Detail NR2 ELEC/INST OVERHOUL
2026-08-07
364-RM1-474-CC1-444-PH1
Wahyu Adi Triono
Problem: Calibration pressure transmitter zero and span area RM-Cooler-PH
Action:
Do calibration zero and span for pressure transmitter area raw mill-cooler-preheater-coal mill totals 10 units note replace 1 unit  pressure transmitter 364 BF1 P1 range 0-150 mmH2O calibration result good because existing pressure transmitter check span output drop to 7 mA ( ADI & EVE TEGAR & UNJ AZRIEL )

Status: done
Back to report list