Detail NR ELEC/INST CR/RE/UTILITY & WORKSHOP
2024-04-17
D3A-PQ4
Bayu Kiln Saputro
Problem: trip breaker di MCC
Action:
Info shift motor cooling fan 1.1 OL disconnect kabel power
cek ulang tahanan coil motor dan tahanan isolasi OK balance
cek nilai induktance OK balance
coba reconnect kabel test ampere 2,8A, setting eocr 2.75
naikkan setting eocr ke 3A 
test run OK

Status: done