Detail NR1 ELEC/INST RM/KL/CM
2024-01-18
423-2K1-PMR-SERVICE-CEMS
Wahyu Adi Triono
Problem: CEMS analyzer are not service yet
Action:
Do service CEMS analyzer such as clean up filter purge air unit for dust hunter and flowsic 100 use instrument air, clean up swivel window dust hunter use cloth do alignment dust hunter for t/r unit and reflector unit, clean up transducer A and B flowsic 100 use iron brush and instrument air supply, clean up filter cabinet MCS 100 E use instrument air supply, do calibration zero and span FIDOR, do zero calibration MCS 100E ( RIZAL)

Status: done