-04-17
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Clean up flange probe-sample line-filter sample line-diaphragm pump-filter balston from dirty of dust coal use instrument air supply. Check function of humidity sensor and filter humidity result function humidity sensor normal and filter good condition ( RIZAL & ANDRI )
|
|
2026-04-17
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
493-AC1
|
Repare slink position
|
Go to site found there is no slink available at site. Install slink spare together with nut test function slink result normal ( EDI & ADI )
|
|
2026-04-17
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER5
|
Ware house ER5 cleaning area inside room
|
Clean up area ware house of ER5 use vacuum cleaner and equipment cleaning tools ( JAJAT & AIMAN )
|
|
2026-04-17
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3
|
GEMBA TPM ER3
|
Do clean up area inside ER3 at bottom side use equipment cleaning tools. also clean stair beside ER3. Move ex MCS 100E to ER3 top floor ( JAJAT & AGUS & EDI & RIZAL & ADI & ANDRI & MUHAIMIN & DADANG )
|
|
2026-04-16
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Activation power point front of WF Limestone
|
Prepare power point ( RIZAL & EVE AJI & ANDRI )
|
|
2026-04-17
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Continue fabrication and prepare welding point out position L1C RE1
|
Prepare welding point ( AGUS & MUHAIMIN )
|
|
2026-04-16
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
PMR service CEMS
|
Do clean up purge air unit motor and filter purge air unit-flange with tube of dust hunter-swivel window T/R + R unit-alignment dust hunter-transducer A+B flowsic 100+CEMS room-CEMS gas room-filter cabinet MCS 100E from dirty of dust use instrument air supply ( RIZAL & EVE AJI & ANDRI )
|
|
2026-04-16
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP-PPUP
|
Inspection electrical and welding tools
|
Do inspection electrical and welding tools of PPUP work shop. Tagging equipment with green color ( EDI & DADANG )
|
|
2026-04-15
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-RE1
|
Fabrication + prepare welding point outside
|
Fabrication panel of welding outside L1C RE1, install at location ( AGUS & MUHAIMIN & DADANG )
|
|
2026-04-15
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Report PMR and WBI
|
Complete data check sheet for PMR analyzer L63 2K1-L63 2K2-L63 @K3-483 2K1-463 2K1-443 2K1-423 2K1-PMR CCTV-Temperature IR TAD-T scanner-Camera Burner-PMR critical motor 363 RM1-443 Ph1-L63 RM1-473 CC1-463 KL1, WBI Elec & Inst Top Blending-CT-PH-KL, WBI Elec & Inst Feed Bin-RM-CT-Dust Transport-BF, WBI Elect & Inst CM-Truck Lift-BC Transport-Reclaimer Coal for month of April 2026 ( ADI )
|
|
2026-04-15
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-CT1-&-WINCI-IDO
|
Check SV abnormal no 4 & 14 & issue failure
|
Replace S/V no 4 & 14 test function S/V normal. Check at location of motor result bad condition. Note replace motor with spare unit ( RIZAL & ANDRI )
|
|
2026-04-14
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-2K1
|
Issue low flow indication
|
Filter Sika Saturated, replace part (Monitor ) Oke ( FIRMAN & RIZAL & DADANG )
|
|
2026-04-14
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-CT1
|
Issue Kiln Down from Temp High
|
Power Bank 3 trip, check Solenoid VK (No 16) short, Replace Part test from DO Jump (Normal) , Mitigasi 1 fuse - 1 solenoid (JAJAT & RIZAL )
|
|
2026-04-14
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-MD1
|
Support Motor recondition 363 MD1
|
Support take and mobilization and document recondition motor 2400 KW to REMS ( AGUS & ANDRI & AIMAN )
|
|
2026-04-14
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe-filter sample line-sample line-diaphragm pump-filter balston from dirty of dust use instrument air supply. Check function humidity sensor and filter humidity result function humidity sensor normal and filter good condition ( RIZAL & DADANG )
|
|
2026-04-14
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
W83-WF1-
|
Fabrication cable power and LCS
|
Pulling cable Control to IO -LCS (6P x 1,5 mmx 4), Pulling cable control Power, fabrication and install Control Panel, Prepare connecting Control Side and IO side , fabrication and install Ladder cable and LCS panel ( JAJAT & AGUS & EDI & ADI & MUHAIMIN & DADANG )
|
|
2026-04-13
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Repare Breake Motor ( Dismalting, fabrication, Setting )
|
Dismalting nut broken, Replace part broken, setting gap,commisioning (Normal) ( EDI & MUHAIMIN & ANDRI & DADANG )
|
|
2026-04-13
5 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1,L63-RM1,473-CC1
|
PMR service critical motor LSR RM-CM & PMR Service Crit Motor & LSR KL & Cooler
|
Cleaning Motor , cek Vibrasi/Temp Motor Fill in Greate tube 363-FN1 /FN2. Cleaning Motor , cek Vibrasi/Temp Motor ( AGUS & RIZAL & EVE AJI )
|
|
2026-04-10
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER6
|
Fabrication cable ladder and cover tunnel ER6
|
Do continue fabrication cable ladder of ER6 and cover tunnel. Install cable ladder and cover tunnel at ER6 ( MUHAIMIN & ANDRI & DADANG )
|
|
2026-04-10
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
453-PW2-&-4D3-SC4
|
Issue temperature Motor alarm & fabrication cover motor also install at site
|
Check at location there is no voltage 220 VAC, make jumper resistor for no 13-14, Note replace relay K-7 contact temperature for 13-14 to make function normal. Painting cover motor with yellow color continue install for cover motor 4D3 SC4 at location ( JAJAT & RIZAL & EDI & ADI & AIMAN )
|
|
2026-04-09
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
CKD-MOTOR
|
Painting Area CKD Motor
|
Do painting area motor at CKD with yellow color ( JAJAT & AIMAN )
|
|
2026-04-09
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Clean up flange probe-sample line-filter sample-diaphragm pump-filter balston from dirty of dust process use instrument air supply. Check function of humidity sensor and filter humidity result function humidity sensor normal and filter humidity good condition ( RIZAL & EVE AJI )
|
|
2026-04-09
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP-&-443-FN1
|
Continue Wiring control W83-WF1 & install panel power point
|
Do wiring control panel W83 WF1 and make hole for exhaust fan panel. Install panel of power point at 443 FN1 ( AGUS & MUHAIMIN )
|
|
2026-04-09
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Report PMR and WBI 30 Maret- 9 April 2026 (Re-Check)
|
Do complete data check sheet WBI grounding-arrester also make folder for WBI Electrical and Instrumentation Check I/O Sump pump Blending-Cooler-Coal Mill-Kiln ( JAJAT & ADI )
|
|
2026-04-08
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Report PMR and WBI 30 March - 8 April 2026
|
Do conplete data check sheet PMR analyzer-PMR hoist crane-PMR IR TAD-T scanner-CCTV-Camera burner-PMR critical motor Note make check sheet folder for WBI Elec & Inst & Check I/O & S. Pump Blending-Cooler-CM-Kiln also print out data check sheet ( JAJAT & ADI )
|
|
2026-04-06
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Prepare Wiring control FABA
|
Do wiring control WF of FABA ( AGUS & MUHAIMIN )
|
|
2026-04-07
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-BL1
|
Issue LS vibration 11 mm/s continue replace bearing and install motor
|
Replace bearing motor with use heater bearing. Install motor at site. Test function motor , measure vibration and noise motor result vibration below 4 mm/s and noise below 2 gE ( AGUS & MUHAIMIN & ANDRI & DADANG & JAJAT & RIZAL )
|
|
2026-04-07
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe-probe-filter sample line-sample line-diaphragm pump-filter balston from dirty of dust process use instrument air supply. Check function humidity sensor and filter humidity result function humidity normal and filer humidity good condition ( RIZAL )
|
|
2026-04-07
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
TRUBA-JAGA-CITA;
|
Inspection electrical and welding tools
|
Do inspection electrical and welding tools of PT Truba Jaga Cita tagging with green color. Note 3 extention cable are rejected because not full fill requirement safety of plant total equipment electrical 18 units and welding 5 units ( EDI & ADI )
|
|
2026-04-06
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR Service Crit Motor & LSR KL & Cooler
|
Clean up area motor and filter motor. Measure vibration-noise-temperature of FS and LS motor. Add grease for 20 times AND 25 times for FS and LS. Write KW-Ampere-Voltage at ER3 put at form check sheet ( MUHAIMIN & DADANG & EVE AJI )
|
|
2026-04-06
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-473-CC1
|
PMR service critical motor LSR RM-CM
|
Clean up area motor and filter motor. Measure vibration-noise-temperature FS and LS motor. Write KW-Voltage-Ampere at ER4 & ER5 put at form check sheet. Add grease 25 times and 30 times for FS and LS ( AGUS & ANDRI )
|
|
2026-04-06
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
PT-PINCURAN-MAS
|
Inspection Tools Pincuran Mas
|
Check electrical tool of PT Pincuran Mas tagging with green color. Note repare connection extention cable and portable lamp ( EDI & ADI )
|
|
2026-04-03
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WF-FABA
|
Support upgrade WF FABA
|
Relocation 2 panel I/O station 21 & 31 from south side to north side of 333 WF5 also move power lighting lamp to panel I/O west side of 333 WF5. Pulling cable for power VS and power control. Prepare control and test partial like function speed and LC ( JAJAT & AGUS & EDI & RIZAL & ADI & MUHAIMIN & ANDRI & AIMAN )
|
|
2026-04-02
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Clean flange probe-sample line-filter sample line-diaphragm pump-filter balston from dirty of coal . Check function humidity sensor and filter humidity result function humidity sensor normal and filter good condition ( RIZAL & EVE CINDA & ANDRI )
|
|
2026-04-02
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER6
|
Cleaning ER6 and MCC panel
|
DO clean up ER room and MCC panel also filter panel form dirty of dust use equipment cleaning tools. Also do vacuum room use vacuum cleaner also mop room ( AIMAN )
|
|
2026-04-02
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Continue Prepare Upgrade fabrication Control WF FABA & Report Bearing Support recondition motor
|
Prepare upgrade control WF FABA Do make report upgrade recondition motor( AGUS & MUHAIMIN )
|
|
2026-04-02
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
CIVIL-BUILDING-WORKSHOP
|
Check Tool Civil Building
|
Inspection electrical tools of Civil Building. Do repare connection portable lamp 2 each test run nomai, repare 1 each extention cable test run normal Note total equipment 25 tools tagging with green color ( EDI & ADI )
|
|
2026-04-01
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
CKD
|
Fabrication cover motor for area CKD - Continue Painting Yellow
|
Do repainting 7 cover yellow color motor at CKD area ( ANDRI )
|
|
2026-04-01
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Continue Prepare Upgrade fabrication Control WF FABA
|
Do fabrication panel for upgrade WF of FABA ( AGUS & MUHAIMIN )
|
|
2026-04-01
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-BC4
|
Issue sump pump abnormal condition
|
Replace sump pump motor with spare unit, test function result sump pump still working abnormal suspected many coal inside water ( EDI & ADI )
|
|
2026-04-01
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-BC4
|
Issue sump pump abnormal condition
|
Replace sump pump motor with spare unit, test function result sump pump still working abnormal suspected many coal inside water ( EDI & ADI )
|
|
2026-04-01
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER4
|
Clean up ER and MCC panel
|
Clean up area Electric Room 4 bottom and top also MCC panel and filter panel from dirty of dust use equipment cleaning tools and vacuum cleaner. Continue mop floor electric room top and bottom (AIMAN )
|
|
2026-04-01
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Complete form recondition motor by SBI and vendor and bearing support
|
Do complete data form of recondition motor from SBI and vendor and write bearing support of motor ( MUHAIMIN )
|
|
2026-04-01
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1-&-L3C-RE1
|
Clean Up Panel Control L1C-TR1, Radio Link, L3C-RE1
|
Do clean up panel control L1C TR1- Radio Link and L3C RE1 from dirty of dust coal use instrument air supply also clean up safety device-lighting lamp-LCS motor-panel welding from dirty of coal dust ( JAJAT & EDI & ADI )
|
|
2026-04-01
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Clean up flange probe-sample line tube-filter sample line-diaphragm pump-filter balston from dirty of coal use instrument air supply. Check function of humidity sensor and check filter humidity result function humidity sensor normal and filter humidity good condition ( RIZAL & ANDRI )
|
|
2026-03-31
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-MD1
|
Issue Temp Winding T6 high > 128 Deg
|
Install blower, Cleaning Filter 363 FA2 (Monitor temperature T6 = 114 deg) ( MUHAIMIN & ANDRI )
|
|
2026-03-31
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Prepare and fabrication control FABA ( info control at Mr.Yunus )
|
Take control at Mr.Yunus bring to workshop. Prepare control FABA at workshop ( AGUS & MUHAIMIN )
|
|
2026-03-31
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe-probe-filter sample-sample line-diaphragm pump-filter balston from dirty of dust. Check function humidity sensor and filter humidity result function humidity normal and filter good condition ( RIZAL & ANDRI )
|
|
2026-03-31
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
413-3B1-&-3B2-&-473-CC1-&-463-KL1
|
WBI Elec & Ins & Check I/O & S Pump Blending, Cooler Area Kiln
|
Do WBI Elec & Ins & Check I/O & S Pump Bl,C Area Kiln. Do test function sump at IDO tank result function normal-L1C BC4 result can not start from LCS because manual function do clean up motor sump pump at workshop found much dirty of coal test function motor sump pump result normal take screning motor sump pump install at motor continue install location test function normal function-L1C BC1 result functon normal. Clean I/O panel area cooler and blending west and east-kiln from dirty of dust use equipment cleaning tools ( EDI & ADI )
|
|
2026-03-30
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WF-FABA
|
Observation power for weigh feeder
|
Power VSD 333 WF5 take from W83 RF3 and for WP3 RF3 take from distribution power ( JAJAT & AGUS & MUHAIMIN )
|
|
2026-03-30
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1
|
T Scanner Abnormal
|
Check at local found stick limit switch broken, replace stick result monitor T scanner normal ( RIZAL & ANDRI )
|
|
2026-03-30
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-FXB-M1
|
Issue Stop Local
|
Check LCS result normal, check I/o module result abnormal, change address signal S test start result function motor normal ( JAJAT & MUHAIMIN & ADI )
|
|
2026-03-30
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
CKD-MOTOR
|
Fabrication cover motor for area CKD
|
Go to location measure motor at CKD for make cover motor. Do fabrication cover motor area CKD at workshop. Install 4 cover motor at site of CKD ( ANDRI & WIKAN )
|
|
2026-03-30
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
PMR service CEMS
|
Clean up purge air motor and filter motor-swivel windows T/R, R unit also flange with tube of Dust Hunter also alignment Dust Hunter-transducer A & B of Flowsic-CEMS room-filter cabinet MCS 100 E-CEMS gas room from dirty of dust use instrument air supply. Replace H2 bottle for FIDOR continue calibration zero and span result normal ( RIZAL & EVE CINDA )
|
|
2026-03-30
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-473-CC1
|
PMR Service Crit Motor & LSR KL & Cooler
|
Clean up area motor and filter motor from dirty of dust use instrument air supply. Measure vibration-noise-temperature FS and LS motor also grease motor for 20 times - 25 times for FS and LS motor. Write ampere-KW-voltage-temperature motor at ER4 & ER5 continue write at check sheet ( AGUS & MUHAIMIN )
|
|
2026-03-30
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR service critical motor LSR RM-CM
|
Clean up area motor, filter motor from dirty of dust use instrument air supply. Measure vibration-noise-temperature of FS and LS motor. Add grease motor for 15 times and 20 times for FS and LS motor, Write ampere-KW-temperature-voltage motor at ER3 and ER4 continue write at check sheet note Carbon Brush no8 at 363 MD1 -1 need to replace with spare unit ( EDI & ADI )
|
|
2026-03-27
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER5-&-423-2K1
|
Clean up ER5 and Cleaning Area Cems ( Report ALL ER period 26 Febuary and 27 March 2026)
|
Clean up ER5 top and bottom made report Feb-March 2026 also do clean up 423 2K1 room analyzer ( AIMAN )
|
|
2026-03-27
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
493-3B1
|
Cleaning and Greasing Motor Area Clinker Silo
|
Cleaning Motor 493-AC1, AC2 ,AC3 also add grease motor ( ANDRI & DADANG )
|
|
2026-03-27
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-EL1
|
Issue door of elevator 5th abnormal
|
Cleaning All Door elevator test function elevator result normal note AC control elevator failure and push button inside elevator bad condition ( AGUS & MUHAIMIN )
|
|
2026-03-27
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
HRG
|
Y43-1G1 Increase Setpoint to 75 %
|
Set HRG to 75% do monitor result normal function ( JAJAT )
|
|
2026-03-27
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
FEED-BIN
|
Observation relocation station area WF ( project upgrade WF FABA)
|
Do observation relocation station of area WF, check cable needed approximately cable needed enough if station move to 333 WF1. Also check cable at warehouse for 4 x 25 mm result cable are not available ( JAJAT & EDI & ADI )
|
|
2026-03-26
6 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
HRG
|
Y43-1G1 ( HRG Purifier (ELGA 2) , Issue Abnormal Level
|
Cleaning Sensor Level, set to overflow do monitor setting 75% ( ADI & MUHAIMIN & ANDRI )
|
|
2026-03-26
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Prepare panel power point
|
Do prepare panel power point at work shop for 2 panel including wiring inside panel ( AGUS & DADANG )
|
|
2026-03-26
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-FA1
|
Issue grease outside tank
|
Check at location found tank grease bad condition make grease motor outside tank, replace tank of grease pump result grease motor function normal ( EDI & DADANG )
|
|
2026-03-26
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-2K1&-L63-2K2-&-L63-2K3-&-483-2K1-&-463-2K1-&-443-2K1
|
PMR service analyzer
|
Do clean up flange probe-sample line-filter sample line-diaphragm pump-filter balston-check function humidity sensor and filter humidity from dirty of coal result function humidity sensor normal and filter good condition note replace filter sample line for L63 2K2 with spare unit. Clean up flange probe-probe-filter sample line-sample line tube-diaphragm pump-filter balston from dirty of dust also check function of humidity sensor and filter humidity result function sensor humidity normal and filter humidity normal ( AGUS & MUHAIMIN & ANDRI )
|
|
2026-03-26
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-463-KL1-&-L63-RM1
|
WBI Switchgear, Cap & Trafo RM, KL & CM1
|
Do WBI WBI Switchgear, Capacitor & Trafo RM, KL & CM1, write result at form ( EDI & DADANG )
|
|
2026-03-26
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Complete data check sheet for WBI Elec & Ins & Check I/O GCT, EP,PH&KL (Report 24-3-26) & PMR CCTV, IR TAD & Kiln Scanner NAR1 (Report 23-3-26)
|
Do complete data check sheet for WBI Elec & Ins & Check I/O GCT, EP,PH&KL and PMR CCTV, IR TAD & Kiln Scanner NAR1 for date 23/3/26 and 24/3/26 at form also make report of SOT of march month ( ADI & JAJAT )
|
|
2026-03-17
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Prepare fabrication support portable power point
|
Do fabrication support of panel power point at workshop ( ADI & ANDRI & DADANG )
|
|
2026-03-16
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-L63-RM1-&-463-KL1-&-473-CC1
|
PMR Service Critical Motor & LSR RM&CM1
|
Do clean up area motor and filter motor. Measure vibration & noise motor of FS and LS. Add grease 25 times-30 times- 15 times for FS and LS ( RIZAL & DADANG )
|
|
2026-03-16
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Report PMR /WBI periode 9- 13 March 2026
|
Do complete data check sheet PMR analyzer L63 2K1-:63 2K2-L63 2K3-483 2K1-463 2K1-443 2K1-423 2K1, PMR IR TAD-CCTV-T Scanner-Pyrometer, Critical motor 363 MD1-363 FN1-363 FN2-423 FN1-443 FN1-L63 MD1-L63 FN1-473 FN7-463 MD1-WBI Top blending-CT-PH-Kiln WBI Bottom Blending-Kiln-Cooler-Clinker Silo WBI CM-Truck Lift-Tripper-Reclaimer Coal and print out data check sheet 9 to 12 copies ( ADI )
|
|
2026-03-13
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
MULTICYCLONE-RAW-MILL
|
Panel welding multicyclone raw mill tapping power
|
Do make hole of power cable panel welding continue connected at panel welding, test output result ok ( AGUS & DADANG )
|
|
2026-03-13
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-MD1
|
Continue Power point at 363-MD1 ( Tapping Power )
|
Do connect cable power point of 363 MD1 at panel welding bottom cyclone raw mill test on measure output result normal ( EDI & ADI )
|
|
2026-03-13
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-FA2-&-363--MD1
|
clean up CB room and check all CB of long carbon brush and clean up 363 FA2 filter motor
|
Clean up area motor 363 MD1 and carbon brush room from dirty of dust also clean 363 FA2 filter motor from dirty of dust use instrument air supply. Check long carbon brush found no 8 is to short replace carbon brush no 8 with spare unit ( EDI & ADI )
|
|
2026-03-13
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
HRG-&-T-SCANNER-&-463-2K1
|
Y43-1G1 Prepare Running + Prepare Install-Cleaning ELGA unit (Continue)- Issue T scanner abnormal - Cooling system failure
|
Replace fuse-install filter and UV lamp. Do replace-modification LS, result T scanner result view T scanner at operator normal. Replace RTD, tidy up cable result cooling system normal at analyzer 463 2K1 ( RIZAL & ANDRI )
|
|
2026-03-12
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Continue Prepare Upgrade Control
|
Do finishing wiring panel of upgrade control also put name of indication at front of panel ( AGUS & MUHAIMIN )
|
|
2026-03-12
6 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-MD1
|
Continue Power point at 363-MD1 ( Pulling cable and fabrication cable route )
|
Install pipe 2 inch for cable route from h-beam raw mill. Puling cable from welding cyclone raw mill to location power point at 363 MD1 also connected cable ( EDI & ADI & DADANG )
|
|
2026-03-12
7 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
473-FA9
|
Issue value draft abnormal
|
Replace pressure transmitter and setting parameter 130 mmH2O result indication draft back to normal at CCR operator. Fabrication support of pressure transmitter. Note Beck actuator function normal but at blade mechanical not response (RIZAL & EVE CINDA & ANDRI )
|
|
2026-03-11
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Continue Prepare Upgrade Control 443 2K1
|
Continue wiring cable inside panel of upgrade panel 443 2K1 ( AGUS & MUHAIMIN )
|
|
2026-03-10
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-3B1
|
Issue signal proximity often bad. Replace proximity of gate bin
|
Do replace proximity for gate because existing signal error at CCR operator result after function normal ( RIZAL & ANDRI )
|
|
2026-03-11
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-2K1
|
Continue upgrade control
|
Continue wiring cable inside panel and install panel upgrade inside analyzer 443 2K1 room ( AGUS & MUHAIMIN )
|
|
2026-03-11
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-2K1
|
Cleaning and painting room of analyzer
|
Do clean up analyzer 443 2K1, and repainting floor with green color and door with yellow color ( JAJAT & AIMAN )
|
|
2026-03-11
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Do clean up filter sample-flange probe-sample line-diaphragm pump-balston filter from dirty of coal use instrument air supply. Check function humidity sensor and filter humidity result function humidity sensor normal and filter humidity good condition ( RIZAL & ANDRI )
|
|
2026-03-10
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-FN1-&-363-FN2
|
Cleaning Filter Issue Dirty - Control Alarm temperature
|
Clean Filter unit both of 363 FN1 and 363 FN2 result alarm temperature disappear ( EDI & DADANG )
|
|
2026-03-10
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Continue Prepare Upgrade Control 443 2K1
|
Continue do wiring panel of upgrade analyzer 443 2K1 ( AGUS & MUHAIMIN )
|
|
2026-03-10
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
PMR service CEMS
|
Clean up purge air unit motor and filter motor- flange with tube Dust Hunter-swivel windows of T/R also R-alignment Dust Hunter- transducer A & transducer B of Flowsic- CEMS room also filter cabinet MCS 100 E-CEMS gas room bottle form dirty of dust use instrument air supply ( RIZAL & ANDRI )
|
|
2026-03-10
7 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
483-FA2-&-483-BL7
|
Issue high noise up 2 gE
|
Add grease motor around 20 times for FS & LS also add grease motor 483 BL7 for LS 10 times and FS 8 times ( EDI & ADI )
|
|
2026-03-10
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-GQ1
|
Issue lighting lamp off at south side
|
Check at location, found lighting lamp off and cable power for lighting lamp is not connected to cable power input. Do reconnected cable power result lighting lamp normal operation ( EDI & ADI & DADANG )
|
|
2026-03-09
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Continue Prepare Upgrade Control 443 2K1
|
Do revision drawing of upgrade control analyzer 443 2K1 and print out file drawing of upgrade control analyzer 443 2K1 ( AGUS & MUHAIMIN )
|
|
2026-03-09
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe-probe-sample line-diaphragm pump-filter balston from dirty of dust process. Check function of humidity sensor and filter humidity result function sensor normal and filter humidity good condition. Note replace filter sika at analyzer 463 2K1 and do calibration zero gas and span gas result calibration ok( RIZAL & EVE CINDA & ANDRI )
|
|
2026-03-09
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-&-473-CC1
|
PMR Service Critical Motor & LSR
|
Clean up area motor-filter motor from dirty of dust use instrument air supply. Measure vibration-noise-temperature for FS and LS motor. Add grease from 25 times-30 times for FS and LS. Write RPM-Voltage-Ampere-Temperature motor and bearing at electric room 4 and electric room 5 ( MUHAIMIN & DADANG )
|
|
2026-03-09
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-L63-RM1
|
PMR Service Critical Motor & LSR
|
Clean up area motor-filter motor from dirty of dust use instrument air supply. Measure vibration-noise-temperature for FS and LS motor. Add grease from 15 times-20 times-30 times for FS and LS. Write RPM-Voltage-Ampere-Temperature motor and bearing at electric room 3 and electric room 4 Note there alarm at 363 FN1 because temperature 112 degree C at MICOM ( EDI & ADI )
|
|
2026-03-06
7 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
WORK-SHOP
|
Continue Prepare Upgrade Control
|
Wiring Control Local ( AGUS & MUHAIMIN )
|
|
2026-03-06
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-BF1
|
Observation replace diaphragm
|
Replace diaphragm L63 BF1 ( RIZAL & ANDRI & DADANG )
|
|
2026-03-06
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-DB1&-473-FA4
|
Repare cable Connection safety device and repare cable Connection Thermocouple
|
Repare and Cleaning result ok ( RIZAL & ANDRI & DADANG )
|
|
2026-03-06
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3-&-ER4-&-ER5-&-ER6
|
PMR Load MCC and UPS
|
Do PMR load MCC and UPS at ER3-ER4-ER5-ER6 ( EDI & ADI )
|
|
2026-03-05
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
433-BE1-&-443-2K1
|
Issue D5 Warning and Failure and observation due contamination of water
|
Check at location, replace contact kit BD 5 of 433 BE1. Do replace pump of dryer gas at 443 2K1, monitor reading O2 and CO2 for probe 1 and probe 2 result reading gas of O2 and CO normal as process ( RIZAL & EVE CINDA & ANDRI )
|
|
2026-03-05
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-SC5
|
Observation issue Abnormal (Signal S dan Speed Monitor)
|
Check 393 SC5 at location, do clean up probe of motion test simulation result normal indication signal S and speed monitor ok at CCR operator ( EDI & DADANG )
|
|
2026-03-05
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
CIVIL-BUILDING-WORKSHOP
|
Repare lighting lamp off
|
Do wiring cable power of lighting lamp 6 units, test result lighting lamp normal ( JAJAT & ADI )
|
|
2026-03-04
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1
|
Support Heating up + Feeding
|
Do support heating up process and feeding kiln ( JAJAT & ADUS & RIZAL & EDI & ADI & MUHAIMIN & ANDRI & DADANG )
|
|
2026-03-04
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Prepare Audit API 2026
|
Numbering File-File at file box and name file at panel ( JAJAT & ADI )
|
|
2026-03-04
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-2K1
|
Line Purging broken and issue reading O2 high
|
Repare-Welding join piping, create valve drain pressure pump leaked, repared, normal ( RIZAL & ANDRI )
|
|
2026-03-04
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3
|
Prepare Panel IO station N31 (Dismantling Panel ER 3 bottom )
|
Dismantling Panel Ex-Sick and LR ( EDI & EVE CINDA & DADANG )
|
|
2026-03-04
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-FN1
|
Prepare power point
|
Tapping Power From welding point transport 423-F1 ( EDI & DADANG )
|
|
2026-03-02
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L93-3B1
|
Issue level abnormal
|
Check at location, do clean up load cell result indication level normal ( RIZAL & MUHAIMIN & EVE CINDA )
|
|
2026-03-02
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
BURNER-FLOOR
|
Prepare and calibration of flow diesel
|
Do calibration flow diesel with drop test result good ( RIZAL & MUHAIMIN & EVE CINTA )
|
|
2026-03-02
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-SC8
|
Prepare and install indication ampere
|
Do prepare CT at workshop 50/5A, and wiring cable for CT at workshop and install CT 50/5A at ER3 for 383 SC8 and wiring cable output at panel I/O at ER3 result indication ampere normal ( JAJAT % EDI & ADI & DADANG )
|
|
2026-02-27
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
433-BE1-&-393-BE1
|
Fabrication and install cover motor
|
Do fabrication cover of motor 393 BE1 -433 BE1 and install at location ( EDI & MUHAIMIN & DADANG )
|
|
2026-02-27
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1
|
Issue shell cooling failure
|
Check at location found cable power is not long enough, also measure resistance cable found bad result. Replace connector cable power motor with spare result motor shell cooling fan function normal ( EDI & MUHAIMIN & DADANG )
|
|
2026-02-27
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Prepare document for AUDIT API
|
Complete data file for calibration RTD year 2025, PMR Service Analyzer-PMR IR TAD-CCTV-Tscanner-Camera Burner-PMR Critical Motor of 363 RM1-443 PH1-L63 RM1-473 FN7-463 KL1-PMR Clean Electric Room of 3-4-5-6 for year 2025 and 2026 and print out data PMR clean up ER3-ER4-ER5-ER6 ( JAJAT & ADI )
|
|
2026-02-27
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER6
|
TPM Gemba 5R
|
Do install sign safety for assembly point 2 each outside ER6-Evacuation Route 4 each inside ER6-Equipment cleaning tools 2 each inside ER6. Accompany assessment at dash board TPM ER6 at work shop ( RIZAL & ADI & AIMAN )
|
|
2026-02-27
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
313-3B1
|
Continue level silo east blending error
|
Do reposition of level sensor and rewiring cable sensor also data, result level same with operator CCR expected ( RIZAL & ANDRI )
|
|
2026-02-26
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-3S1
|
Issue level blending silo error
|
Do dismantle level sensor and clean up sensor reinstall level sensor result indication available at CCR ( RIZAL & MUHAIMIN & EVE CINTA & ANDRI )
|
|
2026-02-26
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP-MECHANIC-1
|
Prepare TPM ER6 report
|
Do prepare report of TPM ER6, print out sign Catatan GEMBA 5R and VOM get sign from Mr.Jajat, Mr. Heri Setiawan and Mr. Safrin and put at dashboard TPM at work shop ( JAJAT & RIZAL & ADI )
|
|
2026-02-26
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-MD1-AND-MOTOR-20-KW
|
Issue noise at L63 MD1
|
Add grease motor at L63 MD1 measure noise result below2 gE. Do add grease motor of 20 KW measure vibration and noise result normal vibration below 4 mm/s and noise below 2 gE ( AGUS )
|
|
2026-02-26
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
PMR service CEMS
|
Clean up purge air unit motor and filter motor, swivel window of Dust Hunter do alignment Dust Hunter, transducer A and transducer B of Flowsick, CEMS room gas bottle area, CEMS room. filter cabinet MCS 100 E from dirty of dust process use instrument air supply ( RIZAL & MUHAIMIN & ANDRI )
|
|
2026-02-26
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Clean up filter sample-sample line-diaphragm pump-filter balston from dirty of coal. Check function humidity sensor and filter humidity result function humidity normal and filter sensor good condition ( EDI & EVE CINTA & DADANG )
|
|
2026-02-25
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-FN1
|
Temperature T6 , issue High indication
|
Install Blower 2 side result temperature normal at CCR operator ( EDI & AGUS )
|
|
2026-02-26
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP-MECHANIC-1
|
Prepare TPM Assesment
|
Do prepare report TPM ( RIZAL )
|
|
2026-02-25
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3
|
Issue AC Robicon issue hot around 36 degree C
|
Monitor, team Karteksi repare piping Leaked, Add Gas Freon result AC function normal and temperature normal ( JAJAT & AGUS )
|
|
2026-02-26
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-SC3
|
Prepare installation indication of ampere
|
Install ampere unit, result view at operator CCR good ( AGUS & MUHAIMIN & DADANG )
|
|
2026-02-25
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-BE1-&-393-BE1
|
Add grease motor
|
Add Grease, result vibration below 4 mm/s. Do monitor vibration motor ( EDI )
|
|
2026-02-25
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-FA-E
|
Issue motor ground replace position motor fan of stand by
|
Do activation motor spare result function motor normal ( JAJAT & AGUS & MUHAIMIN & DADANG )
|
|
2026-02-25
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-2K1
|
PMR service analyzer
|
Clean filter sample-sample line-diaphragm pump-filter balston. Check function humidity sensor and filter humidity result function humidity sensor normal and filter good condition ( RIZAL & EVE CINTA & ANDRI )
|
|
2026-02-24
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-CT1-T2
|
Indication temperature low
|
Check temperature with portable sensor result indication around 96 degree C to 102 degree C compare at CCR indication temperature 45 degree C. Dismantle sensor T/C found very dirty with hard dust and do clean up sensor continue install result indication temperature same between local at CCR ( JAJAT & RIZAL & ANDRI & MUHAIMIN )
|
|
2026-02-25
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
CAMERA-BURNER
|
Issue view is not available at CCR operator
|
Dismantling camera, service all lens and room of camera kiln. Install camera kiln at location result view of camera available at operator CCR ( RIZAL & ANDRI )
|
|
2026-02-25
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
T-SCANNER
|
Dotted line view at CCR operator
|
Do replace limit switch, result view normal monitoring view at CCR ( EDI & DADANG )
|
|
2026-02-24
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
3B1-W.PV-
|
Issue level indication error
|
Do service connection cable sensor and clean up sensor result function level sensor normal ( RIZAL & MUHAIMIN & ANDRI & DADANG )
|
|
2026-02-24
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Ex 393-FA6 Service motor replace bearing
|
Bearing housing broken when try to open use tool ( MUHAIMIN & ADI & EDI )
|
|
2026-02-24
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1
|
, Service analyser Unit
|
Do Service sample point analyzer ( EDI & ADI & MUHAUMIN )
|
|
2026-02-24
7 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
LA3-VA1
|
Proportional Valve Error
|
Replace Proportional Valve , Setting Actual Position, Setting Actual vs Set point result setting and actual position ok ( RIZAL & ANDRI & DADANG )
|
|
2026-02-24
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-SR1
|
Issue indication temperature low at CCR
|
Repare connection (Monitor) ( RIZAL & ANDRI )
|
|
2026-02-23
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-
|
Support heating up process
|
Support process heating up of kiln ( RIZAL & ANDRI & JAJAT & EVE CINTA )
|
|
2026-02-23
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-FA6
|
Replace motor
|
Bring motor spare from ware house electric at ER5 to 8th floor. Dismantle existing motor and install motor spare do test run result function motor normal. Measure ampere 6.3 A and measure vibration-noise-temperature A-H-S for FS and LS result normal indication ( JAJAT & AGUS & MUHAIMIN & EDI & RIZAL & ADI & ANDRI & DADANG )
|
|
2026-02-23
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
413-BF2
|
Replace PLC Siemens issue failure of PLC
|
Do replace PLC SIEMEN of 413 BF2, test run function normal ( RIZAL & ANDRI & EVE CINTA )
|
|
2026-02-23
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-MD1
|
Clean up carbon brush and measure actual condition of carbon brush
|
Do clean up carbon brush room and slip ring use instrument air supply. Continue clen up slip ring use contact cleaner. Check and measure actual long result still good ( EDI & ADI & DADANG )
|
|
2026-02-20
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-SGD-393-SGE-393-SGF
|
Dismantling solenoid valve
|
Dismantling solenoid valve for slide 3 unit bring to work shop ( JAJAT & EDI & ADI )
|
|
2026-02-20
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-FN1
|
Tidy up cable power of blower fan
|
Tidy up cable power for blower of 443 FN1 from panel welding 363 RM1 to panel at 443 WP test on result ok note found breaker 1 failure replace with spare but power blower connected to output power ( EDI & ADI & AIMAN )
|
|
2026-02-20
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1
|
Continue relocation or repare shell kiln fan (Test Motor)
|
Do function motor shell kiln fan result of motor function normal ( AGUS & MUHAIMIN & CIVACON )
|
|
2026-02-20
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
453-AE1-&-483-AE1
|
Check function aeration
|
Do aeration at 453 AE1 and 483 AE1 result function normal ( RIZAL & ANDRI & DADANG )
|
|
2026-02-20
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-FA3
|
Dismantling ex cable power
|
Do dismantling cable ex 473 FA3 with cutting cable and put at safe location ( EDI & ADI & AIMAN (
|
|
2026-02-19
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-HD1
|
Relocation power stop contact
|
Relocation power stop of 473 HD1 ( AGUS & RIZAL & ANDRI & EVE FADHILAH )
|
|
2026-02-19
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1
|
Continue relocation or repare shell kiln fan
|
Do repare cover motor shell fan of kiln. Fabrication cover at workshop and install at location ( AGUS & MUHAIMIN & EVE FADHILAH & DADANG )
|
|
2026-02-19
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-BC1-TO-L1C-BC7
|
check actual KW motor-voltage-ampere motor
|
Check indication KW-ampere-voltage motor at ER6 for L1C BC1-L1C BC2-L1C BC3-L1C BC4-L1C BC5-L1C BC6 and L1C BC7 at ER6. Data send to Mr. Jajat ( EDI & ADI )
|
|
2026-02-19
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
4W3-1NF
|
Replace ELCB di 4W3-1NE (Cooler Area)-- 2 EA broken
|
Do replace ELCB at 4W3 1NE 2 each for 25 A also replace receptacle 2 units ( EDI & ADI )
|
|
2026-02-19
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP-MECHANIC-1
|
Prepare Data AUDIT API
|
Do prepare data AUDIT API, print out form complete data calibration and adjustment feeder for 11/8/2025 ( JAJAT & ADI )
|
|
2026-02-17
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-FA2
|
Test Run
|
Test run 483 FA2 with different speed check indication ampere-vibration result normal ( AGUS & MUHAIMIN & DADANG & JAJAT )
|
|
2026-02-17
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
413-BL2
|
Replace breaker of local isolation
|
Check at site found need to replace panel LCS with new one. Replace panel LCS with spare for 63 A, continue wiring cable power and for Start-Stop-Emergency ( EDI & ADI )
|
|
2026-02-17
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
493-AC2
|
Issue speed failure
|
Check at control miltronic indication lamp ON but 493 AC2 condition stop check at ER5 found breaker input OFF but indication ready jumper cable. Do start breaker input and LCS 493 AC2 existing off position. Try to start from CCR result running normal ( EDI & ADI & FIRMAN & RAFI )
|
|
2026-02-17
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
HEAT-EXCHANGER
|
Activation hoist crane
|
Do pulling and connected Power to Hoist Crane result done ( AGUS & MUHAIMIN & DADANG )
|
|
2026-02-17
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-CT1-&-463-2K1
|
Activation flow meter and replace RTD of IKGA
|
Re-wiring, Set Parameter Sensor, Commissioning Transport result normal. Soldering RTD sensor to Transducer result normal ( RIZAL & ANDRI )
|
|
2026-02-17
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1-473-CC1-413-3S1-413-3S2
|
Clean up panel I/O
|
Do clean up panel I/O area east - west blending -cooler-preheater also LCS from dirty of dust use hand blower ( JAJAT & EDI & ADI & AIMAN )
|
|
2026-02-13
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
CKD
|
Observation, cable needed of part electronic support project CKD
|
Maping cable needed of project CKD ( RIZAL & JAJAT & ADI & MUHAIMIN )
|
|
2026-02-13
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
CKD
|
Observation cable way and prepare part needed rail cable project CKD
|
Do observation cable way and preparing spare part of rail needed project CKD ( EDI & ANDRI & DADANG & AIMAN )
|
|
2026-02-12
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
TOP-BLENDING-&-443-PH1
|
Clean up also check up LCS and motor
|
Do clean up area LCS and motor. Also clean up push button and emergency stop make function normal from dirty of dust ( AIMAN & EDI & ADI )
|
|
2026-02-12
7 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
443-CT1
|
Support replace flow sensor
|
Dismantling old sensor and disconnected sensor ( RIZAL & JAJAT )
|
|
2026-02-12
7 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
4D3-SC6
|
Activation indication ampere
|
Indication ready panel operator view ( JAJAT & AGUS & RIZAL & MUHAIMIN )
|
|
2026-02-12
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
EAST-BLEANDING-&-393-PP1
|
Clean up and check LCS - motor area blower blending east - 393 PP1
|
Clean up and check LCS-motor area blower and 483 PP1 from dirty of dust> Check function AUTO Grease 393 PP1 result function normal grease tank full condition ( EDI & ADI )
|
|
2026-02-12
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-RF2
|
Connected cable power
|
Do connected cable power of 483 RF2 ( EDI & ADI )
|
|
2026-02-11
8 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
483-RF1-&-483-BV1
|
Connect motor and BV
|
Do connect motor also BV test run result stuck at BV. Issue mechanic RF need to connected ( RIZAL & EDI )
|
|
2026-02-11
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-SC6
|
Install indication ampere unit
|
Install unit ampere and create DCS input ( MUHAIMIN & DADANG )
|
|
2026-02-11
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER6
|
Clean up inside and outside from dirty of dust
|
Put bamboo stick 2 each at ER6 continue clean up inside also outside room from dirty of dust use equipment cleaning tools ( ADI & AIMAN )
|
|
2026-02-11
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-FN1
|
Replace vibration sensor at free and fix side
|
Replace vibration sensor for fix and free side motor result ok ( RIZAL & MUHAIMIN & EVE FADHILAH & ANDRI & DADANG )
|
|
2026-02-11
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3
|
install cover concrete at AC ROBICON
|
Install cover concrete of AC ROBICON at ER3 use fork lift ( ADI & AIMAN )
|
|
2026-02-10
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-FN1
|
Support CBM for reposition FAN needed
|
Prepare damage nut fan. Do prepare panel at workshop, install 3 male socket power, put 2 MC and 1 small MC inside panel continue wiring cable ( JAJAT & AGUS & ADI )
|
|
2026-02-10
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
493-AC2
|
Pull Cord damage
|
Replace slink pull cord, test ok ( RIZAL& MUHAIMIN & ANDRI & DADANG )
|
|
2026-02-10
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-LD3
|
Dismantling damper and set gate at 100%
|
Dismantling damper of 483 LD3, Weld Gate to 100 % Open ( RIZAL & MUHAIMIN & ANDRI & DADANG )
|
|
2026-02-09
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3
|
Dismanlting scraft Piping (Robicon AC ER-3)
|
Throw scrap iron to warehouse scrap ( AIMAN & CIAVCON )
|
|
2026-02-09
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-FA2
|
Scaling VSD of motor (Speed -Amp)
|
Setting Parameter, Scaling speed and Ampere Indication Done ( AGUS & EVE FADHILAH )
|
|
2026-02-09
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-FN1
|
Install Main Power and All Sensor
|
Install Power cable and Sensor ( RIZAL & MUHAIMIN & ANDRI & DADANG )
|
|
2026-02-08
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-FN1
|
Install motor spare
|
Take motor spare of 363 FN1 at FM1 warehouse near EVE room bring to location continue dismantle roof of motor and bring existing motor to ER3 and install motor spare at location. Bring existing motor to FM1 ware house near EVE room ( JAJAT & AGUS & AIMAN & CIVACON )
|
|
2026-02-08
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-FA2
|
Activation VSD of motor
|
Turn off incoming power for wiring power input of VSD. Continue wiring cable power input at ER5 and setting parameter at control VSD found error HBB ( Hard Base Block ) do jumper for H1-H2-HC error HBB disappear. Start On motor local mode found frequency motor only 35 HZ resetting parameter maximal frequency from 60 to 100 result can be change from monitor control and result speed motor add at local ( RIZAL & ADI & MUHAIMIN & DADANG )
|
|
2026-02-06
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
BURNER-FLOOR
|
Tidy Up cable area burner
|
Tidy up cable area Burner ( AIMAN )
|
|
2026-02-06
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-FA2
|
Disconnect power damper and indication
|
Turn off power motor, dismantle ring at motor, also cable power damper and cable indication. Set output damper at 100% position ( EDI & MUHAIMIN & ADI )
|
|
2026-02-06
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-BU1
|
Install-Wiring Flow meter 483-BU1 + Commissioning
|
Re-wiring and Installation Kabel sensor, Test oil Circulation , Sensor Normal ( RIZAL & ANDRI & EVE SONY )
|
|
2026-02-06
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-FN1
|
Support job at 363 FN1 ( disconnect cable sensor and Motor)
|
Disconnected All Sensor and Power Motor, Support Mech Sky folding ( AGUS & EDI & ADI & MUHAIMIN & EVE FADHILAH & DADANG )
|
|
2026-02-05
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-FN1
|
Support job at 363 FN1
|
Do create permit, check area and motor ( JAJAT & MUHAIMIN & AIMAN & DADANG & EVE SONY )
|
|
2026-02-05
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-2K1
|
Install sensor temperature Honey Well
|
Install sensor temperature of Honey Well at 443 2K1 ( RIZAL & EVE FADHILAH & ANDRI )
|
|
2026-02-05
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-RF1
|
install seal motor
|
Do install seal motor and do heat of motor. Measure resistance motor for R-S-T to ground result value up to 2 mega ohm. Install motor at site ( AGUS & MUHAIMIN & EVE SONY & DADANG )
|
|
2026-02-05
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1-&-TOP-BLENDING
|
Clean Up and Check LCS + Motor
|
Clean up LCS and motor area top blending and PH, also panel I/O area top blending silo, Check function emergency stop before clean up first result function normal ( EDI & ADI & JAJAT & AIMAN )
|
|
2026-02-04
8 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
FM-OF-DIESEL
|
Make flange at workshop plant
|
Dismantle FM of diesel bring to workshop. Make flange for FM diesel at workshop plant, install flange at FM diesel also connected at location ( RIZAL & 2 CIVACON )
|
|
2026-02-04
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-RF1
|
Install seal motor
|
Install seal motor, measure use megger unit found resistance around 0.8 mega ohm - 0.9 mega ohm. Use heater lamp again at motor put behind workshop ( AGUS & MUHAIMIN & EVE SONY % DADANG )
|
|
2026-02-04
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
433-FM2
|
Repare or fabrication way of load cell
|
Check at location found cable load cell out position not neat. Dismantle cable load cell, install conduit cable tighten use cable tie and protect hole use silicone ( RIZAL & ED I& ADI & EVE FADHILAH )
|
|
2026-02-03
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
IDO-TANK-&-L1C-BC1-&-L1C-BC4
|
Check function sump pump
|
Do check function sump pump result IDO function normal, L1C BC1 function normal, L1C BC4 function normal note to be clean up area sump pump because many coal scattered around sump pump ( EDI & ADI & EVE FADHILAH )
|
|
2026-02-03
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-Z4A-T3
|
Replace Thermocouple
|
Dismantle existing thermocouple, install new housing thermocouple and thermocouple continue connect cable sensor ( RIZAL & EDI & ADI & ANDRI & EVE FADHILAH )
|
|
2026-02-03
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-FX1
|
Relocation LCS
|
Relocation LCS of 463 fX1 ( AGUS & MUHAIMIN & EVE SONY & DADANG )
|
|
2026-02-03
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-FAC-M1
|
Clean up LCS and area motor (Area Burner )
|
Clean up area motor and LCS ( IMAN )
|
|
2026-02-03
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-SC3
|
Support and fabrication new control upgrade
|
Disconnected Motor 4D2-RF1, motion 393-SC3 and LCS ( MUHAIMIN & DADANG & EVE SONY )
|
|
2026-02-03
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-BF1
|
Repare control safety valve issue cable not right position
|
Do make good position of cable 423 BF1 tighten use cable tie. Repare control safety valve by disconnect cable power ( AGUS & MUHAIMIN & DADANG & EVE SONY )
|
|
2026-02-02
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
493-AC1
|
Replace or repare cable burn
|
Repare and activation power distribution ( EDI & ADI & EVE SONY & EVE FADHILAH )
|
|
2026-02-02
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-RF1
|
Issue seal reducer to motor leakage
|
Dismantle motor 483 RF1. Do replace seal and bearing motor continue install at location ( AGUS & MUHAIMIN & DADANG )
|
|
2026-02-02
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-BF1
|
Relocation pressure senso
|
Relocation cause Mech Activity ( RIZAL & ANDRI )
|
|
2026-02-02
8 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
393-SC3-M2
|
Disconnect motor
|
Do disconnect power cable motor at 393 SC3 M2 9 ( JAJAT & EDI )
|
|
2026-02-02
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
SOT of febuary 2026
|
Make report of SOT for 1st weeks of febuary for all members of Electric Nr1 ( JAJAT & ADI )
|
|
2026-02-02
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-HS1
|
Replace / repare -Pulling and install cable burn area 473-HS1
|
Check at location, found dryer air is not function anymore because dryer air already disconnected from tube of air. Eliminated cable power from dryer air. Cutting cable power near wall of dryer air. Do turn off MCB at hydrolic room insulation cable power use electrical insulation ( EDI & ADI & EVE SONY & EVE FADHILAH
|
|
2026-01-30
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER5
|
Continue activation and connected VSD 483 FA2 and create module DCS
|
Do wiring cable DO at module 5 channel 10, dismantle cable K-T-D-R at I/O panel ER4 ( JAJAT & RIZAL & MUHAIMIN & ANDRI & EVE SONI & EVE FADHILAH )
|
|
2026-01-30
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Make report data safety for TPM ER6 4 file
|
Make report for data safety TPM ER6: lighting lamp inside ER6 - door of west ER6 - tube water drain of AC ER6 - conduit pipe porous outside ER6 print out at put at dash board TPM ER6 at workshop electric 1 ( JAJAT & ADI )
|
|
2026-01-29
8 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
ER5-483-FA2
|
Continue activation and connected VSD 483 FA2
|
Install scun of cable power and motor. Pulling cable control (2x6Px0,75mm), Install module AI820- DI810 unit set ( AGUS & MUHAIMIN & ANDRI & DADANG )
|
|
2026-01-29
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
TPM Activity ER6
|
Do send file VOM to TPM coordinator get sign, print out data 5R and laminating at workshop. Take laminating at CCR to put at dashboard TPM ER6 at workshop ( RIZAL & ADI )
|
|
2026-01-29
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Scanning data or complete calibration 2025-2026
|
Complete data calibration for 2024 to 2025, continue scanning send to email Mr. Jajat ( JAJAT & ADI )
|
|
2026-01-28
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER6
|
Gemba TPM ER6
|
Clean up area inside electric room, take picture of safety, replace lighting lamp and repare tube of drain air condition of ER6 ( RIZAL & ADI & IMAN )
|
|
2026-01-27
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
453-PW1
|
Wrapping unit to protect from production activity
|
Do wrapping unit 453 PW1 protect from production activity ( IMAN )
|
|
2026-01-27
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1
|
Wiring and install support welding panel of cyclone 363 RM1
|
Do prepare tray cable at workshop , install at site and pulling cable to panel welding ( AGUS & MUHAIMIN & ANDRI & DADANG )
|
|
2026-01-27
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER5
|
Activation and connected VSD of 483 fA2
|
Observation cable, station and connection ( AGUS & MUHAIMIN & ANDRI & DADANG )
|
|
2026-01-27
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
SUMP-PUMP
|
Check function of sump pump all area
|
Check function of sump pump: IDO tank result ok but note pendulum sump pump outside hole make sump pump always on repare pendulum put inside hole of sump pump, L1C BC4 and L1C BC1 are sump pump normal note hole for sump pump of L1C BC4 many land will make sump pump always start note need to clean up hole of sump pump to make sump pump working properly ( EDI & ADI )
|
|
2026-01-26
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
MAIN-GATE-ACCES-CONTROL
|
Inpsection electrical and welding tools of PT Indoporlen
|
Do inspection electrical and welding tools tagging with red color. Note: 2 extention cable and 1 portable lamp are not safe because not full fell safety requirement of plant ( EDI & ADI )
|
|
2026-01-26
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-FA3-&-473-FA4
|
Fabrication cover motor
|
Fabrication cover motor at work shop and do painting cover with yellow color continue install at site for 473 FA3 and 473 FA4 ( MUHAIMIN & ANDRI & DADANG )
|
|
2026-01-26
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3
|
Activation CCTV ER3 - office way
|
Do activation CCTV of ER3 with IP 10.227.19.170 and 10.227.19.151 result view for CCTV ok ( AGUS, RIZAL )
|
|
2026-01-26
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
EAST-BLEANDING-&-WEST-BLENDING-&-CT-TRANSPORT
|
Clean up welding panel - I/O panel - area motor from dirty of dust
|
Clean up panel welding - panel I/O - panel LCS - area motor - bucket elevator- bag filter - rotary feeder - blower - air slide of east and west blending also CT transport from dirty of dust use instrument air supply and hand blower ( JAJAT & EDI & ADI )
|
|
2026-01-23
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-HS1
|
Issue cable burn area 473 HS1
|
Disconnected cable power , scheduling for repairing ( JAJAT )
|
|
2026-01-23
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
453-GA1-&-453-GA2
|
Disconnected cable 453-GA1/2
|
Disconnected cable 453 GA1 and 453 GA2 at local ( JAJAT & ADI )
|
|
2026-01-23
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3
|
Prepare set of CCTV for ER3 2 unit
|
Do prepare support for CCTV at ER3 at workshop. Continue install at CCTV at ER3 and do setting of CCTV ( AGUS )
|
|
2026-01-23
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
FEED-BIN
|
Extention module I/O at feed bin support upgrade weight feeder FABA
|
Do prepare module extention I/O for WF FABA. Continue install module at panel I/O like module 8 DI 810 - module 9 DI 810 - module10 AI 810 continued download extention module result ok ( RIZAL & ANDRI )
|
|
2026-01-23
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Prepare fabrication power point area L1C BC5
|
Do prepare panel power point of L1C BC and wiring cable, Prepare support of panel at workshop ( MUHAIMIN & DADANG & ADI )
|
|
2026-01-22
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1
|
Fabrication cable tray and connected FX Kiln (Shell Fan Kiln) and Install Point Port (Continue) - Connect port FX
|
Install Cable to distribution port and complete accecories unit to FX (spare 3 FX) ( MUHAIMIN & DADANG )
|
|
2026-01-22
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER2
|
Continue activation remote VCS at ER3
|
Connected cable Terminal control to VCS unit ( AGUS & ANDRI & RIZAL )
|
|
2026-01-22
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
453-PF1-483RF1-483-RF2-483-AG1-453-AG1
|
Wrapping part because production activity
|
Do wrapping equipment due production activity result part complete safe ( RIZAL & ANDRI )
|
|
2026-01-22
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-FN1-&-473-FAA
|
Repare handle LOTOTO ID Fan and handle LCS 473 FAA
|
Replace handle LOTOTO 443 FN1 with spare unit result ok note white lock 7019 still at available at existing lock. Replace handle 473 FAA result ok ( EDI & ADI )
|
|
2026-01-22
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-RF3
|
Disconnect motor rotary feeder
|
Do disconnect power motor for 483 RF3 ( RIZAL & ANDRI )
|
|
2026-01-22
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-BC1
|
Issue sump pump failure
|
Check at local position switch sump pump at manual.. Found power trip at panel input. Turn on power result sump pump working normal ( EDI & ADI )
|
|
2026-01-22
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-CC1-&-463-KL1
|
Clean Up and Check LCS and motor cooler and Kiln Bottom
|
Do clean up panel LCS and motor area 473 CC1 including panel welding area cooler from dirt of dust use equipment cleaning tool a and hand blower ( JAJAT & EDI & ADI & AIMAN )
|
|
2026-01-21
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1
|
Fabrication cable tray and connected FX Kiln (Shell Fan Kiln) + Install Point Port (Continue) - Connect port FX
|
Install fabrication bar electric and wiring cable support installation ( MUHAIMIN & DADANG )
|
|
2026-01-21
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3
|
Prepare-Rewiring LAN Install Converter-POE unit and office way
|
Install converter POE unit and office way at ER3 continue rewiring cable ( EDI & ADI )
|
|
2026-01-21
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3-&-ER4-&-ER5
|
Install SOP of MICOM P122 and P225
|
Laminating SOP of Micom P122 & P226 at workshop. Install SOP of MICOM P122 and P225 at ER3 - ER4 - ER5 ( EDI & ADI )
|
|
2026-01-19
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3-&-MAIN-GATE
|
Inspection electrical and welding tools of PT Civacon and PT RMP
|
Inspection electrical and welding tools of PT CIVACON at ER3. Repare extention cable because for ground cable connected failure for stop contact and welding machine because cable power is not safe at outside welding machine. Inspection electrical and welding tools of PT RMP at main gate. Tagging equipment with red color. Note there are some equipment electrical tools not safe because grounding cable failure ( EDI & ADI )
|
|
2026-01-20
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463KL1-&-BURNER-FLOOR
|
Clean Up dan Check LCS Area Burner + Kiln + Heat Exchanger
|
Do clean up and check up LCS area burner and kiln ( JAJAT & EDI & ADI & AIMAN)
|
|
2026-01-19
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1
|
Fabrication cable tray and connected FX Kiln (Sheal Fan Kiln)
|
Do fabrication cable tray at workshop and install at site continue connected cable sheal fan of kiln ( AGUS & RIZAL & MUHAIMIN & ANDRI & DADANG )
|
|
2026-01-15
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-RE1
|
Cleaning MCC and PLC
|
Cleaning MCC and PLC for L1C RE1 use hand blower from dirty of dust ( JAJAT & AIMAN & DADANG )
|
|
2026-01-15
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1-&-473-CC1
|
Inspection electrical and welding tools of PT TRUBA JAGA CITA
|
Do inspection electrical and welding tools of PT Tuba Jaga Cita. Equipment tagging with red color. Note some extention cable, welding machine-portable lamp are not full feel requirement safety from company ( EDI & ADI )
|
|
2026-01-15
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1
|
Activation I/O 2nd floor 443 PH1 ( project upgrade 443 2K1 & 463 2K1) and addressing
|
Do activation I/O panel 2nd floor of preheater for project upgrade 443 2K1 and 463 2K1 including addressing cable ( AGUS & RIZAL & MUHAIMIN & ANDRI )
|
|
2026-01-15
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-BF1
|
Activation I/O module, migitation solenoid failure
|
Install module solen0id valve, connected cable power for solenoid valve and connector tubing for solenoid valve. Also connected cable at I/O module Continue activation I/O module for migitation solenoid valve failure and install connector tubing at module solenoid valve ( AGUS & RIZAL & MUHAIMIN & ANDRI )
|
|
2026-01-14
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
HRG
|
HRG shutdown ( long time idle )
|
Follow form step by step Log stoppage procedure ( release pressure ,empty Water , Release Power, Stop Valve system , Off breaker control power ) ( JAJAT )
|
|
2026-01-14
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Continue fabrication welding panel area truck lift
|
Install pipe conduit for cable welding panel, continue connected to new welding panel and existing welding panel near hoist crane with action turn off power input existing welding panel ( RIZAL & ANDRI & DADANG & AGUS & JAJAT & ADI & MUHAIMIN & AIMAN )
|
|
2026-01-13
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Fabrication welding point area truck lift
|
Take cable no item 305122055 around 30 meter. Pulling cable power of welding panel at L1C BC1 room to top floor. Prepare pipe conduit around 5 meter and claim pipe at workshop bring to site ( EDI & RIZAL & ADI & ANDRI )
|
|
2026-01-13
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-CC1-AND-BURNER-FLOOR
|
Activation welding panel area burner and cooler
|
Activation welding panel at 493AC2, replace ELCB, install and setting timer of lamp ( AGUS & MUHAIMIN & DADANG )
|
|
2026-01-12
8 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1
|
463 KL1 T1 issue reading temperature at CCR low
|
Replace Thermocouple and repare housing. Result reading temperature back to normal ( RIZAL & ANDRI )
|
|
2026-01-12
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Do clean flange probe-probe-filter sample line-sample line tube-diaphragm pump-filter balston-dryer gas pump from dirty of dust use instrument air supply. Check function humidity sensor and filter humidity result function sensor humidity normal and filter humidity sensor good condition ( RIZAL & ANDRI )
|
|
2026-01-12
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-473-CC1
|
PMR Service Critical Motor & LSR CM & CC
|
Clean area motor and filter motor. Measure vibration-noise-temperature FS and LS motor. Add grease for FS and LS motor 30 times and 25 times ( MUHAIMIN & DADANG )
|
|
2026-01-12
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR service critical motor LSR RM-PH
|
Clean area motor and filter motor. Also clean up filter 363 FA2. Measure vibration-noise-temperature FS and LS motor. Add grease for FS and LS motor 15 times and 20 times. Replace AUTO Grease motor for 363 FN1 and 363 FN2 with spare unit. Refill AUTO Grease empty level at workshop until unit ready to use ( EDI & ADI )
|
|
2026-01-09
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-MD1
|
replace CB no 6-8-9
|
Do clean up carbon brush room area from dirty of dust with instrument air. Replace carbon brush no 6-8-9 with spare unit ( EDI & RIZAL & ADI )
|
|
2026-01-09
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Install camera WS electric
|
Do install camera CCTV at workshop also pulling cable power and LAN cable continue connect at camera result ok ( ANDRI & DADANG )
|
|
2026-01-09
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Complete data check sheet inspection electrical tools of PT Pincuran Mas
|
Do completing data check sheet inspection electrical tools of PT PINCURAN MAS at 6-1-26.. Scan file and send to Mr.Jaenudin Safety Officer PT Pincuran Mas ( ADI )
|
|
2026-01-09
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
493-AC2
|
Replace Box hagger + Accecories
|
Check condition of box LCS for 493 AC2-493 AC3-483 AC4 result condition normal also clean up pabelk LCS from dirty of dust ( EDI & ADI & MUHAIMIN )
|
|
2026-01-09
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L93-SC4
|
Issue speed failure
|
Check speed sensor at local result function sensor good note problem of mechanical ( RIZAL & ANDRI )
|
|
2026-01-09
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1
|
Replace spray pump
|
Do check function water spray at local found have problem when manual do service valve manual result function valve manual water spray normal ( AGUS & EVE FADHILAH & DADANG )
|
|
2026-01-08
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER5
|
Support take sample oil trafo
|
Do support supplier take sample oil trafo at electric room 5 ( JAJAT & AGUS )
|
|
2026-01-08
9 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
463-2K1
|
Issue O2 High and repare chain tention
|
Clean up sample line, and adjust chain of probe retract and insert. Turn off shock blower direct to main hole. Result reading O2 back to normal below 4% ( MUHAIMIN & AGUS & EVE SONY & ANDRI )
|
|
2026-01-08
9 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
363-RM1
|
Prepare part Cover Motor
|
Do prepare part of cover motor area 363 RM1 ( RIZAL & MUHAIMIN & DADANG )
|
|
2026-01-08
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-BC1
|
Install welding point and issue sump pump failure
|
Prepare support for panel welding and install at panel welding. Install panel welding at L1C BC1. Do turn off power input and found motor of sump pump hot. Swap cable connection power, test function sump pump result ok normal ( EDI & ADI & EVE FADHILAH & DADANG & JAJAT )
|
|
2026-01-07
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-CN
|
Prepare Welding Point RM Cyclone
|
Install welding panel at cyclone rawmill (MUHAIMIN & EVE FADHILAH & ANDRI & DADANG )
|
|
2026-01-07
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
L1C BC1-BC2-BC3 prepare welding panel
|
Prepare welding panel ex burner floor bring to workshop do clean up panel. Repainting welding panel use grey color. ( EDI & DADANG )
|
|
2026-01-07
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
PINCURAN-MAS-WORK-SHOP
|
Inspection electrical and welding tools
|
Do inspection electrical tools of PT PINCURAN MAS tools tagging with red color ( ADI )
|
|
2026-01-07
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-BC1
|
Lighting lamp off near welding panel
|
Replace lighting lamp test function result lighting lamp on ( EDI & DADANG )
|
|
2026-01-07
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-BF1
|
Issue JB 21 No 7 Abnormal
|
Check at site, clean up solenoid valve and tubing purging and reconnect tubing result function solenoid valve back to normal ( RIZAL & ANDRI )
|
|
2026-01-06
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Install selector AUTO-MAN for signal START-STOP activated vibrator from CCR
|
Do install selector for AUTO-MAN of signal START & STOP also activated vibrator from CCR ( JAJAT & EDI & RIZAL & ANDRI & DADANG & AGUS & MUHAIMIN & ADI & AIMAN & EVE FADHILAH & EVE SONY )
|
|
2026-01-06
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Prepare cable for sensor position minimal 2 pair around 15 m x 3
|
PM truck lift do prepare cable for sensor around 15 meter x 3 ( ADI & AIMAN & EVE SONY )
|
|
2026-01-06
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Pulling cable and connection sensor to terminal & commissioning ML indication
|
Pulling cable and do connection sensor to terminal. Do commissioning ML indication result ok ( JAJAT & RIZAL & EDI & ANDRI & DADANG )
|
|
2026-01-06
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Fabrication tray cable to sensor ML 3 point
|
Do fabrication cable tray and install at site ( RIZAL & EDI & ANDRI & DADANG & JAJAT )
|
|
2026-01-06
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER6
|
wiring I/O 24 VDC and signal
|
PM truck lift do pulling cable power 110 VAC for DI L1C BC1-L1C BC2-L1C BC3. Also add AO at I/O ER6 and cable power 110 VAC. Continue wiring DI at junction box and panel I/O ER6 ( AGUS & MUHAIMIN & ADI & EVE FADHILAH )
|
|
2026-01-05
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-FA2
|
Cooling Fan Failure
|
Service and clean up cooling fan and filter motor at 363 FA2 result function cooling fan back to normal ( EDI & DADANG )
|
|
2026-01-05
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
FEED-BIN
|
Observation upgrade control WF feed bin
|
Do observation for upgrade control WF feed bin ( AGUS & RIZAL & MUHAIMIN )
|
|
2026-01-05
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe-probe-filter sample line-sample line-diaphragm pump=filter balston-dryer gas pump from dirty of dust. Check function of humidity sensor and filter humidity result function humidity sensor normal and filter humidity good condition ( RIZAL & ANDRI & EVE FADHILAH )
|
|
2026-01-05
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-L63-RM1
|
PMR Service Critical Motor & LSR RM&CM1
|
Clean up area motor and filter motor. Measure vibration-noise-temperature of FS and LS. Add grease 30 times-25 times for FS and LS ( EDI & DADANG )
|
|
2026-01-05
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-&-473-CC1
|
PMR Service Crit Motor & LSR KL & Cooler
|
Clean up area motor and filter motor. Measure vibration-noise-temperature of FS and LS. Add grease 30 times-35 times for FS and LS ( MUHAIMIN & EVE SONY )
|
|
2026-01-02
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Make sign for 493 AC2 and 493 AC3
|
Make sign for LCS 493 AC2 and 493 AC3 print out and laminating continue install at local ( JAJAT & ADI & EVE SONY )
|
|
2026-01-02
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER6
|
Pulling cable control L1C BC1-BC2-BC3
|
Pulling cable control for L1C BC1-LiBC2-L1C BC3 ( MUHAIMIN & ANDRI & DADANG )
|
|
2026-01-02
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
433-BF2
|
Replace or upgrade module. Issue error at process
|
Connect cable at module PLC for power input and output also cable for solenoid valve. Test function bag filter result ok interval every solenoid 5 second ( JAJAT & ADI & MUHAIMIN & EVE SONY & ANDRI & DADANG )
|
|
2025-12-31
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-FN1
|
Observation blower at 443 FN1
|
Observation blower at 443 FN1 ( MUHAIMIN & ANDRI & DADANG )
|
|
2025-12-31
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR Service analyzer Preheater & IKGA N1 + completing part for upgrade 443 2K1 at SAP
|
Clean up flange of probe, probe, filter sample line, sample line, diaphragm pump, filter balston, dryer gas pump from dirty of dust, Check function of humidity sensor and filter humidity, result function humidity sensor normal and filter good condition. Do completing part for upgrade analyzer 443 2K1 at SAP ( RIZAL )
|
|
2025-12-31
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
EP--PH--GCT-PH-KL
|
WBI Elec & Ins & Check I/O GCT, EP,PH&KL
|
Do WBI electric and instrumentation check I/O GCT-EP-PH-KL. Clean up area, also measure vibration - noise - temperature of FS and LS. Write abnormal at file check sheet. Make notification for abnormal condition ( EDI )
|
|
2025-12-31
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
FEED-BIN--RAWMILL-CT--DUST-TRASNPORT---BAG-FILTER
|
WBI Electric & Ins & Check I/O Feed Bin-RM-CT-Dust Transport-Bag Filter
|
Do WBI electric and instrumentation check I/O feed bin, rawmill, CT, dust transport, bag filter. Clean up area, also measure vibration - noise - temperature of FS and LS. Write abnormal at file check sheet. Make notification for abnormal condition ( ADI )
|
|
2025-12-31
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
BURNER-FLOOR
|
Dismalting Welding Point Burner+ Clean Up + relocation power lubrication exchanger point
|
Dismantling welding point of burner floor and continue clean area welding from dirty of dust use instrument air supply. Relocation power lubrication exchanger point ( AGUS & MUHAIMIN & ANDRI & AIMAN )
|
|
2025-12-30
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1
|
Monitoring Heating Up
|
Do monitoring process heating up of KILN NR1 ( JAJAT & AGUS & RIZAL & EDI & ADI & ANDRI & MUHAIMIN & DADANG )
|
|
2025-12-30
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
BURNER-FLOOR
|
Activation panel welding of burner floor
|
Do connect cable power panel welding at burner floor test on result power panel welding available ( AGUS & ANDRI & MUHAIMIN & DADANG )
|
|
2025-12-30
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1
|
Relocation and replace end point hydraulic cooling fan and blower tyer
|
Relocation end point of hydraulic cooling fan and blower tyer ( AGUS & MUHAIMIN & DADANG & ANDRI )
|
|
2025-12-30
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-BF1
|
Install Auto Drain
|
Do install AUTO drain of bag filter ( RIZAL & EDI & ADI )
|
|
2025-12-30
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1
|
Activation panel welding 8th floor
|
Do connect cable power panel welding at 8th floor test on result power panel welding available ( RIZAL & EDI & ADI )
|
|
2025-12-30
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-BF1
|
observation all solenoid valve and installation of L63 BF1 and check relay
|
Replace puppet valve 4 each, replace cage 7 each, bag 6 each and pneumatic 1 each by mechanic team ( RIZAL & ANDRI )
|
|
2025-12-30
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER4
|
Prepare Test Drive (Pulling cable ) + Support Instalation
|
Pulling cable for test drive at ER4 also clean up panel drive motor note make hole at wall of ER4 for cable drive way and heater cable power 220 VAC ( JAJAT & EDI & RIZAL & ADI & MUHAIMIN & ANDRI & DADANG & EKO JUHAN & MARDIYANTO & FIRMAN )
|
|
2025-12-29
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1
|
Analyzer Failure (Issue failure of cable)
|
Do repare cable at 463 2K1 result ok analyzer reading normal from process ( EDI & RIZAL )
|
|
2025-12-29
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-2K1
|
Prepare instalation analyzer DownComer (New Instalation)
|
Do prepare installation analyzer 443 2K1 for new installation ( RIZAL & EDI )
|
|
2025-12-29
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-L63-RM1
|
PMR service critical motor LSR RM-CM
|
Clean up area motor and filter motor. Measure vibration-noise-temperature FS and LS motor also clean up filter 363 FA2 from dirty of dust use instrument air supply. Add grease motor 30 times and 25 times for FS and LS motor ( AGUS & DADANG )
|
|
2025-12-29
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-&-473-CC1
|
PMR service critical motor
|
Clean up area motor and filter motor from dirty of dust use instrument air supply. Measure vibration-noise-temperature FS and LS motor. Add grease motor 30 times and 35 times for FS and LS motor ( MUHAIMIN & EVE SONY )
|
|
2025-12-26
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-FA6
|
Issue high up 2gE for FS and LS
|
Add grease motor for FS and LS around 20 times. Measure noise motor FS: A 1.09 gE - V 1.85 gE - H 1.51 gE; LS: A 1.66 gE - H 1.43 gE - V 1.96 gE ( ADI & EVE SONY )
|
|
2025-12-26
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Repare thermowell ex 463 KL1 T1
|
Do repare thermowell at workshop ( ANDRI & DADANG )
|
|
2025-12-26
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Assembling panel welding area cyclone raw mill
|
Do assembling welding panel for cyclone raw mill ( MUHAIMIN )
|
|
2025-12-26
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
HRG-ROOM-
|
Clean up area and turn off AC
|
Clean up area HRG and turn off AC of HRG ( MUHAIMIN )
|
|
2025-12-26
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
TPM-423-2K1-&-ER3
|
Prepare garbage tank 2 color green and yellow of 423 2 K1 & prepare garbage tank 3 color: green - yellow-red of ER3
|
Take garbage tank for yellow and green color put at outside CEMS room and also take garbage tank for yellow-green-red color put at outside ER3 ( ADI & AIMAN )
|
|
2025-12-24
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-MD1
|
Install guarding fan
|
Install guarding fan at L63 MD1 for cooling fan ( EDI & ADI )
|
|
2025-12-24
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1
|
Issue high O2 reading
|
Clean up probe - filter sample line - motor blower from dirty of dust. Result CO 0.002 to 0.012%, NO 1244 PPM - O2 4.34 to 5.97 % ( EDI & ADI )
|
|
2025-12-24
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-T1
|
Issue reading temperature abnormal
|
Check at local found thermowell failure. Relace sensor T/C - hosing of T/C - thermowell result temperature indication normal ( RIZAL & MUHAIMIN & DADANG )
|
|
2025-12-24
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
TPM activity form
|
Do complete TPM activity form at computer, save at file inside computer ( JAJAT & RIZAL )
|
|
2025-12-24
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
AUTO-DRAIN-OF-CM
|
Install cover of solenoid AUTO drain at L63 2K1
|
Install cover from water and hot of sun at solenoid AUTO drain ( EDI & ADI )
|
|
2025-12-24
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-SR1&-363-FN2
|
Issue high vibration ( add greasing )
|
Add grease motor at 363 SR1 M1 around 20 times, measure vibration at LS: H 6.7 mm/s, A 3.7 mm/s, V 4.7 mm/s at base plate 7.8 mm/s. Also add grease motor at 333 BC1 for FS and LS measure vibration LS: H 1.9 mm/s, V 1.7 mm/s. Add grease motor at 363 FN2 LS around 20 times measure vibration LS: V 2.3 mm/s, H 1.3 mm/s, A 1.0 mm/s ( EDI & ADI )
|
|
2025-12-23
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
IDO-TANK
|
IDO pump can not loading diesel to tank
|
Refill tube for take out diesel from truck, result start pump diesel come out from tube after touch level high tube for loading diesel ( JAJAT & EDI & ADI & EVE SONY )
|
|
2025-12-23
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER6-&-ER5
|
Cleaning ER NAR 1
|
Clean up ER6 and ER5 top also bottom from dirty of dust, also filter MCC use vacuum cleaner and mop floor ( AIMAN )
|
|
2025-12-23
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Final Drawing 443-2K2 + Drawing Remote VCS RM
|
Drawing 443 2K1 and remote VCS of 363 RM save at computer ( AGUS )
|
|
2025-12-23
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TL1
|
Activation alarm Ready to Start - Failure
|
Install indication Ready - Start - Failure for L1C BC4 at L1C TL1. Pulling cable power for lamp indication ( MUHAIMIN & ANDRI & DADANG & EVE SONY )
|
|
2025-12-23
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-FN2
|
Issue high noise for LS motor
|
Measure noise motor at LS, add grease motor around 40 times measure noise result decrease below 2 gE ( EDI & ADI )
|
|
2025-12-23
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
Issue AUTO drain abnormal
|
Check auto drain solenoid valve, found not working. Replace solenoid valve auto drain for 2 air tank at CM test function result normal function. Make cover auto drain near analyzer L63 2K1 for protect from rain ( EDI & ADI )
|
|
2025-12-22
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
TSCANNER
|
Issue problem view at CCR
|
Stick limit switch untouched, make good position of stick can touched, result view T scanner back to normal ( MUHAIMIN & ANDRI )
|
|
2025-12-22
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
CO2-SYSTEM-TANK-
|
Observation safety valve CO ( issue energize )
|
Check at local for safety valve, release valve CO result normal. Note safety valve over pressure make energize ( RIZAL & ANDRI )
|
|
2025-12-22
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-BF1
|
Observation solenoid purging L63 BF1 issue high draff
|
Check at local found tube hose broke, replace tube of solenoid purging at L63 BF1 result drafft back to normal ( RIZAL & ANDRI & EVE SONI )
|
|
2025-12-22
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-&-L63-RM1
|
PMR Service Critical Motor & LSR Kiln & Cooler 1
|
Clean up area motor and filter motor from dirty of dust use instrument air supply. Measure vibration - noise - temperature for FS and LS. Add grease 30 times - 25 times for FS and LS motor ( AGUS & DADANG )
|
|
2025-12-22
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR service critical motor LSR RM-CM
|
Clean up area motor and filter motor also filter motor 363 FA2 from dirty of dust use instrument air supply. Measure vibration - noise - temperature for FS and LS. Add grease 20 times - 25 times for FS and LS motor ( ADI & MUHAIMIN )
|
|
2025-12-19
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
T-SCANNER
|
Issue problem view at CCR
|
Check stick limit switch zero not untouched, repare stick at limit switch zero result T scanner view normal at CCR ( RIZAL & ANDRI )
|
|
2025-12-19
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-2K1
|
Prepare Support Cable of 443-2K1
|
Do prepare support cable at 443 2K1. Measure part cable needed from analyzer ti I/o panel around 553 meter ( RIZAL & EDI & EVE SAFIR & ANDRI )
|
|
2025-12-19
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Scanning PMR dan WBI period July-December 2025
|
Do put back check sheet after scanning. Print out data check sheet 2 until 4 copies for some PMR and WBI ( JAJAT & ADI )
|
|
2025-12-18
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Observation recondition motor OH 2026
|
Do observation recondition motor for OH 2026 ( AGUS & MUHAIMIN )
|
|
2025-12-18
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
TSCANNER
|
Issue error
|
Replace stick for solenoid valve result ok ( RIZAL & ANDRI )
|
|
2025-12-18
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Fabrication or prepare level sensor L1C TL1
|
Do fabrication sensor level at workshop for L1C TL1 ( EDI & EVE SAFIR )
|
|
2025-12-18
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Scanning PMR dan WBI periode July-December 2025
|
Complete data check sheet PMR and WBI start month July to December 2025, continue scanning data check sheet send to Mr.Jajat ( JAJAT & ADI )
|
|
2025-12-17
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
SOLAR-TANK
|
Check function of sump pump
|
Check function sump pump, On breaker sump pump, result function normal. Note there is joint pipe failure advise repare joint pipe immeadiately ( EDI & ADI )
|
|
2025-12-17
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Observation recondition motor OH 2026
|
Observation data recondition motor of OH 2026 write data at computer as DATA MOTOR OH26 ( AGUS & MUHAIMIN )
|
|
2025-12-17
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-FA3
|
Issue Pressure zero
|
Replace pressure tube at 473 FA3 result indication pressure normal ( RIZAL & ANDRI & DADANG )
|
|
2025-12-17
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
433-FM2
|
Issue Error LC
|
Check at location found there is cable short to body panel, repare cable cover with isolation cable result indication normal ( RIZAL & ANDRI )
|
|
2025-12-17
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
fabrication sensor material level L1C TR1
|
Do fabrication sensor material level for L1C TR1 at workshop ( ANDRI & DADANG )
|
|
2025-12-17
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-CC1-&-483-BL7
|
GREASING-MOTOR->-200-KW
|
Add greasing motor for FS and LS around 10 times of motor ( EDI & ADI )
|
|
2025-12-17
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-FA6
|
Issue high vibration motor at FS and LS
|
Check found tank of AUTO grease low level, replace tank of AUTO grease motor with spare unit. Add grease motor at FS and LS around 15 times, measure vibration motor result 1.7 mm/s and 2.9 mm/s ( EDI & ADI )
|
|
2025-12-16
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-FN1
|
Issue AUTOBALANCER problem
|
Replace module and repare socket ( AGUS & MUHAIMIN )
|
|
2025-12-16
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3
|
Observation part needed piping AC robicon ER3 ( compare item number at WH )
|
Measure pipe 4 inchi needed at local around 32 meter. Check pipe 4 inchi at warehouse found but there are no elbow for 4 inchi and 2.5 inchi ( EDI & ADI )
|
|
2025-12-16
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR service critical motor LSR RM-CM
|
Clean up area motor and filter motor. Measure vibration - noise - temperature FS & LS motor. Add grease motor 35 times - 30 times for FS and LS motor. Refill AUTO grease motor ( AGUS & DADANG )
|
|
2025-12-16
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-&-473-CC1
|
PMR service critical motor LSR KL-CM
|
Clean up area motor and filter motor. Measure vibration - noise - temperature FS & LS motor. Add grease motor 25 times - 30 times for FS and LS motor ( MUHAIMIN & EVE SAFIR )
|
|
2025-12-16
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
PMR service CEMS
|
Clean up purge air motor and filter purge air motor, clean up flange with tube - swivel window T/R & R - alignment dust hunter. clean up transducer A & B for flowsic 100, CEMS room - filter cabinet MCS 100E - CEMS gas room from dirty of dust use instrument air supply ( RIZAL & ROMY & ANDRI )
|
|
2025-12-12
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Observation recondition motor for over haul 2026
|
Do observation for recondition motor OH 2026 ( AGUS & MUHAIMIN )
|
|
2025-12-12
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Clean up flange probe - sample line tube -filter sample line - diaphragm pump - dryer gas pump - filter balston from dirty of coal. Check function of humidity sensor and filter humidity result function sensor humidity normal and filter humidity good condition ( RIZAL & ROMY )
|
|
2025-12-12
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
HRG
|
Replace and configuration CCTV at outside of HRG
|
Check communication CCTV at outside HRG result bad communication. Replace CCTV with spare camera test communication result normal view at outside of HRG ( AGUS & JAJAT & EDI & ADI & DADANG )
|
|
2025-12-11
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Setting MICOM with actual temperature
|
Do setting MICOM with standard actual temperature use calibrator of temperature result indication different 7 degree celcius. Install MICOM at ER3 test run function result ok ( AGUS & EDI & MUHAIMIN )
|
|
2025-12-11
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
HRG-ROOM-
|
Cleaning area HRG
|
Do clean up area HRG room and panel of HRG use instrument air supply ( JAJAT & ADI & DEVI )
|
|
2025-12-11
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Fabrication additional HRG filter
|
Do fabrication for filter additional of HRG ( ANDRI & DADANG )
|
|
2025-12-11
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
PMR service CEMS
|
Cleaning area motor purge air unit and filter motor, cleaning swivel window reflector and t/r unit dust hunter also flange with tube and alignment dust hunter, transducer A & transducer B flowsic 100, CEMS room, filter cabinet MCS 100E and CEMS gas room from dirty of dust use instrument air supply ( RIZAL & EVE SAFIR )
|
|
2025-12-10
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1
|
Clean up panel I/O
|
Cleaning up panel I/O area raw mill, 363 FN2, 363 BC1, feed bin from dirty of dust use hand blower ( JAJAT & ADI )
|
|
2025-12-10
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-FN1-&-363-FN2
|
Cleaning motor and filter motor
|
Do clean up area motor and filter motor from dirty of dust use instrument air supply and equipment cleaning tools ( ADI & EDI )
|
|
2025-12-10
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-PF1
|
Panel HMI issue error communication
|
Check cable communication result good communication cable ( RIZAL & JAJAT )
|
|
2025-12-10
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-MD1
|
Cleaning and check motor also CB and connection
|
Cleaning up area motor and filter motor also filter motor 363 FN2 also carbon brush room from dirty of dust use instrument air supply. Measure long carbon brush result normal ( EDI & EVE SAFIR )
|
|
2025-12-10
9 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
363-CV1
|
Issue oil come to motor check and install oil CPME to motor
|
Dismantling motor bring to workshop. Replace bearing motor install at site refill oil motor test run motor measure ampere result ok ( RIZAL & MUHAIMIN & EDI & ANDRI & DADANG )
|
|
2025-12-15
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-SR1
|
Issue high noise 7 gE
|
Add grease motor at FS and LS measure vibration & noise result below 4 mm/s and below 2 gE ( EDI & ROMY )
|
|
2025-12-09
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe - probe - filter sample line - sample line tube - diaphragm pump - filter balston - dryer gas pump from dirty of dust use instrument air supply. Check function humidity sensor and filter humidity result function sensor good and filter humidity good condition ( EDI & ADI & ROMY )
|
|
2025-12-09
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Prepare presentation TPM
|
Do prepare presentation for TPM ( JAJAT & RIZAL & MUHAIMIN )
|
|
2025-12-15
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-&-BURNER-FLOOR
|
Connect welding point
|
Do connect welding point area kiln and burner ( MUHAIMIN & ANDRI & DADANG & EVE SAFIR )
|
|
2025-12-15
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
413-3B1-&-3B2-&-463-KL1-&-473-CC1-&-443-PH1
|
clean up panel I/O
|
Do clean up panel I/O area blending east-blending west, KILN, Cooler and PH from dirty of dust use hand blower and equipment cleaning tool ( RIZAL & ADI & ROMY )
|
|
2025-12-15
9 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-FN1
|
AUTO Balancer support Mr. Eko Juan observation problem
|
Do replace controller result AUTO Balancer ready ( EKO & AGUS )
|
|
2025-12-08
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Complete also scan WBI & PMR support for AUDIT
|
Do complete data check sheet WBI and PMR 2025 for WBI elevator month July to November 2025 and calibration month of August 2025 ( JAJAT & ADI )
|
|
2025-12-08
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1
|
Cross check temperature preheater
|
Do cross check indication temperature at preheater. Adjust range at temperature transmitter to make same indication between local and CCR ( RIZAL & ANDRI )
|
|
2025-12-08
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR Service Critical Motor MD + FN (Raw Mill) + check RTD Motor ( special T6 )
|
Clean up area motor and filter motor. Measure vibration -noise - temperature for FS and LS motor. Add grease motor 25 times and 30 times for FS and LS motor. Also check RTD motor T6 at 363 MD1 result resistance RTD 144 ohm( AGUS & MUHAIMIN )
|
|
2025-12-08
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-&-L63-RM1
|
PMR Service Critical Motor Kiln + CM
|
Clean up area motor and filter motor. Measure vibration - noise - temperature FS and LS motor. Add grease motor 15 times - 25 times for FS and LS motor ( EDI & DADANG )
|
|
2025-12-05
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WF-LIMESTONE
|
Observation issue activation weigh feeder limestone high grade
|
Do observation at WF limestone high grade result ok ( RIZAL & MUHAIMIN )
|
|
2025-12-05
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Prepare Motor Rewinding (Blower Fan)
|
Do prepare motor for rewinding at workshop ( MUHAIMIN & JAJAT & DADANG & EDI )
|
|
2025-12-05
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER#-&-ER4-&-ER5-&-ER6
|
Cleaning MCC room
|
Do clean up MCC room for ER3 - ER4 - ER5 - ER6 from dirty of dust. Mop electrical room with equipment cleaning tool ( AIMAN )
|
|
2025-12-05
10 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
L1C-TR1
|
Prepare part project CCTV truck lift
|
Prepare part for project installation CCTV at L1C TR1 ( AGUS & MUHAIMIN )
|
|
2025-12-05
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Reposition probe sensor material level
|
Reposition probe sensor material level at L1C TR1. Test function probe sensor material level result ok function normal ( RIZAL & ANDRI & DADANG )
|
|
2025-12-05
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-EL1
|
PMR Serv. Elevator PH NAR1 & WBI Sump El
|
Do PMR Serv. Elevator PH NAR1 & WBI Sump El. Clean up 8th floor, 1st to 8th every door of elevator door from dirty of dust. Note lamp indication inside elevator off for 5th and 2nd floor ( EDI & ADI )
|
|
2025-12-05
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
413-3B1&-3B2-&-473-CC1
|
WBI Elec & Ins & Check I/O & S Pump Blending and Cooler
|
Do WBI Elec & Ins & Check I/O & S Pump Blending & ,Cooler. Test function sump pump motor result ok function Note need to clean up sensor sump pump at IDO tank ( EDI & ADI )
|
|
2025-12-04
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-MD1
|
PMS Raw Mill
|
Do clean up CB room and finding 2 ea CB already shorth, Replace CB ( AGUS & RIZAL & ANDRI & DADANG )
|
|
2025-12-04
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Prepare Motor Blower Rewinding
|
Prepare rewinding motor blower 463 FX6 ( EDI & ADI )
|
|
2025-12-04
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Prepare part project CCTV truck lift
|
Prepare part of project CCTV at truck lift ( AGUS & RIZAL & ANDRI & DADANG )
|
|
2025-12-04
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1-&-L3C-RE1
|
Cleaning panel of coal ( PM )
|
Do clean up panel of coal ( JAJAT & AIMAN )
|
|
2025-12-04
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1-&-463-KL1-
|
WBI Elec & Ins & Check I/O GCT, EP,PH&KL
|
Do WBI Elec & Ins & Check I/O GCT, EP,PH&KL. Measure vibration - noise - temperature FS and LS write at form for abnormal condition. Make notification for abnormal condition ( ADI & EVE SAFIR )
|
|
2025-12-04
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-423-BF1-&-FEED-BIN
|
WBI Electric & Ins & Check I/O Feed Bin
|
Do WBI Electric & Ins & Check I/O Feed Bin. Measure vibration - noise - temperature FS and LS for motor ( EDI )
|
|
2025-12-03
10 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
393-FN3
|
Issue motor burned
|
Do dismantle motor bring to workshop. Install motor spare at location also measure ampere motor R-S-T result ok ( EDI & DADANG )
|
|
2025-12-03
10 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
L1C-TR1
|
Observation part needed for installation CCTV
|
Do estimation part need for project installation CCTV ( RIZAL & EDI & DADANG )
|
|
2025-12-03
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Install sensor material level and Cleaning radio link and Control
|
Fabrication and installation sensor material level do monitoring function sensor result ok. Do clean up radio link and control ( RIZAL & ANDRI & AIMAN )
|
|
2025-12-03
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-FX6
|
Issue motor burned
|
Dismantle motor shell cooling kiln bring to workshop. Install motor spare at location test run function result normal motor running ok ( AGUS & EDI & DADANG )
|
|
2025-12-01
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe, probe, filter sample line, diaphragm pump, filter balston, dryer gas pump from dirty of dust. Check function humidity sensor and filter humidity, result function sensor normal and filter humidity good condition ( RIZAL & ANDRI )
|
|
2025-12-01
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-T1
|
Issue reading temperature abnormal
|
Replace thermowell because existing bad condition. Cross check reading temperature result around 1020 degree celcius ( RIZAL & ANDRI )
|
|
2025-12-01
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-&-473-CC1
|
PMR Critical Motor Area Kiln
|
Clean up area motor and filter motor. Measure vibration - noise - temperature FS and LS. Add grease 10 times - 15 times for FS and LS motor ( AGUS & EVE SAFIR )
|
|
2025-11-28
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-MD1-&-423-FN1-&-L63-MD1
|
Issue high noise information from CBM Mr. Najib
|
Add grease motor 15 times for FS and LS motor. Measure vibration result below 4 mm/s and noise below 2 gE ( EDI & DADANG )
|
|
2025-11-28
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1
|
Continue repare lighting lamp area preheater 7th floor
|
Install pipe for cable power lighting lamp. Connection cable power lighting lamp test on result lighting lamp ON ( EDI & DADANG )
|
|
2025-11-28
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Continue fabrication filter HRG
|
Do fabrication filter HRG ( ANDRI & DADANG )
|
|
2025-11-28
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-FN1
|
Support AutoBalancer Test
|
Do support test for AUTOBALANCER result normal ( JAJAT & AGUS & ANDRI )
|
|
2025-11-28
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Complete data check sheet WBI and PMR 2025
|
Completing data check sheet WBI and PMR year of 2025 prepare for AUDIT ( ADI & EDI )
|
|
2025-11-27
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Prepare CCTV for Truck lift (2 each)
|
Prepare CCTV 2 each for L1C TL1 ( AGUS & JAJAT )
|
|
2025-11-27
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1
|
Continue repare lighting lamp area preheater
|
Install panel junction box - pipe - pulling cable power from lighting lamp to junction box ( EDI & ADI & EVE SAFIR & DADANG )
|
|
2025-11-27
10 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
443-FN1
|
AutoBalancer Info Error (Check all sensor)
|
Check sensor AUTOBALANCER result normal (AGUS & ANDRI & DADANG )
|
|
2025-11-27
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-SG9
|
Issue indication abnormal for open and closed
|
Check function limit switch open and close at local, test function open and close but indication still failure. Found stick limit switch for closed bad condition replace stick limit switch test function open and closed result indication normal ( EDI & ADI & EVE SAFIR & DADANG )
|
|
2025-11-26
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ELECTRIC-ROOM
|
Inspection electrci room ( make sure there is keys replace if there is no inspection all electric room )
|
Do inspection electric room 3-4-5-6 and there is key for door electric room ( AIMAN )
|
|
2025-11-26
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TL1
|
Prepare CCTV for Truck lift ( 2 each )
|
Do prepare CCTV 2 each for truck lift ( AGUS & JAJAT )
|
|
2025-11-26
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1
|
Inspection lighting area 443 PH1 4th floor - 6th- 7th - 8th floor
|
Check lighting lamp at 4h floor result 1 lighting lamp off, 6th floor 1 lighting lamp off, 7th floor 3 lighting lamp off, 8th floor result 7 lighting lamp off. Replace lighting lamp 3 each at 7th floor test on result 1 lighting lamp ON, connecting power cable lighting lap at 6th floor join with AFR lighting lamp result lighting lamp ON ( EDI & ADI & DADANG )
|
|
2025-11-26
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer also replace 3 way valve
|
Clean up flange probe - probe - filter sample - sample line - diaphragm pump - filter balston - dryer gas pump from dirty of dust. Check function of humidity sensor and filter humidity result function humidity sensor normal and filter sensor good condition. Replace 3 way valve at 463 2K1 ( RIZAL & EVE SAFIR & ANDRI )
|
|
2025-11-26
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
YM CEMS support MCAL
|
Do support YM CEMS for MCAL with Mr. Hannes and Mr. Adrianus from Kiss Industrial Company ( RIZAL & ANDRI & KISS COMPANY )
|
|
2025-11-25
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
Issue problem at FIDOR
|
Flame off for FIDOR. Check supply H2 set to 3 bar supply gas input H2 at FIDOR available, reset air instrument air suply from normal to 0 PSI and resetting normal again also clean up connector for H2 gas at FIDOR found there is some dirty inside .Found fuse 4A at MCS 100E blown out, replace fuse with 6A result found there is jumpered cable at card. Dismantling jumpered cable at power on result ok Note FIDOR still flame off ( HANNES & JAJAT & ADI )
|
|
2025-11-25
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-MD1
|
Issue high winding temperature information from CBM Mr. Najib
|
Clean up filter 363 FA2. Check thermal stater up 80% because high fluctuation ampere until 265 A ( JAJAT & AGUS )
|
|
2025-11-25
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-MD1
|
Issue high noise information from CBM Mr.Najib
|
Clean up area motor and filter motor. Measure vibration and noise motor FS and LS result FS HVA: 1.1 to 3.7 mm/s and 1.60 to 3.44 gE LS HVA: 1.2 to 2.9 mm/s and 0.65 to 3.34 gE ( JAJAT & AGUS )
|
|
2025-11-25
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-SC3
|
Fabrication cable rel and make position of cable and install terminal of 393 SC3 SGD-SGE-SGF
|
Do fabrication cable rel and make cable position and install terminal 393 SC3 for SGD - SGE - SGF ( EDI & ANDRI & DADANG )
|
|
2025-11-25
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Prepare CCTV for truck lift 2 each
|
Do prepare CCTV for truck lift 2 each ( AGUS )
|
|
2025-11-25
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1
|
Front Cover probe broken
|
Replace front cover probe ( JAJAT & ANDRI )
|
|
2025-11-24
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
HRG
|
Issue pump clorine abnormal function
|
Modification pipe way clorine ( JAJAT & EVE SAFIR )
|
|
2025-11-24
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-BF1
|
Issue leakage compartement 2 & 8
|
All solenoid are working, replace big membrane but still find leakage at small s/v ( RIZAL & ADI & ANDRI )
|
|
2025-11-24
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-L63-CM1-463-KL1-473-CC1
|
PMR service critical motor RM-KL-CC
|
Clean up area motor and filter motor. Measure vibration-noise-temperature FS and LS. Add grease motor 20 times-25 times-30 times for FS and LS motor and check carbon brush ( AGUS & EVE SAFIR & DADANG )
|
|
2025-11-22
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-SC3-&-ER3
|
Pulling cable KDRT, also pulling cable SGD - SGE - SGF; fabrication speed motion for 393 SC3; ER3: pulling cable remote VCS, signal S & G
|
Pulling cable of KDRT also fabrication speed motion and pulling cable SGD-SGE-SGF for 393 SC3 and Pulling cable at ER3 for remote VCS and signal S & signal G ( JAJAT & AGUS & RIZAL & EDI & ADI & MUHAIMIN & ANDRI & DADANG )
|
|
2025-11-21
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
33-WF1
|
Calibration zero and span
|
Do calibration zero and span result zero: 0.0 t/h span 162 t/h ( calculation 52.5 / 0.42 x 0.36 x 3.6 = 162 t/h ) ( RIZAL & ANDRI )
|
|
2025-11-21
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-CV1
|
Issue oil come inside motor
|
Dismantling motor bring to workshop, replace bearing. Install motor measure ampere motor result 6.03 ampere - 6.43 ampere -7.43 ampere also measure vibration and noise motor result 0.0 mm/s and 0.45 gE ( JJAJAT & AGUS & EDI & MUHAIMIN & DADANG )
|
|
2025-11-21
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3;-ER4;-ER5;-ER6
|
Inspection ALL ER
|
Do clean up electric room use brush and vacuum cleaner and continue mop electric room also clean up filter cabinet ( AIMAN )
|
|
2025-11-21
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3
|
Observation extend DI at 363 FN1
|
Prepare cable installation ( JAJAT & RIZAL )
|
|
2025-11-21
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-FA1;-473-FA3;-473-FA4;-473-FA6
|
Add grease motor issue high noise motor up to 2 gE information from CBM Mr. Najib
|
Add grease motor cooler measure noise motor result decrease below 2 gE for 473 FA1 - 473 FA3 - 473 FA4 - 473 FA6 ( EDI & ADI )
|
|
2025-11-21
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TL1
|
Repare Short cable
|
Replace short cable for lighting lamp. Test on lighting lamp result ok normal ( AGUS & MUHAIMIN & ANDRI )
|
|
2025-11-21
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-BC1-&-L1C-BC2-&-L1C-BC3
|
Repare / instal lighting lamp tail L1C-BC1-3
|
Replace blinking lighting lamp west side 2 each for room of L1C BC1-3 and east side 1 each at L1C BC2. Test on result lighting lamp ok all lighting lamp on ( EDI & ADI & DADANG )
|
|
2025-11-20
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Complete data check sheet PMR and WBI month of november 2025
|
Do completing data check sheet PMR analyzer L63 2K1 - L63 2K2 - L63 2K3 - 483 2K1 - 463 2K1 - 443 2K1 - 423 2K1; PMR IR TAD - T scanner - CCTV - Camera burner; PMR service hoist crane; PMR service critical motor KL & CM; WBI electrical & instrumentation bottom blending - kiln - cooler - clinker silo ; WBI electrical & instrumentation top blending - CT - PH - kiln; WBI electrical & instrumentation CM - truck lift - BC transport - tripper - reclaimer coal; WBI electrical & instrumentation feed bin - raw mill - CT - dust transport - BF for month of november 2025 ( JAJAT & ADI )
|
|
2025-11-20
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TL1
|
Trucklift PM ( repair support for LCS BC1-3, observation safety device BD-ML, relocation cable BD of tripper )
|
Repaire Rel LCS BC1-3, Dismantling unuse cable, install and fabrication new lighting lamp, repaire / replace solenoid water L1-BC5. repaire pull core at TR1, observation installation LAN at L1C TL1 ( JAJAT & AGUS & RIZAL & EDI & ANDRI & MUHAIMIN & DADANG )
|
|
2025-11-19
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-BC4
|
Replace lighting lamp off
|
Install 2 eah lighting lamp LED ( EDI & ADI & DADANG )
|
|
2025-11-19
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-FN1-M1
|
install motor
|
Do install motor at 483 FN1 M1. Test function motor measure ampere motor with open damper 65% result 48.7 ampere; 100% result 5.34 ampere with setting OL 7 ampere ( JAJAT & AGUS & RIZAL & MUHAIMIN & DADANG )
|
|
2025-11-19
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-MD1-&-483-BL5-&-493-FN5
|
Issue high vibration up 24 mm/s and high noise up 6 gE
|
Add grease motor 15 times for FS and LS. Measure vibration and noise motor result below 4 mm/s also below 2 gE. Note 493 FN5 there is no point for grease motor also measure vibration from base plat motor result high vibration ( EDI & ADI )
|
|
2025-11-19
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-FA2
|
V-belt motor are cracked bad condition
|
Do replace v-blet v-800 3 each ( EDI & ADI )
|
|
2025-11-18
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ANALYZER-ROOM
|
Cleaning up room analyzer
|
Clean up analyzer room from dirty of dust use brush and instrument air supply ( AIMAN )
|
|
2025-11-18
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
PMR service CEMS
|
Clean up purge air unit motor and filter purge air unit. Also clean up swivel window T/R unit and R unit for dust hunter and flange with tube from dirty of dust. Do alignment dust hunter. Clean up transducer A & transducer B for flowsic 100. Clean up CEMS room and gas botle room and fan cabinet MCS 100 E from dirty of dust ( RIZAL & ENDEN )
|
|
2025-11-18
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-FN1-M1-&-483-FN1-M2
|
Issue motor noise for M1 and trip OCR also breaker. Observation motor
|
Check actual process at CCR, found 483 FN1 M2 running, but 483 FN1 M1 stop. Check at local use meger test found 2 phase ground. Bring down existing motor. Found 3.7 KW same existing motor bring to workshop from ware house. Measure ampere motor stable 3.6 ampere ( JAJAT & AGUS & EDI & ADI & MUHAIMIN & DADANG & ENDEN )
|
|
2025-11-17
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Resetting position of material level and timer ML from 10 s to 5 s
|
Do resetting sensor material level and change timer from 10 second to 5 second ( RIZAL & ADI & ANDRI & DADANG )
|
|
2025-11-17
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-BC4
|
Activated horn at L1C BC4
|
Do install horn at L1C BC4 and connected cable power for horn and cable DO at ER6. Test function horn result success ( JAJAT & AGUS & ADI & MUHAIMIN & DADANG )
|
|
2025-11-17
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe - probe - filter sample line - sample line - diaphragm pump - filter balston - dryer gas pump from dirty of dust. Check function humidity sensor result function normal also check filter humidity sensor result condition filter good ( RIZAL & ANDRI )
|
|
2025-11-17
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-&-L63-RM1
|
PMR critical motor area KILN & CM
|
Clean up area motor and filter motor. Measure vibration - noise - temperature of FS and LS. Add grease 20 times - 30 times for FS and LS motor ( AGUS & DADANG )
|
|
2025-11-17
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM-&-463-KL1
|
PMR critical motor area RM & KILN
|
Clean area motor and filter motor also filter 363 FA2. Measure vibration, noise and temperature of FS and LS. Add grease 10 times - 15 times - 25 times for FS and LS motor. Repaire AUTO grease pump for 363 FN2 ( MUHAIMIN & ADI )
|
|
2025-11-14
10 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
HRG
|
Prepare subtitution and fabrication filter substitution HRG
|
Take materials elbow plate from warehouse. Fabrication support filter substitution at workshop ( ANDRI & MUHAIMIN & DADANG )
|
|
2025-11-14
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KH1-P1
|
Issue indication pressure low at operator CCR
|
Cross check indication pressure at local. Do blow up tubing for pressure and zero adjust of pressure transmitter and measure pressure hood draft result indication pressure at local from 0.1 to 0.7 compare with reading CCR same ( RIZAL & ANDRI )
|
|
2025-11-14
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-FN1-&-473-FA6
|
Issue high noise motor 6.3 gE for 423 FN1 & 13.6 gE also 5.6 gE for 473 FA6
|
Add grease motor 15 times for FS and LS, measure noise motor result for 423 FN1 FS V: 1.49 gE H: 0.67 gE A: 1.48 gE - LS A: 1.18 gE V: 1.07 gE H: 1.33 gE; for 473 FA6 LS: 1.15 gE FS: 1.04 gE ( MUHAIMIN & ADI )
|
|
2025-11-14
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORKSHOP-ELECTRIC-1
|
Prepare take plat cable 12 core from NR2
|
Do take plat cable 12 core at electric Nr2 bring to workshop electric Nr1 ( AIMAN & DADANG )
|
|
2025-11-14
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe, probe, filter sample, sample line, diaphragm pump, filter balston from dirty dust. Check function humidity sensor and filter humidity result function humidity sensor normal and filter humidity good condition. Note replace dryer gas at 463 2K1 with spare unit because existing fault ( RIZAL & ANDRI )
|
|
2025-11-14
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-BL7
|
Issue cooling fan off
|
Take cooling fan at ER3, fabrication supporting cooling fan at workshop. Install cooling fan at 483 BL7 test function result fan running normal ( AGUS & DADANG )
|
|
2025-11-14
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
HOIST-L1C-TR1
|
Hoist L1C TR1 issue can not start at local ( support for certification hoist by 3rd party )
|
Check at ER6 found power of for hoist at L1C TR1, make On for breaker hoist test function result can start at local ( ADI & MUHAIMIN & JOKO SAFETY )
|
|
2025-11-13
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Install senso material level and power supply 220 VAC
|
Fabrication support for sensor material level at workshop. Install sensor material level at L1C TR1. Do test function L1C TR1 and activation sensor material level, result function sensor normal. Install power 220 VAC at L1C TR1, test function power 220 VAC result normal ( JAJAT & RIZAL & ADI & MUHAIMIN & DADANG )
|
|
2025-11-13
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER4-&-ER5
|
Issue sealing trafo room bad condition information finding from CBM
|
Add sealing for area finding CBM Mr. Najib for trafo ER4 and ER5 ( AGUS & DADANG )
|
|
2025-11-13
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-BL7
|
Issue noise high 5.6 gE and high vibration 4.5 mm/s
|
Add grease motor result noise reduce back to normal below 2 gE and vibration below 4 mm/s ( AGUS & DADANG )
|
|
2025-11-13
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-FA6
|
Cross check pressure point
|
Clean up tubing sample pressure point and flange pressure point from dirty of dust result pressure back to normal condition ( JAJAT & ADI & MUHAIMIN )
|
|
2025-11-13
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
CEMS problem board abnormal
|
Check at site found 5 VDC drop to 4.8 VDC increase voltage to 5.0 VDC and clean up filter and tighten cable connection result CEMS back to normal ( RIZAL & ANDRI )
|
|
2025-11-13
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-BL7
|
Issue noise high 5.6 gE and vibration 4.5 mm/s
|
Add grease motor result noise reduce back to normal below 2 gE and vibration below 4 mm/s ( AGUS & DADANG )
|
|
2025-11-12
10 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-SC3
|
Issue pulse motion bad condition
|
Clean up probe sensor and propeller and tighten cable at pre amplifier card result pulse motion back to normal and already indication at CCR operator ( MUHAIMIN & DADANG )
|
|
2025-11-12
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Complete data check sheet report PMR and WBI month november 2025
|
Do completing data check sheet report for PMR analyzer L63 2K1-L63 2K2-L63 2K3-483 2K1-463 2K1-443 2K1-423 2K1; PMR camera burner-IR TAD-T scanner-CCTV; PMR service critical motor 363 MD1-363 FN1-363 FN2-423 FN1-443 FN1-L63 MD1-L63 FN1-473 FN7-463 MD1 for month of november 2025 ( JAJAT & ADI )
|
|
2025-11-12
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-CP1
|
Install lighting lamp
|
Installing lighting lamp at 393 CP1, test function lighting lamp result normal on ( MUHAIMIN & DADANG )
|
|
2025-11-12
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-&-473-CC1
|
Continue PMR service critical motor are KL & CM
|
Clean up area motor and filter motor. Measure vibration, noise and temperature for FS and LS. Add grease motor for FS and LS for 30 times 35 times area L63 RM & 463 KL1 ( AGUS )
|
|
2025-11-12
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-BF1
|
Issue problem at compartemen 4 & compartemen 11
|
Replace solenoid valve 2 each at compartemen 4 and compartemen 11, test function solenoid valve of purging result ok function normal ( RIZAL & ANDRI )
|
|
2025-11-11
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
HRG
|
Issue chiller problem
|
Check at local, do jumper cable test on, found i motor bad condition. Dismantling motor chiller, bring to workshop. Install back support and cover motor chiller. Clean up area HRG from dirty of dust use instrument air also filter HRG ( JAJAT & AGUS & ADI & ANDRI & MUHAIMIN & DADANG )
|
|
2025-11-11
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-463-KL1
|
PMR Service Critical Motor & LSR RM & CM1 & KL
|
Clean up area motor and filter motor. Measure vibration, noise and temperature for FS and LS. Add grease motor for FS and LS for 20 times, 25 times and 30 times ( AGUS & DADANG )
|
|
2025-11-10
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Continue pending Job
|
Activation alarm Over travel, Brake Motor, Install Motion and propeller SX1-SX3 also propeller at BC3 ( AGUS & JAJAT & RIZAL & ADI & ANDRI & MUHAIMIN & DADANG )
|
|
2025-11-10
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-BF1
|
Issue compartemen 10 Abnormal
|
Replace membran solenoid valve. Test function result ok ( RIZAL & ANDRI )
|
|
2025-11-10
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
MAIN-GATE-ACCES-CONTROL
|
Inspection welding and electrical tools of PT Indoporlen and PT RMP
|
Do inspection electrical and welding tools of PT INDOPORLEN & PT RMP Tagging with yellow color for all equipment ( ADI & JAJAT )
|
|
2025-11-07
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-GQ1
|
Prepare fabrication re-position Sensor Pressure 473-GQ1
|
Do fabrication for reposition sensor pressure. Install at location result indication normal ( RIZAL & ANDRI & DADANG )
|
|
2025-11-07
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-463-KL1-&-L63-RM1
|
WBI Switchgear, Cap & Trafo RM, KL & CM1
|
Do WBI Switchgear, Cap & Trafo RM, KL & CM1 ( MUHAIMIN )
|
|
2025-11-07
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
BOTTOME-BLENDING--473-CC1-493-3S1
|
WBI Elec & Ins & Check I/O & S Pump Bl,C
|
Clean up panel I/O area clinker silo-cooler-bottom blending outside panel use equipment cleaning tools. Check function of sump pump result norma function note repaire propeller sump pump L1C BC4 because at outside tank test function sump pump result ok ( EDI & ADI )
|
|
2025-11-07
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
PPUP-WORKSHOP
|
Check Tools Area PPUP
|
Inspection electrical tools of PPUP for mixer-cutting machine-portable compressor-genset. Repaire support for cutting machine reason is not requirement safety plant. Tagging equipment with yellow color ( EDI & ADI )
|
|
2025-11-06
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Issue for L1C BC6 can not start and tidy up cable PLC
|
Check at program found there is some failure at L1C BC6 after reset and run AUTO program result L1C BC6 can run. Tidy up un use cable at PLC result ok ( JAJAT & AGUS & EDI & ADI & MUHAIMIN & DADANG )
|
|
2025-11-06
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-FA4
|
Issue indication abnormal
|
Check at location found leakage of tubing sample pressure and some material block inside tubing, repaire leakage tubing and clean up sample line tubing result indication pressure back to normal at CCR ( RIZAL & ANDRI )
|
|
2025-11-05
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Continue Project L1C-TR1
|
Test run indication signal ready-run-trip-emergency for L1C BC1 to L1C BC7, also signal pcs and bd-tonase result ok ( JAJAT & AGUS & RIZAL & ADI & ANDRI & MUHAIMIN & DADANG & EDI )
|
|
2025-11-04
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
PROJECT L1C-TR1
|
Do connection wiring cable for project L1C TR1. Do test function for start-running-trip-failure for L1C BC1-L1C BC2-L1C BC3-L1C BC7-L1C SX1-L1C SX2-L1C SX3 result ok also measure ampere motor result ampere of SX: 2.1 to 4.2 A for BC: 8.8 to 9.4 A ( JAJAT & AGUS & RIZAL & EDI & ADI & ANDRI & MUHAIMIN & DADANG & AIMAN )
|
|
2025-11-04
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-BF1
|
Issue purging abnormal
|
Check function solenoid valve purging bag filter found 8 membran for solenoid valve bad condition. Replace 8 membran solenoid valve test function result normal function ( RIZAL & ANDRI )
|
|
2025-11-03
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
HRG
|
Replace clorine pump issue pump performance pump already decrase
|
Replace pump clorine with spare pump test function pump result ok ( EDI & ADI )
|
|
2025-11-03
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1
|
Indication temperature outlet fluctuation
|
Replace sensor temperature with spare result indication temperature normal ( RIZAL & ANDRI )
|
|
2025-11-03
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Final Drawing Upgrade L1C-TR1
|
Do final drawing for upgrade L1C-TR1 save at computer ( AGUS )
|
|
2025-11-03
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-463-KL1
|
PMR service critical motor LSR RM-CM
|
Do clean area motor and filter motor. Measure vibration, noise, temperature for FS and LS motor. Add grease for 20 times and 30 times for FS and LS motor ( EDI & ADI )
|
|
2025-11-03
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-&-L63-RM1
|
PMR Service Critical Motor & LSR Kiln & Cooler 1
|
Do clean area motor and filter motor. Measure vibration, noise, temperature for FS and LS motor. Add grease for 20 times and 25 times for FS and LS motor ( MUHAIMIN & DADANG )
|
|
2025-11-03
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L93-3S1
|
Issue Temp Bottom Bin increase- Check Solenoid Purging
|
Check at location bag filter result there is solenoid valve normal, replace 1 solenoid. Test function solenoid valve result ok normal. Check value temperature bin of coal result normal indication ( RIZAL & ANDRI )
|
|
2025-10-31
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-MD1
|
363 MD1 check - clean up - replace carbon brush
|
Clean up filter 363 FA2 for filter main drive, area motor and room carbon brush. Measure long all carbon brush found no 1-2-5-11-12 bad condition. Replace carbon with spare units for no 1-2-5-11-12 ( ADI & MUHAIMIN )
|
|
2025-10-31
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
Y43-1G1
|
Service / replace pump antscalant
|
Replace pump antscalant test run function result ok ( RIZAL & EDI & DADANG )
|
|
2025-10-31
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1
|
IKGA probe Support
|
Do continue welding probe support and repainting area 463 2K1 ( RIZAL & EDI & DADANG & ANDRI & WIKAN & AIMAN )
|
|
2025-10-31
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER6
|
Labelling cable ER6 - Tripper (L1C-TR1) + scun cable
|
Continue do labelling cable at ER6 and observation area tripper ( AGUS & ADI & MUHAIMIN )
|
|
2025-10-30
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Observation add 3 Modul DO PLC
|
Prepare Modul additional ( RIZAL & JAJAT )
|
|
2025-10-29
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe, probe, filter sample line, sample line, diaphragm pump, filter balston from dirty of dust. Check function humidity sensor and filter humidity, result function humidity sensor good and filter humidity ok ( RIZAL & ANDRI )
|
|
2025-10-29
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-BF1
|
Install lighting lamp
|
Do installation lighting lamp at 423 BF1, test on lighting lamp result normal on ( EDI & DADANG )
|
|
2025-10-29
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Completing data PMR and WBI month october 2025
|
Do complete data check sheet PMR and WBI month of october 2025 ( JAJAT & ADI )
|
|
2025-10-29
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-EL1
|
lighting lamp inside elevator room off
|
Replace lighting lamp area inside elevator 2 each, test on result lamp normal on ( MUHAIMIN & AIMAN )
|
|
2025-10-29
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER5
|
Lighting lamp issue off at ER5 outside
|
Replace lighting lamp with spare, test on result lighting lamp normal ( ADI & MUHAIMIN )
|
|
2025-10-28
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
KILN-SCANNER
|
Kiln Scanner (View Abnormal)
|
Replace limit switch of t scanner, test function result view good at CCR ( RIZAL & ANDRI )
|
|
2025-10-28
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-L63-RM1
|
PMR Service Critical Motor & LSR RM & CM1
|
Clean up area motor and filter motor. Measure vibration - noise - temperature FS and LS motor. Add grease motor 25 times - 30 times - 35 times for FS and LS motor ( MUHAIMIN & DADANG )
|
|
2025-10-28
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
BURNER-FLOOR
|
Connect Motor Hoist Area Burner
|
Do connecting motor hoist area burner ( MUHAIMIN & DADANG )
|
|
2025-10-28
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-SR1
|
Cleaning Finishing room trafo 363-SR1
|
Continue finishing room trafo 363 SR1 from dirty of dust use equipment cleaning tools and instrument air supply ( JAJAT & DEVI )
|
|
2025-10-28
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-BF1
|
Solenoid compartement 8 issue purging but no air supply
|
Check at location found 1 solenoid valve bag filter is not function normal, replace 1 solenoid valve test function result normal ( RIZAL & ANDRI )
|
|
2025-10-28
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Complete check sheet PMR or WBI month of october 2025
|
Completing data check sheet PMR analyser L63 2K1-L63 2K2-L63 2K3-483 2K1-463 2K1-443 2K1-423 2K1; PMR IR TAD-T scanner-CCTV-Camera Burner; PMR Hoist and Crane; WBI Bottom Blending-KILN-Cooler-Clinker Silo; WBI Top Blending-CT-PH-KILN; WBI CM-Truck Lift-BC Transport Tripper-Reclaimer Coal; WBI Feed Bin-Raw Mill-CT-Dust Transport-BF month of october 2025 ( JAJAT & ADI )
|
|
2025-10-27
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1
|
fabrication and installation rel also rooler
|
Fabrication for installation rel rooler 463 2K1Installation at local, test run insert probe and retract probe flange result normall ( JAJAT, AGUS, RIZAL, ANDRI, DADANG, MUHAIMIN )
|
|
2025-10-27
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-SR1
|
Cleaning trafo room 363-SR 1
|
Do clean up trafo room from dirty of dust use equipment cleaning tools and instrument air ( JAJAT & ADI & AIMAN )
|
|
2025-10-24
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Wiring panel welding of burner floor
|
Do wiring of panel welding for burner floor. Panel welding ready to install ( AGUS & MUHAIMIN )
|
|
2025-10-24
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-BF1
|
Pulling cable power solenoid valve and install solenoid valve 2 groups
|
Do pulling cable 2 line for power solenoid valve 2 groups and installation 2 groups solenoid valve ( JAJAT, AGUS, RIZAL, ADI, MUHAIMIN, ANDRI, DADANG )
|
|
2025-10-24
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1-GEMBA-TPM-
|
Clean up area outside CEMS shelter
|
Do GEMBA TPM clean area CEMS gas room, wall, roof from dirty of dust use equipment cleaning tools and instrument air supply ( JAJAT, ADI, AIMAN )
|
|
2025-10-23
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-MD1
|
Pulling cable power at L63-MD1
|
Pulling cable for power L63 MD1 ( AGUS & MUAHIMIN & ANDRI )
|
|
2025-10-23
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Clean up flange probe-sample line-filter sample line-diaphragm pump-filter balston from dirty of coal. Check function humidity sensor and filter humidity result function humidity normal and filter good condition ( RIZAL & AIMAN )
|
|
2025-10-23
11 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
ER6-&-ER5
|
PMR Clean Up MCC ER All Area Kiln Nar1
|
Do clean up MCC area ER 6 and ER5 from dust use broom and vacuum filter also filter cabinet from dirty of dust ( AIMAN )
|
|
2025-10-23
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1-&-473-FA3
|
Install lighting lamp 4th floor 443 PH1 and fix also dismantling stop contact area cooler ex 473 FA3
|
Do install lighting lamp at 4th floor test on lamp result ok, fix and dismantling stop contact area ex cable 473 FA3 ( JAJAT & EDI & DADANG )
|
|
2025-10-22
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Sort it out and 5R part work shop
|
Do sort it out part and 5R part area workshop of electric ( JAJAT & AIMAN )
|
|
2025-10-22
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe-probe-filter sample line-sample line-dryer gas pump-filter balston from dirty of dust. Check humidity sensor function and filter sensor result function sensor normal and filter good condition ( EDI & ADI )
|
|
2025-10-22
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
Support Yearly Maintenance CEMS
|
Do support yearly maintenance CEMS with KISS INDUSTRIAL employee hannes and adrianus ( RIZAL & ANDRI & DADANG & KISS INDUSTRIAL )
|
|
2025-10-21
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
HRG
|
Lamp of HRG blinking
|
Replace lamp test lamp result lamp on ( ANDRI )
|
|
2025-10-21
11 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
443-PH1
|
IR TAD issue indication temperature low
|
Cross check by portable tools result normal compare between local and CCR are same ( RIZAL & MUHAIMIN )
|
|
2025-10-21
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
493-AC1
|
Prepare and connection welding point burner
|
Do connection welding panel near 493 AC1 result finnish note wait input power welding at buttom cooler ( EDI & ADI & DADANG )
|
|
2025-10-21
11 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
423-2K1
|
YM CEMS
|
Yearly maintenance CEMS and do support KISS Industrial work YM CEMS ( RIZAL & MUHAIMIN & ANDRI & KISS INDUSTRIAL EMPLOYEE MR. HANNES - MR. ADRIANUS )
|
|
2025-10-21
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
HRG
|
Failure start
|
Reset Alarm , Start step-by-step , monitor di 60% ( AGUS & RIZAL )
|
|
2025-10-20
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1
|
Observation instalation blower sheel kiln
|
Do observation for instalation motor sheel kiln ( RIZAL & MUHAIMIN & ANDRI )
|
|
2025-10-20
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-&--L63-RM1
|
PMR Service Critical Motor area Kiln & CM1
|
Clean up area motor and filter motor. Measure vibration-noise-temperature FS (NDE) and LS (DE) motor. Add grease motor for 25 times and 30 times for FS (NDE) and LS (DE) motor ( AGUS & DADANG )
|
|
2025-10-20
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-443-PH1
|
PMR Service Critical Motor area RM
|
Clean up area motor and filter motor. Measure vibration-noise-temperature FS (NDE) and LS (DE) motor. Add grease motor for 10 times and 15 times for FS (NDE) and LS (DE) motor ( EDI & ADI )
|
|
2025-10-18
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1-;-473-CC1;-L63-RM1;-FEED-BIN
|
Clean panel I/O
|
Do clean up panel I/O area preheater-cooler-coal mill hs-feed bin from dirty of dust use hand blower ( ADI & AMIT & SAIPUL )
|
|
2025-10-18
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-FA3
|
Pulling cable motor from local to ER5
|
Do pulling cable motor from local to ER5, test meger cable result ok. Do test run motor with different speed result ok ( JAJAT, AGUS, RIZAL, ADI, ANDRI, AIMAN, MIHAIMIN, DADANG )
|
|
2025-10-17
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
493-AC2
|
Prepare & Pulling Cable welding point Cooler
|
Pulling cable and cleaning material cable rel ( JAJAT & AGUS & RIZAL & ADI & MUHAIMIN & ANDRI & DADANG & AIMAN )
|
|
2025-10-17
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-SC3
|
Installation and wiring 393-SC3 ( MCC part + LCS+ Motion )
|
Prepare part needed ready to install ( MUHAIMIN & ANDRI & DADANG )
|
|
2025-10-17
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
TPM Area CEMS
|
Do TPM area 423 2K1. Clean air tank, wall outside. Repainting blue color for air tank, green color for wall outside shelter 423 2K1, yellow color for roof outside ( JAJAT, AGUS, RIZAL, ADI, ANDRI, AIMAN, MUHAIMIN, DADANG )
|
|
2025-10-16
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
493-AC2
|
Relocation welding point
|
Relocation welding point close to main distribution welding point ( AGUS & ANDRI & DADANG )
|
|
2025-10-16
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
493-3B1
|
Check Greasing and Cleaning Area Clinker Silo
|
Clean up ALL LCS , Motor, Greasing Motor 493-AC2/AC3 ( JAJAT & MUHAIMIN )
|
|
2025-10-16
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Clean up flange probe-sample line-filter sample-diaphragm pump-filter balston-dryer gas pump from dirty of coal. Check humidity sensor function and filter humidity result function sensor normal and filter good condition ( RIZAL )
|
|
2025-10-16
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
CIVIL-BUILDING-WORKSHOP
|
Inspection electrical and welding tools of Civil Building
|
Inspection electrical tools of civil building tagging with yellow color. ( ADI & EVE AKPAN )
|
|
2025-10-15
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
493-AC2
|
Observation cable welding point area 493 AC2 and planning tap power
|
Do observation cable welding point for 493 AC2 and planning power tap ( MUHAIMIN & AIMAN )
|
|
2025-10-15
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-SC3-&-3-SG
|
Prepare part needed for new installation 393-SC3 + 3 Slide Gate (MCC part + LCS+ Motion)
|
Do prepare part needed new installation 393 SC3 and 3 SG like MCC & motion & LCS ( RIZAL & MUHAIMIN )
|
|
2025-10-15
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Cleaning Area L1C-TR1 (MCC + Radio Link)
|
Do clean up area L1C TR1 for MCC and radio link ( AIMAN )
|
|
2025-10-15
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Finishing Fabrication I/O additional 2nd floor
|
Do finishing fabrication I/O panel 2nd floor ( ANDRI & DADANG )
|
|
2025-10-15
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
CIVIL-BUILDING-WORKSHOP
|
Inspection electrical and welding tools
|
Inspection electrical and welding tools of Civil building work shop. Tagging equipment with yellow color. Note 2 extention cable unsafe to use, 1 circle machine because cable power failure and connector male and female failure ( ADI )
|
|
2025-10-14
11 months ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
393-SC3-&-3-SG
|
Observation part needed new installation 393 SC3 and 3 slide gate
|
Observation part needed new installation 393 SC3 and 3 slide gate ( JAJAT & RIZAL & MUHAIMIN )
|
|
2025-10-14
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1
|
Fabrication I/O additional 2nd floor
|
Fabrication I/O additional at 2nd floor ( MUHAIMIN & ANDRI & DADANG )
|
|
2025-10-14
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
PT-TRUBA-JAGA-CITA
|
Inspection electrical and welding tools
|
Do inspection electrical and welding tools of PT Truba Jaga Cita. Equipment tagging with yellow color ( Total electrical tools: 28 units, welding tools: 6 units ) ( ADI & EVE AKPAN )
|
|
2025-10-13
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-CC1
|
473 FA Cooler refill easylube + greasing
|
Add greaseing motor for FS and LS. Also refill easylube fan motor ( MUHAIMIN )
|
|
2025-10-13
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe-probe-sample line-filter sample line-diaphragm pump-filter balston-dryer gas pump from dirty of dust. Check humidity sensor function and filter humidity result function humidity sensor normal and filter humidity good condition ( RIZAL & ANDRI )
|
|
2025-10-13
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-BF3
|
Replace & Service PLC
|
Service PLC 393 BF3, test function result PLC normal ( AGUS & DADANG )
|
|
2025-10-13
11 months ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-L63-RM1
|
PMR Service Critical Motor & LSR RM & CM1
|
Clean area motor and filter motor. Measure vibration-noise-temperature FS and LS. Add grease 10 times-15 times-25 times and 30 times for FS and LS motor.( ADI & EVE AKPAN )
|
|
2025-10-10
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1
|
Measure mV OZD
|
Measure mV OZD for area RM ( RIZAL & EVE TEGAR )
|
|
2025-10-10
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-MD1-&-363-FN1
|
Check and cleaning carbon brush
|
Cleaning carbon brush room and area motor. Measure long all carbon brush, replace carbon brush 1 because sort 3100 mm. Cleaning carbon brush room and area motor. Measure long all carbon brush for 363 FN1 M1 result ok ( AGUS & MUHAIIMIN & EVE AKPAN )
|
|
2025-10-09
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Clean up flange probe-sample line-filter sample line-diaphragm pump-filter balston-dryer gas pump from dirty of coal. Check humidity sensor function and filter humidity result function humidity normal and filter humidity good condition ( RIZAL & EVE TEGAR & ANDRI )
|
|
2025-10-09
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1
|
Observation power pump fire protection 5th floor
|
Connection cable power pump fire at 5th floor ( EDI & MUHAIMIN )
|
|
2025-10-09
1 year ago
|
NR.SHIFT
|
Wahyu Adi Triono
|
WORK-SHOP
|
Continue fabrication Welding Point
|
Fabrication welding point at workshop ( AGUS & EVE AKPAN & DADANG )
|
|
2025-10-09
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-FA3
|
Observation cable signal S-G Observation cable signal S-G
|
Replace signal cable S-G test signal result ok ( RIZAL & EVE TEGAR & ANDRI )
|
|
2025-10-08
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-BL1
|
Replace Handle LCS failure
|
Replace LCS handle and test signal result ok ( MUHAIMIN & EVE AKPAN )
|
|
2025-10-08
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
PT-PINCURAN-MAS
|
Check Tool Pincuran Work Shop
|
Inspection electrical and welding tools of PT Pincuran Mas. Tagging equipment with blue color ( MUHAIMIN & EVE TEGAR & EVE AKPAN )
|
|
2025-10-07
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1
|
Repare Welding Point 6th floor and dismantling Box ( ex-cable sensor 7th floor)
|
Do repare welding at 6th floor and dismantling box or ex cable sensor at 7th floor ( MUHAIMIN & DADANG )
|
|
2025-10-07
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER4
|
Istall platform bottom ER4
|
Install platform bottom ER4 ( MUHAIMIN & ANDRI & AIMAN )
|
|
2025-10-07
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RF1
|
Reposition speed sensor
|
Adjusting probe, monitor oke ( RIZAL & ANDRI )
|
|
2025-10-07
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
HRG
|
Repare Emergency Door HRG-WTP
|
Do repare welding evacute door + storage chemical room ( JAJAT & DADANG )
|
|
2025-10-07
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-EL1
|
PMR Serv. Elevator PH NAR1 & WBI Sump El
|
Do clean up room of elevator, door elevator from 1st to 8th floor from dirty of dust, cage of elevator from dirty of dust, drive of elevator also from dirty of dust use hand blower. Test function elevator from 8th to 1st floor result normal function. WBI sump pump of elevator ( AGUS & EVE AKPAN )
|
|
2025-10-07
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1;-L63-RM1;-463-KL1
|
PMR CCTV, IR TAD & Kiln Scanner
|
Clean lens IR TAD, camera burner & T scanner-flange probe-camera CCTV from dirty of dust use cleaning tools ( ADI & EVE TEGAR )
|
|
2025-10-06
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-MD-&-453-BL1-&-483-BL5-&-483-BL9
|
Add greasing motor for FS and LS
|
Add greasing motor for FS and LS. Measure vibration-noise for FS and LS until vibration below 4 mm/s and noise below 2 gE ( MUHAIMIN & EVE AKPAN & ANDRI )
|
|
2025-10-06
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Fabrication plat form at bottom ER4
|
Fabrication platform for ER4 at workshop ( ANDRI & MUHAIMIN & DADANG & EDI )
|
|
2025-10-06
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-BF1
|
Compartement 1 south side leakage
|
Check at location found solenoid valve normal function ( MUHAIMIN & ANDRI & EVE AKPAN )
|
|
2025-10-06
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1
|
PMR Critical motor Area Kiln
|
Clean up area motor and filter motor. Measure vibration-noise-temperature for FS and LS motor. Add grease motor for FS and LS around 25 times and 30 times ( AGUS & DADANG & EVE RIZALDI )
|
|
2025-10-06
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1
|
PMR Critical motor Area RM
|
Clean up area motor and filter motor. Measure vibration-noise-temperature for FS and LS motor. Add grease motor for FS and LS around 10 times and 15 times ( EDI & ADI & EVE TEGAR )
|
|
2025-10-03
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-FN1-&-CEMS-ROOM-&-ER3
|
TPM Area 423 FN1 & CEMS Room & ER3
|
Take picture before TPM and make report TPM for dash board and save at computer ( RIZAL & AGUS )
|
|
2025-10-03
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Fabrication plat form at bottom ER4
|
Do fabrication plat form bottom ER4 at workshop ( ANDRI & DADANG )
|
|
2025-10-03
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-RF6
|
Install Motor
|
Install motor at 393 RF6, check ampere motor result ampere motor 2.7 A and 2.9 A from normal 0.9 A. Install original motor and install VSD in order reduce speed motor also pulling cable at ER4 test run motor base on production request for speed motor also measure ampere motor result ampere motor normal ( JAJAT & AGUS & RIZAL & ADI & ANDRI & MUHAIMIN & DADANG & EVE TEGAR )
|
|
2025-10-03
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-SC1
|
Issue motor oil gear leakage
|
Check at location found there is leakage oil from motor, also found nut at motor is not tight. Do tighten every nut motor and add silicone at part of leakage oil ( EDI & ADI & EVE TEGAR )
|
|
2025-10-02
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-SC1
|
Check motor oil gear leakage
|
Check at location, tighten nut of motor and do clean up area motor. Result not found leakage oil at motor ( EDI )
|
|
2025-10-02
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
BURNER-FLOOR
|
Lighting burner check and install new lighting
|
Check lighting at burner floor and install new lighting lamp ( AGUS & MUHAIMIN & DADANG )
|
|
2025-10-02
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Continue fabrication plat form at bottom ER4
|
Do fabrication plat form for bottom ER4 at workshop ( ANDRI & DADANG )
|
|
2025-10-02
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-BF1
|
Check purging not function
|
Replace 1 membran for purging because bad condition also service coil of solenoid valve and solenoid valve because function bad. Do replace nut for solenoid valve. Test function purging result normal ( RIZAL & EVE TEGAR & ANDRI )
|
|
2025-10-02
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1;-L63-RM1;-463-KL1
|
PMR IR TAD- T Scanner- CCTV - Camera Burner
|
Clean lens IR TAD, camera burner & Tscanner-flange probe-camera CCTV from dirty of dust use cleaning tools ( EDI & ADI )
|
|
2025-10-01
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Fabrication plat form at bottom ER4
|
Fabrication plat form at bottom ER4 ( ANDRI & DADANG )
|
|
2025-10-01
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Continue TPM report FI
|
Print out report FI last report and time line dash board with new form of TPM and install at dash board TPM at workshop ( ADI & EVE TEGAR )
|
|
2025-10-01
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ANALYZER-ROOM
|
Clean up area analyzer room
|
Do clean up area analyzer room from dirty dust and coal use broom and dustpan ( AIMAN )
|
|
2025-10-01
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
BURNER-FLOOR-AND-CLINKER-SILO
|
WBI hoist and crane
|
Do WBI hoist and crane area burner floor and clinker silo. Clean up area motor and test function move east-west south-north and up-down result function normal ( EDI & EVE RIZALDI )
|
|
2025-10-01
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-CC1
|
Observation area cooler ( issue Ground F ) from M33-WP4 with measurement result normal related other suspected
|
Do observation area cooler regarding issue ground F of M33 WP4 result normal function ( AGUS & MUHAIMIN )
|
|
2025-09-30
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-FN3
|
Signal cable S I/O is failure
|
Connected signal S of I/O for 393 FN3 test function signal result normal ( RIZAL & EVE TEGAR & CIVACON )
|
|
2025-09-30
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyzer
|
Clean up flange probe-sample line-filter sample inlet-diaphragm pump-dryer gas pump-filter balston from dirty of coal. Check humidity sensor function and filter humidity result function sensor normal and filter humidity good condition ( EDI & ADI )
|
|
2025-09-30
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-AND-BURNER-FLOOR
|
Continue relocation welding point and prepare cable connection burner point + Kiln
|
Do relocation welding point for kiln and burner floor and connection cable of welding point ( MUHAIMIN & DADANG )
|
|
2025-09-30
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-FN1
|
Replace sensor vibration with IFM
|
Do replace sensor vibration of N1 with IFM test function sensor result normal ( RIZAL & EVE TEGAR & CIVACON )
|
|
2025-09-29
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-AND-BURNER-FLOOR
|
Continue relocation welding point and prepare cable connection burner point and Kiln
|
Pulling cable and make connection at end side point ( MUHAIMIN & ANDRI & DADANG )
|
|
2025-09-29
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-463-KL1
|
PMR Service Critical Motor & LSR RM & CM1
|
Clean up area motor and filter motor. Measure vibration-noise-temperature for FS and LS motor. Add grease motor from 25 times-30 times and 35 times for FS and LS motor ( EDI & EVE RIZALDI )
|
|
2025-09-29
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe-probe-filter sample line-sample line-diaphragm pump-dryer gas pump-filter balston from dirty of dust. Check function humidity sensor and filter humidity, result function humidity good and filter humidity good condition ( RIZAL & EVE TEGAR )
|
|
2025-09-29
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Report also complete PMR and WBI September 2025
|
Re write PMR critical motor KILN and RM for 1st and 2nd weeks of september 2025 ( JAJAT & ADI )
|
|
2025-09-29
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER4
|
TPM ER4 repainting green color for floor
|
Repainting green color for floor at ER4 ( JAJAT & ADI )
|
|
2025-09-26
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Complete data check sheet PMR and WBI month of september 2025
|
Do complete data check sheet for PMR and WBI month of september 2025 ( ADI )
|
|
2025-09-26
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER4
|
Gemba TPM ER4
|
Clean area ER4 for south west from dirty of dust, install cover for panel trafo and tightening cover cable tray. Repainting door with red color, and floor of ER4 with yellow and red color. Move unsafe good inside ER4 to garbage tank, put support for cable to warehouse behind ER5 ( JAJAT & AGUS & RIZAL & EDI & ADI & ANDRI & AIMAN & MUHAIMIN & DADANG )
|
|
2025-09-26
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ELGA-2
|
Observation leaked ELGA 2
|
Service leaked at ELGA 2 result test function normal ( RIZAL & ANDRI )
|
|
2025-09-26
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Continue observation and wiring project L1C-TR1
|
Do wiring for project L1C TR1 ( JAJAT & AGUS )
|
|
2025-09-26
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
BURNER-FLOOR
|
Continue relocation welding point and prepare cable connection burner point
|
Do relocation welding point at burner floor and connect cable of welding point ( EDI & MUHAIMIN & DADANG )
|
|
2025-09-26
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER4
|
Gemba TPM ER4
|
Clean area ER4 for south west from dirty of dust, install cover for panel trafo and tightening cover cable tray. Repainting door with red color, and floor of ER4 with yellow and red color. Move unsafe good inside ER4 to garbage tank, put support for cable to warehouse behind ER5 ( JAJAT & AGUS & RIZAL & ADI & ANDRI & MUHAIMIN & AIMAN & DADANG )
|
|
2025-09-25
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1
|
Continue Welding Point + put panel welding near 463 MD1 + Prepare Cable connection
|
Install cable for panel welding at 463 KL1, put cable power at top side near panel welding note wait scafolding to pulling cable power ( MUHAIMIN & DADANG )
|
|
2025-09-25
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Continue observation and wiring project L1C-TR1
|
Do observation L1C-TR1 and wiring project tripper ( AGUS & EDI )
|
|
2025-09-25
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Complete data check sheet PMR and WBI month of september 2025
|
Do complete data check sheet PMR analyzer L63 2K1-L63 2K2-L63 2K3-483 2K1-463 2K1-443 2K1-423 2K1, PMR IR TAD-CCTV-Tscanner-Pyoremeter, PMR hoist & crane, WBI top blending-CT-PH-kiln, WBI bottom blending-kiln-cooler-clinker silo, WBI CM-Truck lift-BC transport-Tripper-Reclaimer coal, WBI feed bin-RM-CT-dust transport-BF month of september 2025 ( JAJAT & ADI )
|
|
2025-09-25
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Upload description L1C-TR1
|
Do upload description for L1C-TR1 and do laminating for file tripper at workshop ( RIZAL & EVE RIZALDI )
|
|
2025-09-24
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
CLINKER-SILO
|
Check + Add greasing + Clean up Motor Area Clinker
|
Check and clean up motor area clinker and add grease motor for FS and LS ( MUHAIMIN & DADANG )
|
|
2025-09-24
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1
|
PMR service analyser
|
Clean up flange probe-sample line-filter sample line-diaphragm pump-filter balston-dryer gas pump from dirty of coal. Check function humidity sensor and filter humidity result function sensor ok and filter humidity good condition ( ADI & MUHAIMIN & EVE RIZALDI )
|
|
2025-09-24
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-FN7
|
Support take motor 473-FN7 from vendor
|
Do support motor from vendor of 473-FN7 ( EDI & DADANG )
|
|
2025-09-24
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
PMR analyzer CEMS
|
Clean up purge air unit motor and filter purge air unit for Dust Hunter and Flowsic 100-swivel window dust hunter for T/R and R unit and transducer A & transducer B for Flowsic from dirty of dust. Do alignment dust hunter T/R and R dust hunter. Clean up CEMS room, CEMS gas room and filter cabinet MCS 100 E from dirty of dust ( RIZAL & ANDRI )
|
|
2025-09-24
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Continue observation and wiring project L1C-TR1
|
Do observation and wiring project for L1C-TR1 ( AGUS & EDI )
|
|
2025-09-23
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Continue Observation Project L1C-TR1
|
Do observation project for L1C TR1 ( JAJAT & AGUS )
|
|
2025-09-23
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP-&-463-KL1
|
Fabrication support lamp + Welding panel and install lighting lamp area kiln
|
Install lighting lamp at area kiln test on result lighting lamp normal on and make fabrication support lamp and welding panel at workshop ( MUHAIMIN & ANDRI & DADANG )
|
|
2025-09-23
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR service analyzer
|
Clean up flange probe-probe-filter sample line-sample line-diaphragm pump-dryer gas pump-filter balston from dirty of dust use instrument air supply. Check humidity sensor function and filter humidity result function humidity normal and filter humidity good condition. For 463 2K1 clean up motor and filter heat exchanger from dirtyof dust use instrument air supply ( EDI & ADI )
|
|
2025-09-22
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Continue wiring control Radio Link
|
Wiring control radio link. Ready to Install ( RIZAL )
|
|
2025-09-22
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1
|
Observation replacement lamp without cover area kiln
|
Do observation instalation lighting lamp without cover area kiln. Fabrication support for lighting lamp ( MUHAIMIN )
|
|
2025-09-22
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-KL1-&-473-CC1
|
PMR Critical motor Kiln and Cooler
|
Cleaning area motor and filter motor. Measure vibration-noise-temperature for FS and LS. Add grease motor for 35 times-30 times for FS and LS ( AGUS )
|
|
2025-09-22
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-RM1-&-L63-RM1
|
PMR Critical motor Raw Mill and Coal Mill
|
Cleaning area motor and filter motor. Measure vibration-noise-temperature for FS and LS. Add grease motor for 25 times-30 times for FS and LS ( RIZAL )
|
|
2025-09-22
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L3A-BC1
|
Lighting lamp off 2 each
|
Replace lighting lamp 2 unit with spare test on result lighting lamp ok ( ANDRI & DADANG )
|
|
2025-09-20
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Pulling cable 6P x 1.5 mm 3 line from tripper to I/O ER6
|
Pulling cable 6P x 1.5 mm 3 line around 250 m from tripper to I/O panel ER6 ( JAJAT & AGUS & RIZAL & ADI & MUHAIMIN & ANDRI & DADANG & AIMAN )
|
|
2025-09-19
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
IDO-TANK
|
Instalation pump
|
Check at location can not found motor at IDO tank base information from Mr.Jajat motor still at Mr.Nopayadi CBM ( ADI & MUHAIMIN )
|
|
2025-09-19
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Prepare + Wiring RD for L1C-TR1
|
Do prepare wiring radio link for L1C TR1 test function result ok
|
|
2025-09-19
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Install Support Welding point
|
Make support for welding panel at workshop ( ANDRI & DADANG )
|
|
2025-09-19
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L1C-TR1
|
Obsevation / prepare for pulling cable
|
Observation for job pulling cable at L1C TR1 ( AGUS & EDI & MUHAIMIN )
|
|
2025-09-18
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
443-PH1-CYCLONE-4
|
Add tubing cone C4A
|
Add tubing of cone C4A ( ANDRI & DADANG )
|
|
2025-09-18
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
ER3-&-ER4-
|
PMR Clean Up MCC ER
|
Clean up electric room 3 & electric 4 top and bottom side, MCC from dirty of dust use brush and mop electric room ( AIMAN )
|
|
2025-09-18
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
393-FV9
|
Check / install double tipping valve new control
|
Install double tipping valve for new control test function result normal ( EDI & MUHAIMIN )
|
|
2025-09-17
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-HC1
|
Service pipe lighting back of HC
|
Test on lighting lamp result normal lighting lamp area 473 HC1 all on ( AGUS & ADI & MUHAIMIN & DADANG )
|
|
2025-09-17
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
473-GQ1
|
Install lighting lamp north side
|
Make support lighting lamp at workshop. Install lighting lamp test on result lighting lamp normal ( AGUS & ADI & MUHAIMIN & DADANG )
|
|
2025-09-17
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Prepare box and PS 12 VDC 20A
|
Prepare box for power supply 12 VDC 20A, install power supply and cable power input bring panel to CCR server room give to Mr.Muklas ES ( MUHAIMIN & ADI )
|
|
2025-09-17
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
463-2K1-&-443-2K1
|
PMR Service Analyser
|
Clean up flange probe-probe-sample line-filter sample line-diaphragm pump-fiter balston-dryer gas pump from dirty of dust. Check function humidity sensor and filter humidity result function sensor normal and filter humidity good condition ( RIZAL & ANDRI & EVE HADIF & EVE RIZALDI )
|
|
2025-09-16
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-MD1
|
Clean up and check carbon brush
|
Clean up carbon brush room, measure long all carbon brush, replace 8 carbon brush with spare carbon brush ( AGUS )
|
|
2025-09-16
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
363-SR1
|
Observation cracked at base plate motor
|
Check at location found cracked at support 363 SR1 ( MUHAIMIN & DADANG )
|
|
2025-09-16
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
WORK-SHOP
|
Closing WO Electric 1
|
Do closing WO for date 8-9-25 to 12-9-25 ( ADI )
|
|
2025-09-16
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
L63-RM1-&-L1C-TR1-&-L1C-TL1
|
WBI Elect & Ins & Check I/O CM, Sump T&T
|
Do WBI electrical and instrumentation and check I/O coal mill, sump T&T. Measure vibration-noise motor FS and LS ( EDI )
|
|
2025-09-16
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-BL7-AND-473-FA2
|
Install lighting lamp
|
Install lighting lamp area blower and motor. Test on result ok lighting lamp on ( MUHAIMIN & DADANG )
|
|
2025-09-16
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
423-2K1
|
PMR Service CEMS
|
Clean up purge air unit motor and filter purge air unit, swivel window R unit & T/R unit of dust hunter also flange with tube and alignment dust hunter, transducer A & transducer B of flowsic, CEMS room, filter cabinet MCS 100 E and gas bottle room from dirty of dust ( RIZAL & ANDRI )
|
|
2025-09-15
1 year ago
|
NR.EL-01
|
Wahyu Adi Triono
|
483-BL5
|
Replace Motor & Cek Structure P
|
Check motor spare and replace motor ( AGUS & ADI & MUHAIMIN )
|