423-BF1-&-L63-HS1-&-443-2K2-&-483-PF1-&-453-PF1
Wahyu Adi Triono
Problem: Issue zero value is big around 2.2 mbar. Recalibration for zero adjust-issue sump pump area many water or sump pump not working-rewiring cable for reset continue test function reset and alarm humidity-calibration zero and span
Action:
Check indication pressure of 423 BF1 PDT 2002 value 2.2 to 2.3 mbar same with CCR operator. Bring down pressure transmitter do zero adjustment result indication become 0.0 mbar output 4.00 mA. Install pressure transmitter at site result indication  0.1 mbar compare CCR around 0.2 mbar-Check at location area sump pump at L63 HS1 found there is no water and sump pump working normal-Do rewiring cable for reset at 443 2K2 continue test function result good also test function for alarm humidity result good-Do calibration zero at 483 PF1 with running blower and calibration zero-span for 453 PF1 with running blower result calibration good ( JAJAT & EDI & ADI & DADANG )

Status: done