Detail NR ELEC/INST CR/RE/UTILITY & WORKSHOP
2024-03-02
ER-7A
Bayu Kiln Saputro
Problem: Manuver Power
Action:
Normal Power OTR-301
- OFF Outgoing OTR-301 All
- OFF Bustie 16, Rack Out ACB
- OFF Bustie 17, Rack Out ACB
- Rack In ACB Incoming OTR-301, ON ACB
- ON Outgoing OTR-301 All

* Saat ON ACB Incoming OTR-301, OCB OTR-301 OFF
* Relay 86 di panel incoming trip, Reset relay 86
* Hanya ada indikasi Alarm di Vamp, Reset
* Turunkan OLTC ke posisi tap 3
* ON OCB OTR-301, tunggu tegangan sampai 6300V
* ON ACB Incoming OTR-301


Status: done