443-W1-M1&-443-WI1-M1
Wahyu Adi TrionoProblem: Issue motor high load. Prepare motor spare
Action:
Check name plate motor of 443 WI1 M1 and 443 WI1 M3 and cross check spare motor at warehouse result find motor 2P 45 KW do test run megger motor result good no load measure ampere R-S-T get value 10 until 12 ampere and put motor spare 443 WI M3 behind workshop electric 1 ( EDI & ADI & JAJAT )
Status: done