Bayu Kiln SaputroProblem: Trip Overload
Action:
- Tes bukaan valve in dan out by mekanik
- Resetting eocr sesuai pembacaan clampamp (set load eocr dari 3A ke 3.25A dng CT 100/5; dtime 10s; otime 5s)
- Cek ampere d mcc ok 59.5A saat bukaan valve in dan out 100% nameplate motor 61.3A
Status: done