Bayu Kiln SaputroProblem: Yearly maintenance (OH)
Action:
- Manuver load OTRA ke OTRB (bustie 20 closed)
- OFF OTRA
- OFF GIS to OTRA
- OFF DS BusA
- Grounding GIS OTRA
- Replace indicator lamp Receiving Panel OTRA
- Service acb all outgoing bus OTR-A
Service OTRA by quadro
- PI
- TTR
- winding Resistance
- dinamic resistance
Status: done