OTR-302
Bayu Kiln SaputroProblem: Yearly Maintenance (OH)
Action:
- Bolt tightening dan tambal cover trafo yang rembes
- Bolt tightening kabel arrester 70 kV
- Function Test protection trafo
* Indikasi Bukholz 1 stage Alarm tidak ada di panel RCP, cek relay kerja, lampu indikasi mati
* Indikasi OLTC Oil Low Level aktif terus, cek kabel OK, cek kontak level switch rusak,
sementara di lepas kabelnya
-Energize Trafo
- Supervisi PT Megavolt
* Insulation Test After service
* Pasang kabel sisi HV dan LV
* Function Test
- Bolt tightening kabel arrester 70 kV
- Function Test protection trafo
* Indikasi Bukholz 1 stage Alarm tidak ada di panel RCP, cek relay kerja, lampu indikasi mati
* Indikasi OLTC Oil Low Level aktif terus, cek kabel OK, cek kontak level switch rusak,
sementara di lepas kabelnya
-Energize Trafo
- Supervisi PT Megavolt
* Insulation Test After service
* Pasang kabel sisi HV dan LV
* Function Test
Status: done