Detail NR1 ELEC/INST RM/KL/CM
2023-12-29
363-MD1-PM-RAW-MILL-MEASURE-RMEGGER-LINE-TO-GROUND-AND-CLEAN-UP-CARBON-BRUSH-ROOM-FROM-DIRT-OF-DUSTESISTANCE-
Wahyu Adi Triono
Problem: Carbon brush room need to be clean up and resistance from line to ground need to be check with megger
Action:
Do clean up carbon brush room from dirt of dust process, continue measure resistance Line to Ground before and after clean up result for resistance every line to ground avaerage before 0.5 M Ohm after clean up average for line to ground  > 4000 M Ohm (AGUS & ADI)

Status: done
Back to report list