Detail NR ELEC/INST CR/RE/UTILITY & WORKSHOP
2024-02-22
MCC-COOLING-TOWER-NAR1
Bayu Kiln Saputro
Problem: Yearly Maintenance (OH)
Action:
Clean up trafo MV (6,3 kV) to LV (400 V)
- Ukur tahanan isolasi sisi HV to ground 
   RST to ground = 12,8 Gohm ; 14,6 Gohm ; 15,1 Gohm (inject 5000 V)
- Ukur tahanan isolasi sisi LV to ground = 520 Mohm (inject 500 V)
- Ukur tahanan isolasi sisi HV terhadap sisi LV = 63,3 Gohm (inject 2500 V)

Status: done